1-4
BE1-51 General Information
9137200997 Rev D
Style Number Identification Chart
(Figure 1-1) illustrates the manner in which the relay style number is
determined. For example, if the style number were
H3E-Z1P-B2C1F,
the device would have the following
characteristics:
H
- Three-Phase-and-Neutral
sensing
3
-
Sensing input range of 1.5 to 12.0 amperes for phase and 0.5 to 4.0 amperes for neutral
E
-
Normally open outputs
Z1
-
Switch selectable time curves
P
-
Operating power derived from 125 Vdc or 120 Vac
B
-
Current operated targets
2
-
Two instantaneous elements
C
- Push-to-energize
outputs
1
-
Normally open auxiliary timed output relay
F
- Semi-flush
mounting
Figure 1-1. Style Number Identification Chart