Self-Test/Self-Diagnostics (G2)

Operation

The purpose of this option is to provide Self-testing and Self-diagnostic capabilities to the EXIT sign. At predetermined 

intervals, the EXIT sign will automatically switch into battery mode. Refer to the 

Self-Test Features

 section of this page for 

timing details. The EXIT sign will also perform various Self-diagnostic tests of the unit. Visual signaling will alert maintenance 

personnel to a fault of the EXIT sign electronics, battery and/or battery charger. The circuitry continuously monitors the 

operating condition of the EXIT sign and battery charging circuit/battery supply voltage. Refer to the 

LED Indicator 

section 

below for fault reporting details.

Self-Test Features

• The EXIT sign will automatically switch to battery mode every month for a period of 5 minutes.

• The EXIT sign will automatically switch to battery mode twice, 24 hours apart, every 6 months for a period of 90 

  minutes.

LED Indicator

The unit is equipped with a bi-color LED, which displays green and/or red.

• A steady green LED indicates that normal AC power is being supplied to the EXIT sign.

• A flashing green LED indicates that the EXIT sign is undergoing a test.

• A flashing red and green LED indicates that the battery is under high charge.

• A red LED indicates whenever the Self-diagnostics system has detected a fault condition. 

  Refer to the chart below when the red “UNIT ALERT” LED is blinking:

Test Button Features

LED TEST – Pressing and holding the test button for 3 seconds will test the LEDs.  The LED indicator will blink red 3 times.

MANUAL TEST – Pressing the test button will switch the unit into battery mode for a set amount of time. The desired length 

of the test is determined by the number of times the test button is pressed.

• Pressing the test button once will switch the unit into battery mode for a period of 2 seconds.

• Pressing the test button twice within 2 seconds will switch the unit into battery mode for a period of 15 minutes.

Pressing and holding the test button for 5 seconds while the unit is MANUAL TEST mode will cancel the manual test and 

return the unit to normal AC power.

Use in accordance with local building codes.

Red LED Indication

Steady

Blinking 1 Time

Blinking 2 Times

Blinking 3 Times

Unit Fault

Battery Disconnected

Battery Failure

Battery Charge Failure

LED Failure

Corrective Action

Check Battery then Consult Factory

Replace Battery

Check Battery then Consult Factory
Check Battery then Consult Factory

Summary of Contents for Exitronix CP-EX Series

Page 1: ...ns if applicable Do not mount near gas or electrical heaters Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product li...

Page 2: ...ote For large units the battery batteries may be shipped separate from the housing Install the battery batteries into the housing and make the appropriate battery connections 8 If desired remove appropriate chevrons Chevrons are made of 2 layers of self adhesive vinyl To remove manuver a utility knife underneath the desired chevron so that both layers of vinyl are penetrated Carefully peel the che...

Page 3: ...emergency power from an external DC power supply is desired make connections as follows 120 277 or 347VAC External DC Supply White Common Purple Negative Black 120VAC Yellow 6 24VDC Orange 277VAC or Red 347VAC Note The AC and auxiliary power cannot be simultaneously live consult factory for a solution NiCad Battery Fig 5 AC Only Fig 6 With Battery Fig 7 Two Circuit Input 2CI 2CI Relay Generator UP...

Page 4: ...supplied to the EXIT sign A flashing green LED indicates that the EXIT sign is undergoing a test A flashing red and green LED indicates that the battery is under high charge A red LED indicates whenever the Self diagnostics system has detected a fault condition Refer to the chart below when the red UNIT ALERT LED is blinking Test Button Features LED TEST Pressing and holding the test button for 3 ...

Reviews: