background image

Manual    2100-374
Page        15

MIS-1174

FIGURE  10

DEFROST CONTROL BOARD

Use a small screwdriver or other metallic object, or
another 1/4 inch QC, to short between the SPEEDUP
terminals to accelerate the HPC timer and initiate
defrost.

Be careful not to touch any other terminals with the
instrument used to short the SPEEDUP terminals.  It
may take up to 10 seconds with the SPEEDUP
terminals shorted for  the speedup to be completed and
the defrost cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.
Otherwise the timing will remain accelerated and run
through the 1 minute minimum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a  0° coil temperature.
This can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the SEN JMP terminals (a
1/4 inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test the SEN JMP
jumper must be removed.  If left in place too long the
compressor could stop due to the high pressure control
opening because of  high pressure condition created by
operating in the cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is likely no actual
frost on the outdoor coil in this artificial test condition.

There is also a 5 minute compressor time delay function
built into the HPC.  This is to protect the compressor from
short cycling conditions.  In some instances it is helpful to
the service technician to override or speed up this timing
period, and shorting out the SPEEDUP terminals for a few
seconds can do this.

Summary of Contents for WH242D

Page 1: ...ONS WALL MOUNTED PACKAGE HEAT PUMP Model WH242D Manual 2100 374D Supersedes 2100 374C File Volume III Tab 17 Date 09 01 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as p...

Page 2: ...ontrol Board 15 Figure 11 Fan Blade Setting 18 Figure 12 Circuit Diagram H P Cooling Mode 21 Figure 13 Circuit Diagram H P Dehumidification 21 Start Up Important Installer Note 13 Crankcase Heaters 13...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingt...

Page 4: ...he equipment covered in this manual is to be installed by trained experienced service and installation technicians The refrigerant system is completely assembled and charged All internal wiring is com...

Page 5: ...i n U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C D D 2 4 2 H W 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2...

Page 6: ...three feet of duct attached to the outlet air frame is required See Pages Wall Mounting Instructions and Figure 3 for further details Ducts through the walls must be insulated and all joints taped or...

Page 7: ...bly and sliding the brackets apart to the required width and retightening the four 4 screws FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is...

Page 8: ...airflow to the outdoor coil Additional clearance may be required to meet local or national codes WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or HACR...

Page 9: ...Manual 2100 374 Page 7 FIGURE 3 MOUNTINGINSTRUCTIONS MIS 353...

Page 10: ...Manual 2100 374 Page 8 FIGURE 5 WALLMOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 549 MIS 548 FIGURE 4 WALLMOUNTINGINSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS...

Page 11: ...Manual 2100 374 Page 9 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS MIS 550...

Page 12: ...plication of these parts FIGURE 7 WHxxxDx HOT GAS REHEAT DURING DEHUMIDIFICATION WITH CS2000 ENERGY MONITOR FULL TIME DEHUMIDIFICATION FACTORY JUMPER H600A MIS 1561 8403 032 BARD CS2000 8403 038 HONEY...

Page 13: ...wn in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only be proper selection and application of these parts FIGURE 8 WHxxxDx...

Page 14: ...1 e l b a m m a r g o r P n o N c i n o r t c e l E r e v o e g n a h C l a u n a M r o o t u A 9 4 0 3 0 4 8 0 8 3 3 9 F 1 t a e h e g a t s 3 l o o c e g a t s 2 e l b a m m a r g o r P y a D 7 r e...

Page 15: ...OOLING Circuit R Y makes at thermostat pulling in compressor contactor starting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call for cooling operation...

Page 16: ...erative to match the correct pressure curve to the unit by model number DEFROST CYCLE The defrost cycle is controlled by temperature and time on the solid state heat pump control See Figure 10 When th...

Page 17: ...frost operation of the unit without waiting for the outdoor ambient to fall into the defrost region By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost senso...

Page 18: ...c e c a l p e R t o n g n i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w...

Page 19: ...17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 90 0...

Page 20: ...s 3 Remove screws 9 holding fan shroud to condenser and bottom 4 Unwire condenser fan motor 5 Slide complete motor fan blade and shroud assembly out the left side of the unit 6 Service motor fan as ne...

Page 21: ...2 4 2 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 5 7 6 1 2 6 7 9 2 2 7 7 2 4 2 9 7 6 5 2 0 8 1 7 2 1 8 6 8 2 3 8 2 0 3 4 8 8 1 3 6 8 6 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L...

Page 22: ...n a l B r e p m a D r i A h s e r F c i r t e m o r a B r e p m a D r i A h s e r F d e z i r o t o M t s u a h x E h t i w r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o...

Page 23: ...V 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL INDOOR COIL REHEAT COIL 4 WAY VALVE CHECK VALVE CAPILLARY DRAIN ASSY 3 WAY VALVE COMPRESSOR TXV 2 THRU 3 1 2 TON USE ORIFICE OUTDOOR COIL FIGURE 12 BARD MFG...

Reviews: