Deseo Cresnet
Manual
11
/
17
v0.6
© 2020 basalte
Digital inputs:
<
IsHeating
>
Indicates that the system is heating. A high signal will highlight the
flame symbol in heating mode.
High/1 = Heat running; Low/0 = System not running
Digital inputs:
<
IsCooling
>
Indicates that the system is cooling. A high signal will highlight the
snowflake symbol in cooling mode.
High/1 = Cool running; Low/0 = System not running
Digital inputs:
<
Fan_Low_FB
>
<
Fan_Mid_FB
>
<
Fan_High_FB
>
<
Fan_Auto_FB
>
<
Fan_Off_FB
>
Selects the fan mode on the rising edge of the input. The fan state is
visible in the upper left corner of the display.
High/1 (rising edge) = Select fan mode; Low/0 = no effect
Digital outputs:
<
Fan_Low
>
<
Fan_Mid
>
<
Fan_High
>
<
Fan_Auto
>
<
Fan_Off
>
Reports the current fan mode after the fan mode button is pressed.
High/1 = Fan mode selected; Low/0 = Fan mode not selected
Analog input:
<
External_Temperature
>
Receives the room temperature from an external sensor. If enabled in
the
‘
Basalte Deseo Configuration
’
module the temperature can be
displayed on the start screen of the Deseo.
This value is ignored if the internal sensor is used.
Analog output:
<
Internal_Temperature
>
Reports the ambient room temperature in tenths of a degree Celsius
or Fahrenheit.
Depending of the report type, the temperature will be updated every
60 seconds, or on every temperature change of 0.5° Celsius. (equal to
0.9° Fahrenheit)
The temperature format and report type can be set using the
‘
Basalte
Deseo Configuration
’
module.