Baso BG1600M Installation Instructions Manual Download Page 2

 

2

    BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions 

Location Considerations

Choose a location that provides the shortest, direct 
cable route to the spark electrode, pilot burner/igniter-
sensor assembly. Easy access to the terminals is 
desired for wiring and servicing. The control may be 
mounted in any position. Mount the control on a 
grounded metal surface with #6 sheet metal or 
machine screws through the mounting holes provided 
in the enclosure. 

The pilot burner/igniter-sensor must be securely 
mounted to the main burner to ensure that the pilot 
burner flame remains properly positioned with respect 
to the main burner flame. The pilot burner must be 
located such that the flame receives an ample supply 
of air, free from the products of combustion. The flame 
must not be exposed to draft conditions, the full force 
of main burner ignition, or falling scale, which could 
otherwise impede ignition of main burner flame. 

Securely mount the pilot burner/igniter-sensor to the 
main burner with metal screws at a distance 
approximately 3/8 in (9.52 mm) above and 1/4 in. (6.35 
mm) away from the center of the nearest main burner 
port. Ensure that the main burner flames do not 
impinge on any part of the pilot burner. 

Wiring 

!

  WARNING:

 

Risk of Explosion or Fire. 

Locate all safety, limit, and operating controls in 
series with the thermostat terminal (TH) on the 
ignition control. Improper installation may cause gas 
leaks, which can lead to an explosion or fire and 
may result in severe personal injury or death.

 

 
Refer to Figure 1 for wiring diagrams. All wiring should 
be in accordance with the National Electrical Code 
(NEC) and all other local codes and regulations. 

Check the voltage rating marked on the control and 
make sure it is suited to the application. Use a Class 2 
transformer capable of providing 24 VAC under 
maximum load, including valves. A transformer having 
excessive primary impedance due to poor coupling 
affects the ignition potential. 

The high-voltage spark transformer cable is noise 
suppression (resistive) type rated for at least 15kV and 
must not be in continuous contact with a metal 
surface. Use standoff insulators. Ensure that the flame 
sensor wire and high voltage spark transformer cable 
are separated from one another by a minimum of 
1/4 in. (6.35 mm) and are not wrapped around any 
pipe, other wiring, or accessories. 

!

  WARNING:

 

Risk of Electric Shock. 

Before applying power to the control, connect the 
high voltage cable to the spark transformer terminal 
and spark electrode (pilot burner assembly). Verify 
the ground wire is attached to the pilot burner and 
the control ground terminal strip. Failure to follow 
this procedure can cause electric shock and may 
result in severe personal injury or death. 

The BG1600M replaces existing intermittent pilot 
ignition controls with the following specifications: 

 

flame detection using flame rectification 
technology (ability of a flame to conduct and 
rectify current) 

 

1 trial for ignition 

 

dual rod (remote sense) flame sensing 

 

100% shutoff/lockout with none or 5 minutes 
continuous retry 

 

trial time for ignition is 85 seconds 

 

prepurge period of none or 15 seconds 

 

interpurge period of 15 seconds 

 

main burner 400,000 Btu/hr maximum 

 

pilot burners with flow rates of 1,500 Btu/hr or 
less 

 

must be used with redundant gas valves and 
not subjected to temperatures below 
-40˚F (-40˚C) or above 170˚F (77˚C) 

Summary of Contents for BG1600M

Page 1: ...Explosion or Fire Do not install the control in an area that is exposed to water for example dripping spraying rain Do not use the control if it has been exposed to water Exposure to water may cause...

Page 2: ...ould be in accordance with the National Electrical Code NEC and all other local codes and regulations Check the voltage rating marked on the control and make sure it is suited to the application Use a...

Page 3: ...in the flame for proper sensing signal Pilot Burner Ignitor Flame Sensor 6 GND 24V R O SW Rollout Switch PV MV Figure 1 Wiring for 2 Rod Flame Sense with Rollout Switch Rollout Switch Function The ro...

Page 4: ...24V THS 2 Connect To 4 24V TH PV 1 Connect To 5 PV MV 3 Connect To 6 MV R O SWH R1 Connect To 7 R O SW SENSE 4 Connect To 8 SENSE NC none NC none 9 INTERN SPARK Rajah Connect To 10 SPARK NOTE NC means...

Page 5: ...sful ignition at least five times 10 Return the thermostat to a normal temperature setting before leaving the installation WARNING The control module can not be serviced by user If any faults are dete...

Page 6: ...he pilot valve will be shut off Lockout will occur if your model has no retry For models with retry the control will wait for 5 minutes and then begin another trial for ignition sequence Table 1 LED I...

Page 7: ...Sensor tip is in the flame For proper sensing the rod tip must be 3 8 10 mm to 1 2 13 mm in the Flame 7 Check Flame Sensor is wired to terminal 8 SENSE and terminal 2 GND BURNER 8 Check that the sense...

Page 8: ...eturns to the idle state Wait 0 1 second checking memory and relay driver circuits OK Flame on Yes No Flame off 0 7 second Turn pilot and main gas valves off wait 0 7 second inter purge blinking LED o...

Page 9: ...t pin 2 3 shorting plug to damper No Spark wire and electrode OK Replace module Replace spark wire or electrode Yes Yes No Pilot flame does not light 24V between PV and GND terminals Replace module Ga...

Page 10: ...clear If all OK replace main valve Yes No Replace module Yes Yes No Gas at main burner Adjust pilot flame size and position or replace pilot burner or main burner After main is lit do valves turn off...

Page 11: ...sonally should be checked before shutdown and again before the next use Consequence of Unexpected Shutdown Where the cost of an unexpected shutdown would be high the system should be checked more ofte...

Page 12: ...A40A 602H 24 Resistive Wire Harness with 2 1 4 Terminals bag of 1 WHA40A 603D 24 Resistive Wire Harness with 1 1 4 Terminal and 1 Rajah Terminal box of 25 WHA40A 603H 24 Resistive Wire Harness with 1...

Page 13: ...BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions 13 Notes...

Page 14: ...14 BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions Notes...

Page 15: ...perating and Storage Temperature 40 to 170 F 40 to 77 C Humidity 95 RH noncondensing Type of Gas Natural Liquefied Petroleum LP Manufactured Mixed or LP Gas Air Mixture Packaging Individual pack 1 per...