background image

Manual   2100-403
Page    11

WIRING — MAIN POWER

Refer to the unit rating plate for wire sizing
information and maximum fuse or “HACR" type
circuit breaker size. Each outdoor unit is marked with
a “Minimum Circuit Ampacity”. This means that the
field wiring used must be sized to carry that amount
of current. Depending on the installed KW of electric
heat, there may be two field power circuits required.
If this is the case, the unit serial plate will so indicate.
All models are suitable only for connection with
copper wire. Each unit and/or wiring diagram will be
marked “Use Copper Conductors Only”. These
instructions 

must be

 adhered to. Refer to the National

Electrical Code (NEC) for complete current carrying
capacity data on the various insulation grades of
wiring material. All wiring must conform to NEC and
all local codes.

The electrical data lists fuse and wire sizes (75ºC
copper) for all models, including the most commonly
used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR" type circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection and also to assure
that there will be no nuisance tripping due to the
momentary high starting current of the compressor
motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab
located in the bottom left hand corner of the
disconnect opening under the disconnect access panel
straight out. This tab will now line up with the slot in
the door. When shut, a padlock may be placed through
the hole in the tab preventing entry.

See Start-up section for information on three phase
scroll compressor start-ups.

WIRING — LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual
primary voltage transformers. All equipment leaves
the factory wired on 240V tap. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:

Nine (9) wires should be run from thermostat subbase to
the 24V terminal board in the unit. A nine conductor, 18
gauge copper, color-coded thermostat cable is
recommended. The connection points are shown in
Figures 7 and 8.

LOW VOLTAGE CONNECTIONS

These units use a grounded 24 volt AC low voltage
circuit.

The 

"R"

 terminal is the 

hot

 terminal and the 

"C"

terminal is 

grounded

.

"G"

 terminal is the 

fan input

.

"Y"

 terminal is the 

compressor input for cooling

.

"B"

 terminal is the 

reversing valve input

.  The reversing

valve must be energized for heating mode.

"R"

 terminal is 

24 VAC hot

.

"C"

 terminal is 

24 VAC grounded

.

"L"

 terminal is 

compressor lockout 

output

.  This

terminal is activated on a high or low pressure trip by
the electronic heat pump control.  This is a 24 VAC
output.

"W2

" terminal is 

second stage heat

 (if equipped).

"01"

 terminal is the 

ventilation input

.  This terminal

energizes any factory installed ventilation option.

"E"

 terminal is the e

mergency heat input

.  This terminal

energizes the emergency heat relay.

"W3"

 terminal is the 24 

dehumidification circuit

.

"W1"

 terminal is the 

compressor input of heat pump

heating

.

NOTE: for total and proper control using DDC, a

total of 8 controlled outputs are required (7 if
no ventilation system is installed).  For proper
system operation under Emergency Heat
conditions where the compressor needs to be
deactivated, the B-W2-E outputs need to be
energized.  Removing the W1 (compressor)
signal alone turns the compressor off, but does
not activate the additional circuitry embedded
in the heat pump for proper and complete
operation.

NOTE: The voltage should be measured at the field

power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).

p

a

T

e

g

n

a

R

0

4

2

8

0

2

6

1

2

-

3

5

2

7

8

1

-

0

2

2

S

N

O

I

T

C

E

N

N

O

C

E

G

A

T

L

O

V

W

O

L

L

O

R

T

N

O

C

C

D

D

R

O

F

y

l

n

O

n

a

F

G

e

z

i

g

r

e

n

E

e

d

o

M

g

n

il

o

o

C

G

,

Y

e

z

i

g

r

e

n

E

g

n

i

t

a

e

H

p

m

u

P

t

a

e

H

B

,

G

,

1

W

e

z

i

g

r

e

n

E

g

n

i

t

a

e

H

e

g

a

t

S

d

n

2

)

d

e

y

o

l

p

m

e

f

i

(

B

,

1

W

,

2

W

,

G

e

z

i

g

r

e

n

E

n

o

i

t

a

l

i

t

n

e

V

1

O

,

G

e

z

i

g

r

e

n

E

n

o

i

t

a

c

i

f

i

d

i

m

u

h

e

D

3

W

e

z

i

g

r

e

n

E

t

a

e

H

y

c

n

e

g

r

e

m

E

G

,

E

,

2

W

,

B

e

z

i

g

r

e

n

E

Summary of Contents for WH421D Series

Page 1: ...T PUMPS MODELS WH421D WH483D WH602D INSTALLATION INSTRUCTIONS Manual 2100 403A Supersedes 2100 403 File Volume III Tab 17 Date 09 01 03 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Movin...

Page 2: ...vs Resistance of Temperature Sensor 20 Fan Blade Dimensions 21 Removal of Fan Shroud 21 Refrigerant Charge 21 Pressure Tables 22 23 Optional Accessories 23 Figures Figure 1 Unit Dimensions 3 Figure 2...

Page 3: ...r and Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Q Duct System Design for Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Conditioning...

Page 4: ...6 3 0 0 6 5 2 CONTROL MODULES See Chart Below NOTE For 0 KW and circuit breakers 230 208 V or pull disconnects 460 V applications insert 0Z in the KW field of model number MODEL NUMBER CAPACITY 42 3 1...

Page 5: ...Manual 2100 403 Page 3 FIGURE 1 UNIT DIMENSIONS MIS 411...

Page 6: ...1 4 3 0 6 6 8 0 5 0 7 0 9 8 6 3 0 1 8 8 A N 4 3 4 3 A N 6 2 2 5 A N 0 5 0 5 A N 0 3 0 6 A N 8 8 A N 0 1 6 A N 0 1 0 1 A N 0 1 0 1 Z 0 B 0 0 B D 1 2 4 H W 6 0 B 3 9 0 B 3 8 0 2 0 3 2 1 1 1 6 2 4 4 3 5...

Page 7: ...rs of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent conde...

Page 8: ...r drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with the fresh air damper assembly the assembly is shipped already attac...

Page 9: ...pening would then be 32 x 12 See Figures 2 4 and 7 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain fl...

Page 10: ...nch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in fire FIGURE 4 ELECTRIC HEAT CLEARANCE Side section view of sup...

Page 11: ...3 Page 9 FIGURE 5 WALL MOUNTINGINSTRUCTIONS FIGURE 6 WALL MOUNTINGINSTRUCTIONS MIS 548 MIS 549 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DU...

Page 12: ...Manual 2100 403 Page 10 FIGURE 7 COMMONWALL MOUNTINGINSTALLATIONS MIS 550...

Page 13: ...e operating voltage range for the 240 and 208V taps are Nine 9 wires should be run from thermostat subbase to the 24V terminal board in the unit A nine conductor 18 gauge copper color coded thermostat...

Page 14: ...hermostat and subbase must be matched and the correct operation can be assured only by proper selection and application of these parts MIS 1561 NC C C R NC C AREA OCCUPIED PWR HVAC H600A 6 5 4 3 C G R...

Page 15: ...ons as shown in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only be proper selection and application of these parts MIS 15...

Page 16: ...c that will prevent compressor for operating will cause red lamp to activate This is a signal to the operator of the equipment to place system in emergency heat position TABLE 3 THERMOSTAT WIRE SIZE r...

Page 17: ...Monitor on page 15 of this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no negative impac...

Page 18: ...call for dehumidification the compressor and three way valve of the unit are energized to provide dehumidification Dehumidification mode will continue until the humidistat is satisfied If the room te...

Page 19: ...erminal The manufacturer s recommendation is for 60 minute defrost cycles Refer to Figure 11 There is a cycle speed up jumper on the control This can be used to reduce the time between defrost cycle o...

Page 20: ...Manual 2100 403 Page 18 FIGURE 11 DEFROST CONTROL BOARD...

Page 21: ...e h C g n i d n i w r o t o m r o t o m e c a l p e R r o t i c a p a c r o t o M e v i t c e f e d k c e h C g n t a r r o t i c a p a c k c e h C r o t i c a p a c d e t r o h s r o n e p o r o f r...

Page 22: ...85371 82699 80121 77632 75230 72910 70670 68507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0...

Page 23: ...s shown in the Table 7 TABLE 7 SUCTION LINE TEMPERATURES l e d o M d e t a R w o l f r i A D O F 5 9 e r u t a r e p m e T D O F 2 8 e r u t a r e p m e T 1 2 4 H W 3 8 4 H W 2 0 6 H W 0 0 4 1 0 5 5 1...

Page 24: ...7 5 0 2 5 7 0 2 2 7 7 5 3 2 8 7 1 5 2 9 7 6 6 2 0 8 2 8 2 0 8 7 9 2 1 8 3 1 3 2 8 9 2 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 9 7 0 1 2 0 8 6 2 2 2 8 1 4 2 3 8 7 5 2 4 8 3 7 2 5 8...

Page 25: ...9 3 1 3 5 0 A 2 4 H W H E s e g a k c a P r e t a e H X 0 1 A 2 4 H W H E s e g a k c a P r e t a e H X 6 0 C 2 4 H W H E s e g a k c a P r e t a e H X 5 0 A 4 0 H W H E s e g a k c a P r e t a e H X...

Reviews: