Table 1-2. Power Supplies
Input Voltage
Type
Nominal Range
Burden at Nominal
J (mid range)
125 Vdc
120 Vac
24 to 150 Vdc
90 to 132 Vac
5.0 W
12.2 VA
K (mid range)
48 Vdc
24 to 150 Vdc
4.8 W
L (low range)
24 Vdc
12 to 32 Vdc
∗
4.9 W
Z (high range)
250 Vdc
240 Vac
68 to 280 Vdc
90 to 270 Vac
5.3 W
14.4 VA
∗
Type L power supply may require 14 Vdc to begin operation. Once operating, the voltage may be
reduced to 12 Vdc.
Output Circuits
Resistive Ratings
120 Vac:
Make, break, and carry 7 Aac continuously
250 Vdc:
Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously, and
break 0.3 Adc
500 Vdc:
Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously, and
break 0.3 Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc:
Break 0.3 A (L/R = 0.04)
Isolation
In accordance with IEC 255-5 and ANSI/IEEE C37.90, one minute dielectric (high potential) tests as
follows:
All circuits to ground:
2,121 Vdc
Input to output circuits: 1,500 Vac or 2121 Vdc
Radio Frequency Interference (RFI)
Maintains proper operation when tested for interference in accordance with IEEE C37.90.2-1987,
Standard Withstand Capability of Relay Systems to Radiated Electromagnetic Interference from
Transceivers.
Surge Withstand Capability
Qualified to ANSI/IEEE C37.90.1-1989
Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems.
Fast Transient
Qualified to ANSI/IEEE C37.90.1-1989.
Impulse Test
Qualified to IEC 255-5.
Temperature
Operating Range
-40
°
C (-40
°
F) to 70
°
C (158
°
F)
Storage Range
-65
°
C (-85
°
F) to 100
°
C (212
°
F)
Summary of Contents for BE1-50BF
Page 2: ......
Page 8: ...vi BE1 50BF Introduction 9190600990 Rev F This page intentionally left blank...
Page 10: ...ii BE1 50BF General Information 9190600990 Rev F This page intentionally left blank...
Page 18: ...ii BE1 50BF Controls and Indicators 9190600990 Rev F This page intentionally left blank...
Page 22: ...2 4 BE1 50BF Controls and Indicators 9190600990 Rev F This page intentionally left blank...
Page 24: ...ii BE1 50BF Functional Description 9190600990 Rev F This page intentionally left blank...
Page 28: ...3 4 BE1 50BF Functional Description 9190600990 Rev F This page intentionally left blank...
Page 30: ...ii BE1 50BF Installation 9190600990 Rev F This page intentionally left blank...
Page 34: ...4 4 BE1 50BF Installation 9190600990 Rev F Figure 4 3 Outline Dimensions Front View Case Cover...
Page 42: ...4 12 BE1 50BF Installation 9190600990 Rev F This page intentionally left blank...
Page 44: ...ii BE1 50BF Testing 9190600990 Rev F This page intentionally left blank...
Page 46: ...5 2 BE1 50BF Testing 9190600990 Rev F This page intentionally left blank...