background image

Orange (277VAC) or Red (347VAC)
Black (120VAC)
White (Com)

LED 

Indicator

Transformer

LED 

Indicator

 

Electrical Connections

All electrical connections should be made inside the 

J-box. Make electrical connection as follows:

Note: 

Cap unused leads to prevent shorting.

AC Only or With Battery Models (Fig. 5 and 6)

120, 277, or 347VAC

White - Common

Black - 120VAC

Orange - 277VAC

or Red - 347VAC

Two Circuit Input (2CI) Models (Fig. 7)

2CI option models 

have two inputs, one for the AC 

input and the other for the auxiliary input. Please 

make connections as follows:

105-360VAC Line 

 

Auxiliary Line

White - Common 

 

Blue - Common

Black - 105-360VAC 

 

Brown - 105-360VAC

External DC Supply Models (Fig. 8)

If emergency power from an external DC power 

supply is desired, make connections as follows:

120, 277, or 347VAC   

External DC Supply

White - Common 

 

Purple - Negative

Black - 120VAC  

 

Yellow - 6-24VDC

Orange - 277VAC

or Red - 347VAC

Note: 

The AC and auxiliary power cannot be 

           simultaneously live, consult factory for a 

           solution.

NiCad Battery

Fig. 5 - AC Only

Fig. 6 - With Battery

Fig. 7 - Two Circuit Input (2CI)

2CI Relay

Generator/UPS

Brown (105-360VAC)

Blue (Com)

Utility Power

Black (105-360VAC)
White (Com)

Fig. 8 - External DC Supply

Orange (277VAC) or Red (347VAC)
Black (120VAC)
White (Com)

Yellow (6-24VDC)
Purple (Negative)

External DC Supply

LED 

Indicator

Transformer

Transformer

PCB/LED Board

PCB/LED Board

PCB/LED Board

PCB/LED Board

Orange (277VAC) or Red (347VAC)
Black (120VAC)
White (Com)

LED 

Indicator

Transformer

CP-EX Series

Installation Instructions

10070224 

R

EV 1 - 07/20

   

3

800-533-3948 www.barronltg.com

Summary of Contents for Exitronix CP-EX Series

Page 1: ...ns if applicable Do not mount near gas or electrical heaters Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product li...

Page 2: ...ote For large units the battery batteries may be shipped separate from the housing Install the battery batteries into the housing and make the appropriate battery connections 8 If desired remove appropriate chevrons Chevrons are made of 2 layers of self adhesive vinyl To remove manuver a utility knife underneath the desired chevron so that both layers of vinyl are penetrated Carefully peel the che...

Page 3: ...emergency power from an external DC power supply is desired make connections as follows 120 277 or 347VAC External DC Supply White Common Purple Negative Black 120VAC Yellow 6 24VDC Orange 277VAC or Red 347VAC Note The AC and auxiliary power cannot be simultaneously live consult factory for a solution NiCad Battery Fig 5 AC Only Fig 6 With Battery Fig 7 Two Circuit Input 2CI 2CI Relay Generator UP...

Page 4: ...supplied to the EXIT sign A flashing green LED indicates that the EXIT sign is undergoing a test A flashing red and green LED indicates that the battery is under high charge A red LED indicates whenever the Self diagnostics system has detected a fault condition Refer to the chart below when the red UNIT ALERT LED is blinking Test Button Features LED TEST Pressing and holding the test button for 3 ...

Reviews: