As long as there are conditions favourable for the creation of condensate ensure the unit condensate outlet is
connected to an appropriate waste system.
•
The use of a condensate siphon is only recommended where gravity assisted drainage is achievable.
•
Ensure the condensate syphon is installed with sufficient height difference from the unit so that the conden
-
sate can drain freely by gravity.
•
Ensure that the condensate is routed to a suitable outlet.
•
If the pipework connecting the outlet from the unit to the condensate drainage system is installed on a loca
-
tion that can freeze the pipe must be insulated or equipped with a frost pipe heater.
•
Ensure that the condensate discharge point height does not exceed the maximum head of 12 m for the con
-
densate pump.
•
If the condensate pumps is fitted ensure it is properly mounted so pipes and hoses will not kink or become
detached in operation. Pipe clips should always be used.
•
For additional information on the pump installation, operation and maintenance please refer to the
IOM
pro
-
vided with the pump.