Table L: Selecting the appropriate monitoring equipment:
Base your selection on the number and type of trace heating circuits to be installed, the type of continuity monitoring you need. and the area
classification:
TABLE L: Monitoring Equipment Selection Recommendations
Heating circuit type
Application
Monitoring options
Suitable BARTEC monitoring product
Quantity required
Self-regulating heating circuits on pipes
Freeze protection
High profile end seal or
signal light for indication
ELS-200
ELL-200
1 per circuit
Self-regulating heating circuits on pipes
Temperature maintenance or
tight temperature control
High profile end seal
ELS-200
1 per circuit
→ Example
The application is temperature maintenance (25 °C) of a pipe in a hazardous area.
The maintenance team wants to be able to quickly locate the end seal.
appropriate monitoring equipment = ELS-200
Step 13: Finalize the required Materials List (BOM):
Accessories including the glass tape for attachment and pipe straps for the components and electrical traced warning labels
→ Example
Heating cable catalog no. (see Step 1-5 beginning on page 6) and required length (see Step 9 on page 16) =
Temperature control device including power connection enclosure (see Step 12 on page 18)
High profile end seal for ease of maintenance (see Step 12 on page 18) =
Accessories (see section Accessories in the manual of the product):
Glass cloth tape (see selection table in section Accessories in the manual of the product)
Pipe straps (see selection table in section Accessories in the manual of the product)
Electrically traced warning labels (see section Accessories in the manual of the product)
10PSB2-CT
PBTW-200-E
ELS-200
GT-164
PC-1
HTWL-EN
64 m
1 pc.
1 pc.
1 rolls
4 pcs.
16 pcs.