42
Audible
Alarm
Battery Mode
Sounds once every 1.5 seconds
Low Battery
Sounds once every 0.2 seconds
Overload
Sounds once every 3 seconds
Normal alarm
Sounds once every 3 seconds
Fault
Continuous tone
Protection
Short Circuit
Bypass mode : Breaker
Normal Mode : Output Breaker/Electronic Circuit
Battery Mode : Output Breaker/Electronic Circuit
Battery
ABDM
EPO
UPS shuts down immediately.
Over Temperature
Normal Mode :Transfer to Bypass Mode
Battery Mode : UPS shuts down immediately
Physical
Dimensions UPS (inches)
W x H x D ( mm)
6.1 x 10.2 x 15.9
(154 x 259 x 404)
6.1 x 10.2 x 15.9
(154 x 259 x 404)
6.7 x 11.3 x 17.4
(171 x 288 x 441)
7.6 x 12.6 x 21.8
(192 x 320 x 553)
Weight lbs. (kg)
27.1lb (12.3Kg)
33.1lb (15Kg)
47.4lb (21.5Kg) 67.2lb (30.5Kg)
Environme
ntal
Operating Temperature
Operating : 0ºC ~ 40ºC (32ºF to 104ºF)
Storage : -10ºC ~ 50ºC (14ºF to 122ºF)
Noise Level
≦
50dB
Relative Humidity
0-90% (without condensation)
Interface
Standard
RS-232, USB Port, EPO/ROO,RJ11/RJ45 Surge Protection,
(UPS Bundled UPSilon2000 Software)
Option
2ndRS-232, RS485, Dry Contact Closure, Mega
SNMP/HTTP Agent & Peripherals Only
Compatible Platforms
Microsoft Windows series, Linux, Mac, etc.
Standards
and
Certificatio
ns
Safety
UL1778 V4 ( cTUVus )
EMC
FCC Part 15 Class A
Markings
FCC , cTUVus
*
1000 VA
1500 VA
2000 VA
3000 VA
120V:1000VA,900W,PF=0.9
115V:1000VA,900W,PF=0.9
110V:1000VA,900W,PF=0.9
100V:1000VA,900W,PF=0.9
120V:1500VA,1350W,PF=0.9
115V:1450VA,1230W,PF=0.85
110V:1380VA,1180W,PF=0.86
100V:1250VA,1060W,PF=0.85
120V:2000VA,1800W,PF=0.9
115V:1910VA,1700W,PF=0.89
110V:1830VA,1610W,PF=0.88
100V:1650VA,1460W,PF=0.88
120V:3000VA,2700W,PF=0.9
115V:2920VA,2620W,PF=0.9
110V:2795VA,2500W,PF=0.9
100V:2540VA,2230W,PF=0.88
* The UPS Communication software may be downloaded from Battery Backup Power, Inc. at:
https://www.backupbatterypower.com