6
5. TECHNICAL SPECIFICATIONS
Model without electric pre-heating coil and...
...without coil / with water heating coil / with WCO coil / with DX coil
Model with electric pre-heating coil and...
...without coil / with water heating coil / with WCO coil / with DX coil
Characteristics of the fan electric motor (per fan)
Characteristics of LPHW coil
* For water temperature gradient 60/40 and inlet air temperature 15°C
...electric post heating coil
...electric post heating coil
Characteristics of electric preheater coil
Type
Voltage [V]
Frequency [Hz]
Rated power [kW]
Rated current [A]
HRFL2-040
230
50
0.34
2.7
HRFL2-070
230
50
0.33
2.5
HRFL2-150
230
50
1
5.6
HRFL2-200
230
50
1
6.3
Type
Voltage [V]
Frequency [Hz]
Rated power [kW]
Rated current [A]
HRFL2-040
230
50
0.9
4.1
HRFL2-070
230
50
1.8
8.8
HRFL2-150
400
50
3.7
18
HRFL2-200
400
50
5.8
13.5
Type
Voltage [V]
Frequency [Hz]
Rated power [kW]
Rated current [A]
HRFL2-040
230
50
1.7
7.4
HRFL2-070
230
50
3.1
13.5
HRFL2-150
400
50
6.3
14.7
HRFL2-200
400
50
9.4
19.8
Type
Voltage [V]
Frequency [Hz]
Rated power [kW]
Rated current [A]
HRFL2-040
230
50
2.7
11.8
HRFL2-070
400
50
4.5
11.7
HRFL2-150
400
50
9
18
HRFL2-200
400
50
14.2
24.8
Type
Phase [pcs]
Voltage [V] Frequency [Hz]
Rated power [W]
Rated current [A]
Speed [r/min]
Protection IP
Insulation class
HRFL2-040
1
230
50
169
1.35
4120
54
B
HRFL2-070
1
230
50
175
1.3
2800
44
B
HRFL2-150
1
230
50
455
3.1
2600
54
B
HRFL2-200
1
230
50
500
3.15
1970
54
B
Type
Phase [pcs]
Voltage [V]
Frequency [Hz]
Rated power [kW]
∆ T [°C]
HRFL2-040
1
230
50
1.1
6.3
HRFL2-070
1
230
50
1.6
6.3
HRFL2-150
1
230
50
2.7
5.3
HRFL2-200
3
400
50
4.8
6.3
Type
Phase [pcs]
Voltage [V]
Frequency [Hz]
Rated power [kW]
∆ T [°C]
HRFL2-040
1
230
50
1.35
10
HRFL2-070
1
230
50
2.7
10
HRFL2-150
3
400
50
5.3
10
HRFL2-200
3
400
50
8.4
10
Type
Rated capacity *[kW]
Water pressure loss [kPa]
Air pressure loss [Pa]
Connections diameter
Air fl w [m³/h]
HRFL2-040
1.75
1
10
1/2“
400
HRFL2-070
2.71
3
15
1/2“
700
HRFL2-150
5.92
17
27
1/2“
1500
HRFL2-200
9.22
9
21
1/2“
2000
Characteristics of electric
post heating
coil
NOTE:
Please note all performance data is displayed for reference only. Coil performance is based on the nominal conditions stated and should be