9424200994 Rev U
491
BE1-11
g
Directional Overcurrent (67) Test
panel display. Note that 50-2 can also be set to operate for calculated IN (3I0) while still being
polarized by VXIG. Verify operation by repeating steps 25 and 26 with 50-2 set for 3I0 operate.
Verify that there is a 50-2-67-Residual target on the front-panel display.
Step 29: Set Zero Sequence Mode to VXIN on the Protection, Current, Directional (67-1) screen. The
polarizing reference quantities are an external source of 3V0 applied at the VX input compared
to the calculated IN (3I0) quantity. Apply polarity of a single-phase voltage source (30 Vac at
nominal frequency) to terminal C17 and non-polarity to C18 at an angle of 180 degrees lagging.
An angle of 180 degrees is used to simulate a broken delta voltage where polarity to non-
polarity is 180 degrees out of phase with, for example, the A-phase current during an A-phase
to ground fault. The BE1-11
g
internally compensates for the 180-degree phase difference such
that polarity voltage from the broken delta source connected to polarity of the BE1-11
g
results in
a 0-degree condition for a Forward fault. To verify, connect A-phase current in series with IG
current. That is, polarity current should go in D1 out D2 and in D7 out D8 if IG is available.
Repeat steps 25 and 26 with 50-2 set for 3I0 operate. Verify that there is a 50-2-67-Residual
target on the front-panel display. Note that 50-2 can also be set to operate for measured
independent ground (IG) while still being polarized by VXIN. Verify operation by repeating steps
25 and 26 with 50-2 set for 3I0 operate. Verify that there is a 50-2-67-Residual target on the
front-panel display.
Step 30: Repeat steps 4 through 29 for "Reverse Polarization." BE1-11
g
operation will occur 180
degrees away from the Positive and Negative Sequence torque angle (both at 80 degrees or
260 degrees I lags E in our example). Verify that the output contacts remain closed from 170
through 260 to 350 degrees I lags E.
Step 31: (Optional.) Repeat steps 4 through 30 for 50-4, 50-5, and 50-6. Setup commands and
associated operational setting Tables must be modified accordingly.
Step 32: (Optional.) Repeat steps 4 through 31 for settings group 1, 2, and 3.
Step 33: (Optional.) Repeat steps 1 through 33 with CT Circuit 2 selected as the CT source for the
instantaneous overcurrent (50) and directional overcurrent (67) elements, and 67-2 as the
directional source, for protection systems equipped with two sets of CTs. In Step 1, D7 with F7,
D8 with F8.
Zero-Sequence Current Polarization
Use setup commands in Table 217. Using Table 223 as a guide, send the settings to the BE1-11
g
.
Table 223. Directional, Current-Polarizing, Neutral Operational Settings
Setting
Value
BESTCOMSPlus Screen
Description
Polarization
Method
IG=checked
Q=unchecked
V=unchecked
Protection, Current, Directional
(67-1)
Selects zero sequence
current polarization
Pickup
0 A
Protection, Current, Instantaneous
Overcurrent (50-1)
Sets 50-1 pickup to 0 amps
Pickup
2.0 A
Protection, Current, Instantaneous
Overcurrent (50-2)
Sets 50-2 pickup to 2.0
amps
Pickup
0 A
Protection, Current, Instantaneous
Overcurrent (50-3)
Sets 50-3 pickup to 0 amps
Step 1: Apply 2 Aac current at 0 degrees to the independent ground input IG, terminals D7 (polarity)
and D8 (non-polarity). No ac voltage is required for this test.
Step 2: From a second current source, apply 0 amp A-phase current at an angle of 0 degrees and
slowly increase the current until OUT2 closes. Decrease A-phase current until OUT2 just drops
out. Pickup will occur within
±
2% of the 50-2 pickup setting (1.96 A to 2.04 A). Dropout will
occur at approximately 95% of the actual pickup value. Verify that there is a 50-2-67-Residual
target on the front-panel display.
Summary of Contents for BE1-11g
Page 2: ......
Page 21: ...9424200994 Rev U 9 BE1 11g Introduction Figure 1 Style Chart...
Page 22: ...10 9424200994 Rev U Introduction BE1 11g...
Page 36: ...24 9424200994 Rev U Quick Start BE1 11g...
Page 44: ...32 9424200994 Rev U Controls and Indicators BE1 11g...
Page 54: ...42 9424200994 Rev U Contact Inputs and Outputs BE1 11g...
Page 62: ...50 9424200994 Rev U Overexcitation 24 Protection BE1 11g...
Page 68: ...56 9424200994 Rev U Sync Check 25 Protection BE1 11g...
Page 74: ...62 9424200994 Rev U Phase Undervoltage 27P Protection BE1 11g...
Page 82: ...70 9424200994 Rev U Negative Sequence Voltage 47 Protection BE1 11g...
Page 88: ...76 9424200994 Rev U Phase Overvoltage 59P Protection BE1 11g...
Page 94: ...82 9424200994 Rev U Auxiliary Overvoltage 59X Protection BE1 11g...
Page 96: ...84 9424200994 Rev U Stator Ground 64G Protection BE1 11g...
Page 100: ...88 9424200994 Rev U Vector Jump 78V Protection BE1 11g...
Page 106: ...94 9424200994 Rev U Frequency 81 Protection BE1 11g...
Page 150: ...138 9424200994 Rev U Power 32 Protection BE1 11g...
Page 154: ...142 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Protection BE1 11g...
Page 158: ...146 9424200994 Rev U Distance 21 Protection BE1 11g...
Page 170: ...158 9424200994 Rev U Resistance Temperature Detector 49RTD Protection BE1 11g...
Page 174: ...162 9424200994 Rev U Analog Input Protection BE1 11g...
Page 192: ...180 9424200994 Rev U Logic Timers 62 BE1 11g...
Page 198: ...186 9424200994 Rev U Breaker Control Switch 101 BE1 11g...
Page 206: ...194 9424200994 Rev U Setting Groups BE1 11g...
Page 236: ...224 9424200994 Rev U Alarms BE1 11g...
Page 238: ...226 9424200994 Rev U Differential Reporting BE1 11g...
Page 248: ...236 9424200994 Rev U Demands BE1 11g...
Page 250: ...238 9424200994 Rev U Load Profile BE1 11g...
Page 254: ...242 9424200994 Rev U Power Quality BE1 11g...
Page 262: ...250 9424200994 Rev U Trip Circuit Monitor 52TCM BE1 11g...
Page 272: ...260 9424200994 Rev U BESTnet Plus BE1 11g Figure 188 Power Quality Page...
Page 274: ...262 9424200994 Rev U Mounting BE1 11g Figure 190 J Type Case Side Dimensions...
Page 282: ...270 9424200994 Rev U Mounting BE1 11g Figure 198 H1 Rack Mount Case Dimensions...
Page 283: ...9424200994 Rev U 271 BE1 11g Mounting Figure 199 H1 Panel Mount Case Dimensions...
Page 289: ...9424200994 Rev U 277 BE1 11g Mounting Figure 206 Dovetailing Procedure...
Page 290: ...278 9424200994 Rev U Mounting BE1 11g...
Page 298: ...286 9424200994 Rev U Terminals and Connectors BE1 11g...
Page 304: ...292 9424200994 Rev U Typical Connections BE1 11g...
Page 324: ...312 9424200994 Rev U BESTCOMSPlus Software BE1 11g...
Page 344: ...332 9424200994 Rev U BESTlogic Plus BE1 11g...
Page 354: ...342 9424200994 Rev U Communication BE1 11g Figure 263 Modbus Mapping Screen...
Page 370: ...358 9424200994 Rev U Timekeeping BE1 11g...
Page 374: ...362 9424200994 Rev U Device Information BE1 11g...
Page 392: ...380 9424200994 Rev U Configuration BE1 11g...
Page 396: ...384 9424200994 Rev U Introduction to Testing BE1 11g...
Page 408: ...396 9424200994 Rev U Commissioning Testing BE1 11g...
Page 422: ...410 9424200994 Rev U Sync Check 25 Test BE1 11g...
Page 426: ...414 9424200994 Rev U Phase Undervoltage 27P Test BE1 11g...
Page 442: ...430 9424200994 Rev U Phase Overvoltage 59P Test BE1 11g...
Page 454: ...442 9424200994 Rev U Auxiliary Overvoltage 59X Test BE1 11g...
Page 458: ...446 9424200994 Rev U Vector Jump 78V Test BE1 11g...
Page 466: ...454 9424200994 Rev U Frequency 81 Test BE1 11g...
Page 496: ...484 9424200994 Rev U Inverse Overcurrent 51 Test BE1 11g...
Page 516: ...504 9424200994 Rev U Phase Current Differential 87 Test BE1 11g...
Page 520: ...508 9424200994 Rev U Neutral Current Differential 87N Test BE1 11g...
Page 526: ...514 9424200994 Rev U Power 32 Test BE1 11g...
Page 530: ...518 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Test BE1 11g...
Page 534: ...522 9424200994 Rev U Distance 21 Test BE1 11g...
Page 560: ...548 9424200994 Rev U Virtual Control Switches 43 Test BE1 11g...
Page 570: ...558 9424200994 Rev U Logic Timers 62 Test BE1 11g...
Page 584: ...572 9424200994 Rev U Troubleshooting BE1 11g...
Page 614: ...602 9424200994 Rev U Specifications 25 Hz Operation BE1 11g BESTlogic Plus Update Rate cycle...
Page 672: ...660 9424200994 Rev U RTD Module BE1 11g...
Page 694: ...682 9424200994 Rev U BESTCOMSPlus Settings Loader Tool BE1 11g...
Page 705: ......