INSTALLATION 

PAGE 7 

Wiring Your Outputs 

Refer to Figure 2 for details of output pinouts. 

 

Figure 2  Output Connections 

 

The four output relays can be programmed for either manual remote 
control or to automatically indicate an internal status of the Cv3. Internal 
statuses available are ‘new alarm present’, ‘any alarm present’, a pulsed 
output when an acknowledgement is received or as a system alarm. When 
used for status indicators, specific relays are assigned as follows: 

 

Relay 1  New Alarm 

 

Relay 2  Any Alarm 

 

Relay 3  Acknowledge Received 

 

Relay 4  System Error 

 
Two contacts from each relay are brought to the terminal block. The idle 
state of the contacts (either normally open or normally closed) is selectable 
in programming.  

 

 

 

Summary of Contents for B1277-HSPA

Page 1: ...Installation Operation Manual March 2017 Rev 4 1 200 550 71st Avenue SE Phone 403 255 9544 Calgary Alberta Canada Fax 403 259 2343 T2H 0S6 www barnettprotalk com email sales barnettprotalk com...

Page 2: ......

Page 3: ...YOUR OUTPUTS 7 5 PROGRAMMING 8 PROGRAMMING WITH A PC 8 PROGRAMMING WITH A HANDSET 9 HANDSET PROGRAMMING CODES 10 6 TESTING THE INSTALLATION 25 7 OPERATIONS 26 8 SPECIFICATIONS 31 9 TECHNICAL DRAWINGS...

Page 4: ...ng a remote telephone for control of external equipment Configuration of the ProTalk Cv3 can be accomplished using the dedicated PC application Additionally limited programming can be done using a loc...

Page 5: ...der who will provide you with a Mobile Identification Number MIN Additionally to program the Cv3 and the embedded transceiver one of the following is required Standard telephone set with DTMF keypad o...

Page 6: ...put voltages between 8 and 30 volts DC The internal battery is limited to 1 4Ahr if you require a larger battery capacity please contact our sales office for alternative battery options Since a Cv3 eq...

Page 7: ...sales office if your needs exceed the limits of this antenna as we may be able to supply or recommend an appropriate substitute Installation using a two way radio or public address system The radio po...

Page 8: ...0 Technical drawings have been provided on page 40 for your reference In addition to the standard detection of an alarm state at the input a digitally formatted input can also be configured as an intr...

Page 9: ...volts DC and 0 to 30 volts DC For analog voltage operation connect the signal to the single terminal for inputs 1 through 6 and the terminal for inputs 7 through 10 Inputs 7 through 10 are also capab...

Page 10: ...al statuses available are new alarm present any alarm present a pulsed output when an acknowledgement is received or as a system alarm When used for status indicators specific relays are assigned as f...

Page 11: ...e time If you are using the USB connection you will need to install the drivers found on the installation CD Select USB Driver Update from the CD Menu This will launch the USB driver application Selec...

Page 12: ...Programming For a remote session call in to the B1277 from your touch tone telephone set When answering an incoming call this unit responds depending on the previously programmed Security Level settin...

Page 13: ...d for five seconds the Cv3 will announce the menu choices 1 Voices page 11 2 Directories page 12 3 General Site Configuration page 14 5 Output Configuration page 16 6 Group and Shift Configuration pag...

Page 14: ...l voices Exit to Main Menu Exit to Main Menu Playback or Record Voices Cv3 Site is Ajax Compressor Station or Input 1 is Low Temperature or Output 1 is Yard Lights You 2 Record new voice Exit to voice...

Page 15: ...that follows for the available directory entries Cv3 Group 1 on Shift 1 Directory Line 1 is or Directory Line 1 is DIAL 4032559544 VOICE You 2 Edit current line 3 Erase current line 4 Insert line Next...

Page 16: ...he telephone number 1 RADIO ALERT VOICE 2X WAIT X is the time in seconds 255 9X SMS TEXT X is the data phone number Custom Sequences Custom sequences are created by selecting a prefix to define the po...

Page 17: ...Menu Next setting Cv3 Relay voices are You X Enter new value 0 off 1 on Exit to Main Menu Next setting Cv3 Security Level is You X Enter new value 1 2 or 3 Exit to Main Menu Next setting Cv3 Access Co...

Page 18: ...ys 1 Monday 2 Tuesday Exit to Main Menu Next setting Cv3 Status Report Text Message Number is You X Enter new destination phone number 0 Erase phone number disabled Exit to Main Menu Next setting Cv3...

Page 19: ...for this input Menu items for Manual On Off Outputs are Cv3 Output One Type is On Off Cv3 Output Format is You x Enter a new value 0 NO contacts 1 NC contacts Exit to Main Menu Next setting Cv3 DTMF...

Page 20: ...1 seconds 2 minutes Exit to I O Configurations Next Setting Cv3 Output Time is You x Enter new value 1 to 65535 Exit to Main Menu Next Setting Menu items for Automatic On Off Outputs Relays 1 2 or 4...

Page 21: ...0 NO contacts 1 NC contacts Exit to Main Menu Next setting Cv3 Output Scale is You x Enter new value 1 seconds 2 minutes Exit to I O Configuration Next Setting Cv3 Output Time is You x Enter new valu...

Page 22: ...ng Cv3 Interrogate Code is You X Enter a new DTMF code Erase Exit to Main Menu Next setting Cv3 Directory Timer is You X Enter new value 1 to 255 min Exit to Main Menu Next setting Cv3 Acknowledge Req...

Page 23: ...steps Exit to Main Menu Next setting Cv3 Radio Volume One is minus TX Tone You X Enter a new value 0 to 20 Exit to Main Menu Next setting Cv3 Radio Volume Two is minus TX DTMF You X Enter a new value...

Page 24: ...PROGRAMMING PAGE 21 8 Reset Database Cv3 Empty Program Cv3 Alert Enter Octo Three One Star Star You 31 Confirm Exit to Main Menu Exit to Main Menu Cv3 Program is Empty...

Page 25: ...PAGE 22 9 Cellular Module Status Cv3 Phone Interrogate Cv3 Signal Strength is 0 to 15 3 poor 6 good You Exit to Main Menu Next item Cv3 Roaming status is 0 or 1 0 Off 1 On You Exit to Main Menu Exit t...

Page 26: ...ontains a HSPA based module that is pre configured at the factory except for the assigned Mobile Number Cv3 Program Phone Cv3 SIM Card Number is 19 or 20 digit number You Exit to Main Menu Next item C...

Page 27: ...rsion Cv3 Module Number is You Exit to Main Menu You Next Cv3 Hardware version is You Exit to Main Menu You Next Cv3 Firmware version is You Exit to Main Menu You Next Cv3 Options are You Exit to Main...

Page 28: ...d Yellow No Signal Solid Red 4 Flashing Red Invalid MIN Not Registered Flashing Red 4 Solid Yellow Invalid MIN Registered Flashing Green 1 to 4 Solid Green Invalid MIN Roaming Flashing Yellow 1 to 4 S...

Page 29: ...the directory If the B1277 reaches the end of the directory without being acknowledged it will wait two minutes Directory Timer then start calling again beginning at the top of the directory In addit...

Page 30: ...efined codes Acknowledge code Interrogate code Totalizer or Accumulator input reset code Intrusion input arm or disarm code Shift change code Relay on or off code Program mode access code If an Access...

Page 31: ...the group Green Group alarms are unacknowledged Flashing Red Group alarms are acknowledged Solid Red Group alarms are being reported Flashing Yellow 2 ALARM 12 ten hardware inputs one power supply mon...

Page 32: ...mode in effect Normal conditions Short Green Flash Error condition Short Red Flash Tone Idle Off While a tone is being transmitted Solid Red While a tone is being received Solid Green Voice Voice Off...

Page 33: ...dicator Pressing the power switch briefly will restore operation to full power While the Cv3 is operating at full power pressing the switch briefly will force it into low power mode The unit cannot be...

Page 34: ...tand up to 30 VDC Inputs 1 to 6 Analog voltage mode Input impedance 210k ohm Range 0 to 5 or 0 to 30 VDC Digital mode Internal 4 7k ohm pull up resistor to 5 VDC Operates with ground closure Low state...

Page 35: ...e between 0 dBm and 20 dBm RX audio 600 ohms single ended capacitor coupled Adjustable between 0 dBm and 20 dBm Program Ports Telset RJ11 connector Internal telset bias from the primary power supply O...

Page 36: ...TECHNICAL DRAWINGS PAGE 33 9 TECHNICAL DRAWINGS Unit Dimensions...

Page 37: ...TECHNICAL DRAWINGS PAGE 34 Wiring Inputs Digital connection Inputs 1 through 6 Digital connection Inputs 7 through 10 Analog Connection DC Voltage Inputs 1 through 6...

Page 38: ...TECHNICAL DRAWINGS PAGE 35 Analog Connection DC Voltage Inputs 7 through 10 Analog Connection DC Current Inputs 7 through 10...

Page 39: ...ng all the electronics can now be removed from the base of the Cv3 The SIM card socket can be seen near the center of the board by the cutout provided for the antenna cable Pressing it in until a clic...

Page 40: ...h and low alarm setpoint with an accepted range on the input terminal of 0 to 5 VDC Call Activity Detect a function that when enabled delays alarm annunciation until the recipient of the call speaks i...

Page 41: ...es are defined and the directories used have unique lists of callout instructions GSM Global System for Mobile Communications a mobile telephony standard used by carriers such as AT T Mobility T Mobil...

Page 42: ...isolated contacts that have the capacity to be used to turn on lights or sirens or control other equipment Shift a time when an alternate directory or set of directories is used Shift Select Input an...

Page 43: ...Ltd At 1 800 268 2646 or email support barnett engg com Product Repairs For all your repair needs please contact Barnett Engineering Ltd Barnett Engineering Ltd commits to a Repair Turnaround Time of...

Page 44: ...cept any interference received including interference that my cause undesired operation Warning This equipment generates uses and can radiate radio frequency energy If not installed and used in accord...

Page 45: ...ment or refund the purchase price at Barnett Engineering Ltd s option after return of such equipment by buyer to Barnett Engineering Ltd Shipment to Barnett Engineering Ltd s facility shall be borne o...

Reviews: