30
MENU 14 -
TRICKLE MODE
7. INITIAL COMMISSIONING
15 - Boost
16 - Freecooling
12 - Flow shift
14 - Occupied mode
MENU 12 - FLOW OFFSET
MENU 11 - BYPASS TEMPERATURE
Overpressure/
underpressure
settings
MENU 13 - FIRE FLOW
Setting the
unit's rate when
the FIRE contact
opens (input ter-
minals 15/16)
The FIRE input has the highest priority
(it disables all the other modes, including anti-freeze protec-
tion)
Flow shift
Flow shift
Drain 0 %
Drain 0 %
10 - Blowing limits
12 - Flow shift
Flow in fire mode
Drain 100 %
MIN = 0°C ~ 20°C
Offset_percent > 0
exhaust = supply * ( 1 – (Offset_percent / 100) )
Offset_percent < 0
supply = exhaust / (1 – (Offset_percent / 100) )