Bypass Supply
<
105
%
continuous
106-120
%
for 250 seconds shuts down
121-130
%
for 125 seconds shuts down
131-135
%
for 50 seconds shuts down
136-145
%
for 20 seconds shuts down
146-148
%
for 5 seconds shuts down
149-157
%
for 2 seconds shuts down
158-176
%
for 1 seconds shuts down
177-187
%
for 0.32 seconds shuts down
>
188
%
for 0.16 seconds shuts down.
Buzzer continuously alarms.
Efficiency
( Full Linear
Load )
Line mode
(Rating 120Vac)
>90%
>91%
>91%
>92%
Battery mode
(12Vdc/pcs)
>87%
>87%
>87%
>87%
ECO mode
(Rating 120Vac)
>97%
Battery
Number of batteries
2
3
4
6
Battery type
12 V/9Ah Sealed, non-spillage, maintenance-free, lead acid
Rated Battery Voltage
24 VDC
36 VDC
48 VDC
72 VDC
Backup time
(Linear Load)
50%
Load
>9min
>9min
>9min
>9min
70%
Load
>5min 30sec >5min 30sec >5min 30sec >5min 30sec
100%
Load
>3 min
>3 min
>3 min
>3min
Charger
Charge
Current (Max.)
Standard
1.8 A
1.8 A
1.6A
1.4 A
Supplementary
Charger
(Max.)
Optional
3.1A
3.1A
3.1A
3.1A
Recharge time
(to 90%)
4hr
4hr
4hr
4hr
Floating Mode Charging
Voltage
27.3Vdc
±
1
%
40.95 dc
±
1
%
54.6Vdc
±
1
%
81.9Vdc
±
1
%
Bulk Mode Charging
Voltage
28.2Vdc
±
1
%
42.3Vdc
±
1
%
56.4Vdc
±
1
%
84.6Vdc
±
1
%
DC leakage current
≤
30 µA with no AC applied and the unit in the off position
Transfer
time
AC to DC
0 ms
Inverter to Bypass
2.5 ms (Typical)
0 ms (Typical)
DC start
startup in battery mode
during a power failure
Yes
Self
Diagnostics
Upon Power-on, Front Panel Setting & Software Control, 24
hours routine check
Programma
ble outlet
Programmable relay
support 2 outlets
Front Panel
LCD (Standard)
LED (Optional)
Normal, Battery, Bypass, Self-Test, Battery Weak & Bad,
Site Wiring Fault , Fault, Overload, and Load/Battery Level
Programmable Outlet1/ Programmable Outlet2
4 Button (Optional)
ON / OFF / Select / Silence
6 Button (Standard)
ON(Silence) / OFF / Enter / Function / UP / Down