9424200994 Rev U
Synchronizer (25A) Test
BE1-11
g
Step 3: Increase the phase voltage source until OUT4 begins pulsing. This should occur immediately
but reaches the maximum width/interval period when the source is raised above approximately
74.48 V.
Step 4: Pulse width at the maximum period should be verified by measuring the elapsed time between
when the contact closes and when it opens. The measured length should be 5 s
±
33.3 ms.
Step 5: Pulse interval should be verified by measuring the elapsed time between when a contact opens
and when it closes. The measured length should be 10 s
±
50 ms.
Step 6: Decrease the phase voltage source until OUT5 begins pulsing. This should occur immediately
but reaches the maximum width/interval period when the source is raised above approximately
58.89 V.
Step 7: Repeat Steps 4 and 5.
Step 8: (Optional) Repeat Steps 2 through 7 for Settings Group 1, 2, and 3.
Frequency Raise/Lower Proportional Output Verification
Step 1: Use BESTCOMS
Plus
to monitor the status of OUT2 (Lower) and OUT3 (Raise).
Step 2: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11
g
terminals C13
(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,
∠
0
°,
to terminals C17 (Vx-phase) and C18 (Vx-neutral). OUT2 and OUT3
should be open.
Step 3: Slowly increase the frequency of the phase voltage source until OUT2 begins pulsing. This
should occur immediately but reaches the maximum width/interval period when the source is
raised above approximately 60.4 Hz.
Step 4: Pulse width should be verified by measuring the elapsed time between when the contact closes
and when it opens. The measured length should be 10 s
±
50 ms.
Step 5: Pulse interval should be verified by measuring the elapsed time between when a contact opens
and when it closes. The measured length should be 5 s
±
33.3 ms.
Step 6: Decrease the phase voltage source until OUT5 begins pulsing. This should occur immediately
but reaches the maximum width/interval period when the source is lowered below approximately
59.6 Hz.
Step 7: Repeat Steps 4 and 5.
Step 8: (Optional) Repeat Steps 2 through 5 for Settings Group1, 2, and 3.
Breaker Close Attempts/Sync Fail Activation Delay Verification
Step 1: Use BESTCOMS
Plus
to verify the settings in Table 241 and set the logic in Figure 330 above.
Step 2: Prepare to monitor the status of OUT1 (Close Breaker) and OUT8 (Sync Fail).
Step 3: Connect a balanced, three-phase voltage source of 69.28 Vpn, 60 Hz to BE1-11
g
terminals C13
(A-phase), C14 (B-phase), C15 (C-phase), and C16 (neutral). Apply a single-phase, 60-hertz
voltage of 69.28 Vpn,
∠
0
°,
to terminals C17 (Vx-phase) and C18 (Vx-neutral).
Step 4: Connect a contact sensing input to terminals B3 (IN2+) and B4 (IN2-).
Step 5: Apply contact sensing voltage to IN2 to initiate a close attempt and cause OUT1 to close.
CAUTION: Applying voltage above the capabilities of the BE1-11
g
power supply can cause
irreversible damage to the BE1-11
g
. Consult the
Specifications
chapter for more information on
contact input voltage ranges.
Step 6: OUT1 should close two more times for a total of three close attempts. OUT8 should close
approximately 5 seconds after the third close attempt.
Step 7: (Optional.) Repeat Steps 2 through 6 for Settings Group 1, 2, and 3.
Summary of Contents for BE1-11g
Page 2: ......
Page 21: ...9424200994 Rev U 9 BE1 11g Introduction Figure 1 Style Chart...
Page 22: ...10 9424200994 Rev U Introduction BE1 11g...
Page 36: ...24 9424200994 Rev U Quick Start BE1 11g...
Page 44: ...32 9424200994 Rev U Controls and Indicators BE1 11g...
Page 54: ...42 9424200994 Rev U Contact Inputs and Outputs BE1 11g...
Page 62: ...50 9424200994 Rev U Overexcitation 24 Protection BE1 11g...
Page 68: ...56 9424200994 Rev U Sync Check 25 Protection BE1 11g...
Page 74: ...62 9424200994 Rev U Phase Undervoltage 27P Protection BE1 11g...
Page 82: ...70 9424200994 Rev U Negative Sequence Voltage 47 Protection BE1 11g...
Page 88: ...76 9424200994 Rev U Phase Overvoltage 59P Protection BE1 11g...
Page 94: ...82 9424200994 Rev U Auxiliary Overvoltage 59X Protection BE1 11g...
Page 96: ...84 9424200994 Rev U Stator Ground 64G Protection BE1 11g...
Page 100: ...88 9424200994 Rev U Vector Jump 78V Protection BE1 11g...
Page 106: ...94 9424200994 Rev U Frequency 81 Protection BE1 11g...
Page 150: ...138 9424200994 Rev U Power 32 Protection BE1 11g...
Page 154: ...142 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Protection BE1 11g...
Page 158: ...146 9424200994 Rev U Distance 21 Protection BE1 11g...
Page 170: ...158 9424200994 Rev U Resistance Temperature Detector 49RTD Protection BE1 11g...
Page 174: ...162 9424200994 Rev U Analog Input Protection BE1 11g...
Page 192: ...180 9424200994 Rev U Logic Timers 62 BE1 11g...
Page 198: ...186 9424200994 Rev U Breaker Control Switch 101 BE1 11g...
Page 206: ...194 9424200994 Rev U Setting Groups BE1 11g...
Page 236: ...224 9424200994 Rev U Alarms BE1 11g...
Page 238: ...226 9424200994 Rev U Differential Reporting BE1 11g...
Page 248: ...236 9424200994 Rev U Demands BE1 11g...
Page 250: ...238 9424200994 Rev U Load Profile BE1 11g...
Page 254: ...242 9424200994 Rev U Power Quality BE1 11g...
Page 262: ...250 9424200994 Rev U Trip Circuit Monitor 52TCM BE1 11g...
Page 272: ...260 9424200994 Rev U BESTnet Plus BE1 11g Figure 188 Power Quality Page...
Page 274: ...262 9424200994 Rev U Mounting BE1 11g Figure 190 J Type Case Side Dimensions...
Page 282: ...270 9424200994 Rev U Mounting BE1 11g Figure 198 H1 Rack Mount Case Dimensions...
Page 283: ...9424200994 Rev U 271 BE1 11g Mounting Figure 199 H1 Panel Mount Case Dimensions...
Page 289: ...9424200994 Rev U 277 BE1 11g Mounting Figure 206 Dovetailing Procedure...
Page 290: ...278 9424200994 Rev U Mounting BE1 11g...
Page 298: ...286 9424200994 Rev U Terminals and Connectors BE1 11g...
Page 304: ...292 9424200994 Rev U Typical Connections BE1 11g...
Page 324: ...312 9424200994 Rev U BESTCOMSPlus Software BE1 11g...
Page 344: ...332 9424200994 Rev U BESTlogic Plus BE1 11g...
Page 354: ...342 9424200994 Rev U Communication BE1 11g Figure 263 Modbus Mapping Screen...
Page 370: ...358 9424200994 Rev U Timekeeping BE1 11g...
Page 374: ...362 9424200994 Rev U Device Information BE1 11g...
Page 392: ...380 9424200994 Rev U Configuration BE1 11g...
Page 396: ...384 9424200994 Rev U Introduction to Testing BE1 11g...
Page 408: ...396 9424200994 Rev U Commissioning Testing BE1 11g...
Page 422: ...410 9424200994 Rev U Sync Check 25 Test BE1 11g...
Page 426: ...414 9424200994 Rev U Phase Undervoltage 27P Test BE1 11g...
Page 442: ...430 9424200994 Rev U Phase Overvoltage 59P Test BE1 11g...
Page 454: ...442 9424200994 Rev U Auxiliary Overvoltage 59X Test BE1 11g...
Page 458: ...446 9424200994 Rev U Vector Jump 78V Test BE1 11g...
Page 466: ...454 9424200994 Rev U Frequency 81 Test BE1 11g...
Page 496: ...484 9424200994 Rev U Inverse Overcurrent 51 Test BE1 11g...
Page 516: ...504 9424200994 Rev U Phase Current Differential 87 Test BE1 11g...
Page 520: ...508 9424200994 Rev U Neutral Current Differential 87N Test BE1 11g...
Page 526: ...514 9424200994 Rev U Power 32 Test BE1 11g...
Page 530: ...518 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Test BE1 11g...
Page 534: ...522 9424200994 Rev U Distance 21 Test BE1 11g...
Page 560: ...548 9424200994 Rev U Virtual Control Switches 43 Test BE1 11g...
Page 570: ...558 9424200994 Rev U Logic Timers 62 Test BE1 11g...
Page 584: ...572 9424200994 Rev U Troubleshooting BE1 11g...
Page 614: ...602 9424200994 Rev U Specifications 25 Hz Operation BE1 11g BESTlogic Plus Update Rate cycle...
Page 672: ...660 9424200994 Rev U RTD Module BE1 11g...
Page 694: ...682 9424200994 Rev U BESTCOMSPlus Settings Loader Tool BE1 11g...
Page 705: ......