228
9424200994 Rev U
Breaker Monitoring
BE1-11
g
edit this value at the front-panel display. To view the breaker status using BESTCOMS
Plus
, use the
Metering Explorer to open the Control, Breaker Control Switch tree branch.
The breaker operations counter can be monitored to give an alarm when the value exceeds a threshold.
See
Breaker Alarms
in this chapter for more information about this feature.
Breaker duty monitoring is discussed in the following paragraphs.
Breaker Duty Monitoring
When the breaker opens, the current interrupted in each pole of the circuit breaker is accumulated by the
breaker duty monitor. Breaker opening is defined by the breaker status monitoring function (Breaker
Status). Figure 158 illustrates breaker status during a fault and protective trip. Table 86 serves as a
legend for the call-outs of Figure 158.
Each time the breaker trips, the breaker duty monitor updates two sets of registers for each pole of the
breaker. In the Accumulated
I
Duty registers, the breaker duty monitor adds the measured current in
primary amperes. In the Accumulated
I
2
Duty registers, the function adds the measured current in
primary amperes squared. The user selects which of the two sets of duty registers are reported and
monitored when setting up the breaker duty monitor.
Even though duty register values are calculated and stored in primary amperes or primary amperes-
squared, the duty value is reported as a percent of maximum. The user sets the value that the BE1-11
g
will use for 100 percent duty (D
MAX
). The value set for maximum duty is used directly for reporting the
accumulated
I
Duty. The square of the value set for maximum duty is used for reporting the accumulated
I
2
duty.
Since the true measure of contact wear includes a factor for arcing time (t), an assumed arcing time for
the breaker should be included when choosing the setting for 100 percent interruption duty (D
MAX
).
When testing the BE1-11
g
by injecting currents, the values in the duty registers should be read and
recorded prior to the start of testing. Once testing is complete and the BE1-11
g
is returned to service, the
registers should be reset to the original pre-test values. A block accumulation logic input can be used
when testing so that simulated breaker duty is not added to the duty registers. The Block logic input of the
breaker duty function is an OR logic term (e.g., IN1 or OUT5) which blocks the breaker monitoring logic
when true (1). Block is set to zero to disable blocking. When breaker monitoring is blocked (logic
expression equals 1), breaker duty is not accumulated.
Summary of Contents for BE1-11g
Page 2: ......
Page 21: ...9424200994 Rev U 9 BE1 11g Introduction Figure 1 Style Chart...
Page 22: ...10 9424200994 Rev U Introduction BE1 11g...
Page 36: ...24 9424200994 Rev U Quick Start BE1 11g...
Page 44: ...32 9424200994 Rev U Controls and Indicators BE1 11g...
Page 54: ...42 9424200994 Rev U Contact Inputs and Outputs BE1 11g...
Page 62: ...50 9424200994 Rev U Overexcitation 24 Protection BE1 11g...
Page 68: ...56 9424200994 Rev U Sync Check 25 Protection BE1 11g...
Page 74: ...62 9424200994 Rev U Phase Undervoltage 27P Protection BE1 11g...
Page 82: ...70 9424200994 Rev U Negative Sequence Voltage 47 Protection BE1 11g...
Page 88: ...76 9424200994 Rev U Phase Overvoltage 59P Protection BE1 11g...
Page 94: ...82 9424200994 Rev U Auxiliary Overvoltage 59X Protection BE1 11g...
Page 96: ...84 9424200994 Rev U Stator Ground 64G Protection BE1 11g...
Page 100: ...88 9424200994 Rev U Vector Jump 78V Protection BE1 11g...
Page 106: ...94 9424200994 Rev U Frequency 81 Protection BE1 11g...
Page 150: ...138 9424200994 Rev U Power 32 Protection BE1 11g...
Page 154: ...142 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Protection BE1 11g...
Page 158: ...146 9424200994 Rev U Distance 21 Protection BE1 11g...
Page 170: ...158 9424200994 Rev U Resistance Temperature Detector 49RTD Protection BE1 11g...
Page 174: ...162 9424200994 Rev U Analog Input Protection BE1 11g...
Page 192: ...180 9424200994 Rev U Logic Timers 62 BE1 11g...
Page 198: ...186 9424200994 Rev U Breaker Control Switch 101 BE1 11g...
Page 206: ...194 9424200994 Rev U Setting Groups BE1 11g...
Page 236: ...224 9424200994 Rev U Alarms BE1 11g...
Page 238: ...226 9424200994 Rev U Differential Reporting BE1 11g...
Page 248: ...236 9424200994 Rev U Demands BE1 11g...
Page 250: ...238 9424200994 Rev U Load Profile BE1 11g...
Page 254: ...242 9424200994 Rev U Power Quality BE1 11g...
Page 262: ...250 9424200994 Rev U Trip Circuit Monitor 52TCM BE1 11g...
Page 272: ...260 9424200994 Rev U BESTnet Plus BE1 11g Figure 188 Power Quality Page...
Page 274: ...262 9424200994 Rev U Mounting BE1 11g Figure 190 J Type Case Side Dimensions...
Page 282: ...270 9424200994 Rev U Mounting BE1 11g Figure 198 H1 Rack Mount Case Dimensions...
Page 283: ...9424200994 Rev U 271 BE1 11g Mounting Figure 199 H1 Panel Mount Case Dimensions...
Page 289: ...9424200994 Rev U 277 BE1 11g Mounting Figure 206 Dovetailing Procedure...
Page 290: ...278 9424200994 Rev U Mounting BE1 11g...
Page 298: ...286 9424200994 Rev U Terminals and Connectors BE1 11g...
Page 304: ...292 9424200994 Rev U Typical Connections BE1 11g...
Page 324: ...312 9424200994 Rev U BESTCOMSPlus Software BE1 11g...
Page 344: ...332 9424200994 Rev U BESTlogic Plus BE1 11g...
Page 354: ...342 9424200994 Rev U Communication BE1 11g Figure 263 Modbus Mapping Screen...
Page 370: ...358 9424200994 Rev U Timekeeping BE1 11g...
Page 374: ...362 9424200994 Rev U Device Information BE1 11g...
Page 392: ...380 9424200994 Rev U Configuration BE1 11g...
Page 396: ...384 9424200994 Rev U Introduction to Testing BE1 11g...
Page 408: ...396 9424200994 Rev U Commissioning Testing BE1 11g...
Page 422: ...410 9424200994 Rev U Sync Check 25 Test BE1 11g...
Page 426: ...414 9424200994 Rev U Phase Undervoltage 27P Test BE1 11g...
Page 442: ...430 9424200994 Rev U Phase Overvoltage 59P Test BE1 11g...
Page 454: ...442 9424200994 Rev U Auxiliary Overvoltage 59X Test BE1 11g...
Page 458: ...446 9424200994 Rev U Vector Jump 78V Test BE1 11g...
Page 466: ...454 9424200994 Rev U Frequency 81 Test BE1 11g...
Page 496: ...484 9424200994 Rev U Inverse Overcurrent 51 Test BE1 11g...
Page 516: ...504 9424200994 Rev U Phase Current Differential 87 Test BE1 11g...
Page 520: ...508 9424200994 Rev U Neutral Current Differential 87N Test BE1 11g...
Page 526: ...514 9424200994 Rev U Power 32 Test BE1 11g...
Page 530: ...518 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Test BE1 11g...
Page 534: ...522 9424200994 Rev U Distance 21 Test BE1 11g...
Page 560: ...548 9424200994 Rev U Virtual Control Switches 43 Test BE1 11g...
Page 570: ...558 9424200994 Rev U Logic Timers 62 Test BE1 11g...
Page 584: ...572 9424200994 Rev U Troubleshooting BE1 11g...
Page 614: ...602 9424200994 Rev U Specifications 25 Hz Operation BE1 11g BESTlogic Plus Update Rate cycle...
Page 672: ...660 9424200994 Rev U RTD Module BE1 11g...
Page 694: ...682 9424200994 Rev U BESTCOMSPlus Settings Loader Tool BE1 11g...
Page 705: ......