![Basler BE1-27 Instruction Manual Download Page 8](http://html1.mh-extra.com/html/basler/be1-27/be1-27_instruction-manual_2707483008.webp)
GENERAL INFORMATION
1-3
Figure 1-2. Style Number Identification Chart
SAMPLE STYLE NUMBER
The style number identification chart above illustrates the manner in which a relay's style number is
determined. For example, if the model number is BE1-27/59 and the style number is A3F E1J AOS1F the
device has the following features:
A) Single-phase voltage sensing
3) Sensing input compatible with a pickup adjustment range of 55 to 160 Vac
F) Two normally open output relays (one per function)
E1) Definite timing for each function
J) Operating power derived from a 125 Vdc or 100/120 Vac source
A) Two internally operated target indicators (one per function)
O) No instantaneous functions
S) Push-to-energize outputs (pushbuttons)
1) Two normally open auxiliary output relays (one per function)
F) Semi-flush mounting
Summary of Contents for BE1-27
Page 22: ...4 4 INSTALLATION Figure 4 3 S1 Case Single Ended Projection Mount Outline Dimensions Side View...
Page 24: ...4 6 INSTALLATION Figure 4 5 S1 Case Double Ended Projection Mount Outline Dimensions Side View...
Page 26: ...4 8 INSTALLATION Figure 4 7 S1 Case Single Ended Projection Mount Outline Dimensions Rear View...
Page 29: ...INSTALLATION 4 11 Figure 4 10 S1 Case Panel Drilling Diagram Semi Flush Mounting...
Page 32: ...4 14 INSTALLATION Figure 4 13 BE1 27 Internal Connections...
Page 33: ...INSTALLATION 4 15 Figure 4 14 BE1 59 Internal Connections...
Page 34: ...4 16 INSTALLATION Figure 4 15 BE1 27 59 Internal Connections...