Self-Test/Self-Diagnostics (G2)

Operation

The purpose of this option is to provide Self-testing and Self-diagnostic capabilities to the emergency unit. At predeter-

mined intervals, the emergency unit will automatically switch into battery mode. Refer to the 

Self-Test Feature

 section 

below for timing details. The emergency unit will also perform various Self-diagnostic tests to determine if there are any 

faults.  Visual signaling will alert maintenance personnel to a fault of the emergency unit electronics, battery, and/or 

battery charger.  The circuitry continuously monitors the operating condition of the emergency unit and battery charging 

circuit/battery supply voltage. Refer to the 

LED Indicator

 section below for fault reporting details.

Self-Test Feature

• The emergency unit will automatically switch to battery mode every

 30 days for a period of 5 minutes.

• The emergency unit will automatically switch to battery mode every

 6 months for a period of 90 minutes.

LED Indicator

The LED indicator of the emergency unit will display a visual signal indicating the status of the unit.  Refer to the table 

below for LED indication conditions:

Test Button Features

MANUAL TEST – Pressing the test button will switch the unit into battery mode for a set amount of time. The desired 

length of the test is determined by the number of times the test button is pressed.

• Pressing the test button once will switch the unit into battery mode for a period of 2 seconds.

• Pressing and holding the test button until the LED indicator turns orange will switch the unit into battery mode for a 

  period of 5 minutes.

• Pressing and holding the test button until the LED indicator flashes red/green will switch the unit into battery mode 

  for a period of 90 minutes.

Pressing the test button once while the unit is MANUAL TEST mode will cancel the manual test and return the unit to 

normal AC power.

RESET – Pressing the test button 3 times will reset the red “UNIT ALERT” LED. If multiple faults are present, it may be 

necessary to repeat this procedure for each remaining fault indicated by the “UNIT ALERT” LED.

Use in accordance with local building codes.

LED Indication

Steady
Pulse
Steady
Pulse

Steady

Pulse
LED Color

LED Color

Green
Green
Red
Red

Orange

Orange

Red/Green

Unit Condition

Float Charge
Hi-Rate Charge

Low Batt Voltage

Emer Lamp Failure

No AC Power

Charge Failure

5 Minute Test
Batt Disconnected
90 Minute Test

Comment

Batt Fully Charged
Batt Under High-Rate Charge
Replace Battery

Check AC Connection

Replace Transformer

5 Min Test Every 30 Days
Check Batt Connections
90 Min Test Every 6 Months

Replace Damaged or 

Missing Lamps

 

CP-EMW Series

Installation Instructions

10070140 

R

EV 5 - 02/21

4

800-533-3948 www.barronltg.com

Summary of Contents for CP-EMW Series

Page 1: ...near gas or electric heaters Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for other than int...

Page 2: ...rovided 5 For additional mounting support remove additional knockouts and use appropriate hardware for mounting surface Fig 3 6 All electrical connections should be made inside the junction box Make electrical connections as follows 120VAC 277VAC White Common White Common Black 120VAC Orange 277VAC Green Ground Green Ground Note Cap unused leads to prevent shorting 7 Secure the battery using the v...

Page 3: ... 1 2 1 in length not provided 4 Unit can be installed using steel banding for routing around the poles and I beam Standard banding 3 4 in width or less can be used not provided 5 Follow steps 6 10 under Wall Mount Fig 5 Fig 4 Backplate Gasket Steel Band Not provided Universal Bracket Option POLE OR I BEAM MOUNTING POLE OR I BEAM MOUNTING Weatherproof Seal Steel Band Not provided Conduit Access Plu...

Page 4: ...of time The desired length of the test is determined by the number of times the test button is pressed Pressing the test button once will switch the unit into battery mode for a period of 2 seconds Pressing and holding the test button until the LED indicator turns orange will switch the unit into battery mode for a period of 5 minutes Pressing and holding the test button until the LED indicator fl...

Reviews: