Commissioning
Technical data subject to change.
05/2020
EN 37/45
7.1
Final Inspection
Check the following requirements before commissioning the device:
Only open the terminal compartment with terminals for the supply and data line(s) once it
has been ensured that no potentially explosive atmosphere is present and that the power
supply has been turned off.
POLARIS Remote
–
Has the reinforcement frame between the bracket and enclosure been inserted?
–
Is there no damage to seals, cable connections or glass panel?
–
Are the supply and data line(s) correctly wired?
–
Is the PE connection correctly earthed?
–
Have the supply and data line(s) been tightened in the screw terminals?
–
Are all terminal compartments closed?
–
Have all cable glands been tightened and all open cable entries closed with
blanking plugs?
Local Unit
–
Is the network box connected to the local unit via patch cable?
–
Are the data lines for USB, DVI and the power pack connected?
Only start the POLARIS (if a potentially explosive atmosphere is present) once the final
inspection has been carried out.