Baso BG1600M Installation Instructions Manual Download Page 11

 

BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions    

11

 

Maintenance Requirements in Severe 
Environments 

Regular preventive maintenance is important in any 
application, but especially so in commercial cooking, 
agricultural, and industrial applications because: 

 

In many such applications, particularly 
commercial cooking, the equipment operates 
100,000 to 200,000 cycles per year. Such heavy 
cycling can wear out the gas control in one to 
two years. A normal forced air furnace, for which 
the controls were originally intended, typically 
operates less than 20,000 cycles per year. 

 

Exposure to water, dirt, chemicals, and heat can 
damage the ignition control module or the gas 
control and shut down the control system. A 
NEMA 4 enclosure can reduce exposure to 
environmental contaminants. 

!

  WARNING:

 

Risk of Explosion or Fire. 

Do 

not attempt to take the ignition control module apart 
or to clean it. Improper reassembly and cleaning 
may cause unreliable operation, which can lead to 
an explosion or fire, and may result in severe injury, 
property damage or death.

 

Maintenance frequency must be determined 
individually for each application. Some considerations 
are: 

 

Cycling Frequency – Appliances that may cycle 
more than 20,000 times annually should be 
checked monthly. 

 

Intermittent Use – Appliances that are used 
seasonally should be checked before shutdown 
and again before the next use. 

 

Consequence of Unexpected Shutdown – 
Where the cost of an unexpected shutdown 
would be high, the system should be checked 
more often. 

 

Dust, Wet, or Corrosive Environment – Since 
these environments can cause the controls to 
deteriorate more rapidly, the system should be 
checked more often. 

Repairs and Replacement 

!

  CAUTION:

 

Risk of Electric Shock. 

Disconnect power supply before making electrical 
connections to avoid electric shock.

 

 

!

  WARNING:

 

Risk of Explosion or Fire. 

Shut off the gas supply at the main manual shutoff 
valve before installing or servicing the control. 
Failure to shut off the gas supply can result in the 
release of gas during installation or servicing, which 
can lead to an explosion or fire, and may result in 
severe injury or death.

 

 

!

  WARNING:

 

Risk of Explosion, Fire, or 

Electric Shock. 

Label all wires before they are 

disconnected when replacing or servicing the 
BG1600M. Wiring errors can cause improper or 
dangerous operation and may result in an explosion, 
fire, or electric shock leading to severe personal 
injury or death.

 

Field repairs must not be made to the BG1600M 
control. Any attempt to repair this assembly voids the 
manufacturer’s warranty. For a replacement control, 
contact the original equipment manufacturer or the 
nearest BASO Gas Products distributor. 

All other accessories, such as flame sensors, 
electrode assembles, pilot assemblies, and leads can 
be obtained through the original equipment 
manufacturer or a  BASO Gas Products distributor. 

 

 

Summary of Contents for BG1600M

Page 1: ...Explosion or Fire Do not install the control in an area that is exposed to water for example dripping spraying rain Do not use the control if it has been exposed to water Exposure to water may cause...

Page 2: ...ould be in accordance with the National Electrical Code NEC and all other local codes and regulations Check the voltage rating marked on the control and make sure it is suited to the application Use a...

Page 3: ...in the flame for proper sensing signal Pilot Burner Ignitor Flame Sensor 6 GND 24V R O SW Rollout Switch PV MV Figure 1 Wiring for 2 Rod Flame Sense with Rollout Switch Rollout Switch Function The ro...

Page 4: ...24V THS 2 Connect To 4 24V TH PV 1 Connect To 5 PV MV 3 Connect To 6 MV R O SWH R1 Connect To 7 R O SW SENSE 4 Connect To 8 SENSE NC none NC none 9 INTERN SPARK Rajah Connect To 10 SPARK NOTE NC means...

Page 5: ...sful ignition at least five times 10 Return the thermostat to a normal temperature setting before leaving the installation WARNING The control module can not be serviced by user If any faults are dete...

Page 6: ...he pilot valve will be shut off Lockout will occur if your model has no retry For models with retry the control will wait for 5 minutes and then begin another trial for ignition sequence Table 1 LED I...

Page 7: ...Sensor tip is in the flame For proper sensing the rod tip must be 3 8 10 mm to 1 2 13 mm in the Flame 7 Check Flame Sensor is wired to terminal 8 SENSE and terminal 2 GND BURNER 8 Check that the sense...

Page 8: ...eturns to the idle state Wait 0 1 second checking memory and relay driver circuits OK Flame on Yes No Flame off 0 7 second Turn pilot and main gas valves off wait 0 7 second inter purge blinking LED o...

Page 9: ...t pin 2 3 shorting plug to damper No Spark wire and electrode OK Replace module Replace spark wire or electrode Yes Yes No Pilot flame does not light 24V between PV and GND terminals Replace module Ga...

Page 10: ...clear If all OK replace main valve Yes No Replace module Yes Yes No Gas at main burner Adjust pilot flame size and position or replace pilot burner or main burner After main is lit do valves turn off...

Page 11: ...sonally should be checked before shutdown and again before the next use Consequence of Unexpected Shutdown Where the cost of an unexpected shutdown would be high the system should be checked more ofte...

Page 12: ...A40A 602H 24 Resistive Wire Harness with 2 1 4 Terminals bag of 1 WHA40A 603D 24 Resistive Wire Harness with 1 1 4 Terminal and 1 Rajah Terminal box of 25 WHA40A 603H 24 Resistive Wire Harness with 1...

Page 13: ...BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions 13 Notes...

Page 14: ...14 BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions Notes...

Page 15: ...perating and Storage Temperature 40 to 170 F 40 to 77 C Humidity 95 RH noncondensing Type of Gas Natural Liquefied Petroleum LP Manufactured Mixed or LP Gas Air Mixture Packaging Individual pack 1 per...

Reviews: