23
4.
While the unit is flushing, the “UNIT FLUSHING” and
“OPERATING/STBY” LED lights will remain lit and
membrane pressure will drop.
5.
The flush can be terminated at any time by pressing
the flush button.
Resetting the Carbon Timer
The red “Replace Carbon Filter” light on your control panel
illuminates when it is time to replace the carbon filter. This
light illuminates after the operation time reaches the chlorine
level set point.
1.
Press the “CARBON” button on the control panel.
2.
Press the “ENTER/RESTART” button while the
“Replace Carbon Filter” LED light is blinking to reset
the carbon timer.
Resetting the Membrane Timer
The red “Replace Membrane” light on your control panel illu-
minates when it is time to replace the membrane. The mem-
brane light illuminates after approximately 12 months of use.
1.
Press the “MEMBRANE” button on the control panel.
2.
The “Replace Membrane” LED light will begin blink-
ing.
3.
Press the “ENTER/RESTART” button while the
“Replace Membrane” LED light is blinking to reset
the membrane timer.
Pressure Gauges
There are 4 pressure gauges on the DIamond RO. The func-
tions of the gauges are to provide you the necessary informa-
tion, to monitor system performance as well as when certain
maintenance procedures should be accomplished. The pres-
sure gauges are located in the inside of the right front door.
The 4 gauge functions are as follows:
1.
Prefilter Inlet—
Provides you with incoming water
pressure and is used in conjunction with the prefilter
outlet gauge to determine when it is time to change
the prefilter.
N
ORMAL
O
PERATION
Note
Sustained exposure to high chlorine
levels can damage the RO mem-
brane(s). It is highly recommended
to replace the carbon filter when
indicated by the “Replace Carbon
Filter” LED.
Summary of Contents for DIamond 1265 Series
Page 2: ...2 ...