background image

Manual 2100-347F
Page

10 of 24

FIGURE  4

MOUNTING INSTRUCTIONS

MIS-796

Summary of Contents for WH611

Page 1: ...ATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model WH611 Manual 2100 347F Supersedes 2100 347E File Volume III Tab 17 Date 03 27 06 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving...

Page 2: ...3 Table 10 Maximum ESP of Operation 23 Table 11 Pressure Table Cooling 24 Table 12 Pressure Table Heating 24 Getting Other Information and Publications For More Information 3 Wall Mount General Heat P...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...43 3 Ton 49 4 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate C Commercial Ventilator Motorized w o...

Page 5: ...n U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B 1 1 6 H W 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4...

Page 6: ...rmation on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct...

Page 7: ...Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be...

Page 8: ...or vented type system to assure proper drainage FIGURE 3 CONDENSATE DRAINS MIS 1278 CONDENSER CONDENSATE DRAIN EVAPORATOR CONDENSATE DRAIN CONDENSATE DRAIN CONDENSER A hole is provided in the unit bas...

Page 9: ...h clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 4 and 5 for details WARNING Failure...

Page 10: ...Manual 2100 347F Page 10 of 24 FIGURE 4 MOUNTING INSTRUCTIONS MIS 796...

Page 11: ...RNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 i...

Page 12: ...G WALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FIN...

Page 13: ...Manual 2100 347F Page 13 of 24 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS 550...

Page 14: ...the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capabilit...

Page 15: ...eat loss calculation of the building are useful in determining the correct set points OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 10 and 11 Heat pump compressor operation at outdoor temperatures...

Page 16: ...mostat This is done to maximize efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from the t...

Page 17: ...d light to activate This is a signal to the operator of the equipment to place system in the emergency heat position TH5220D1151 8403 058 Thermostat Thermostat will display on the screen Em Heat when...

Page 18: ...ing See the Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is changed or rewired If improper rotation is corrected at this time there wil...

Page 19: ...ow in operation The second option has no Auto changeover position but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in Heat position the B t...

Page 20: ...ng for the outdoor ambient to fall into the defrost region FIGURE 15 DEFROST CONTROL BOARD MIS 1174 By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost senso...

Page 21: ...a l p e R t o n g n i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w S r o...

Page 22: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Page 23: ...r u t a r e p m e T D O 2 8 e r u t a r e p m e T 1 1 6 H W 0 5 3 1 1 5 8 4 3 5 0 5 TABLE 10 MAXIMUM ESP OF OPERATION d e e p S h g i H d e e p S m u i d e M 5 0 A 8 0 A 0 1 A 3 3 3 3 3 3 9 0 B 3 3 9...

Page 24: ...i S h g i H 9 6 1 8 1 0 7 7 0 2 2 7 9 2 2 3 7 7 4 2 5 7 1 6 2 6 7 2 7 2 6 7 8 7 2 7 7 1 8 2 8 7 0 8 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 7 7 8 1 2 7 4 1 2 5 7 7 3 2 6 7 6 5 2...

Reviews: