background image

Manual 2100-423C
Page

8 of 21

INSTALLATION  INSTRUCTIONS

WALL MOUNTING INFORMATION

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the unit being installed.

4. The unit is suitable for 0 inch clearance from the

unit, and from the supply and return air ducts.

MOUNTING THE UNIT

1. Two holes for the supply and return air openings

must be cut through the wall as shown in Figure 3.

2. Locate and mark lag bolt locations and bottom

mounting bracket location, if desired.  See Figure 3.

3. Mount bottom mounting bracket, if used.

4. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of
the back.

5. Position unit in opening and secure with 5/16 lag

bolts.  Use 5/16" diameter flat washers on the lag
bolts.

6. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 3.

7. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

8. On side-by-side installations, maintain a minimum

of 20 inches clearance on right side of unit to allow
access to control panel and heaters, and to allow
proper airflow to the outdoor coil.  Additional
clearance may be required to meet local or national
codes.

Summary of Contents for WH184

Page 1: ...PACKAGE HEAT PUMP Models WH184 WH242 INSTALLATION INSTRUCTIONS Manual 2100 423C Supersedes 2100 423B File Volume III Tab 17 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Mo...

Page 2: ...eat Hold Off Wiring 14 Figure 10 Start Up Procedure Decal 15 Figure 11 Defrost Control Board 16 Figure 12 Fan Blade Setting 19 Start Up Important Installer Note 15 Crankcase Heaters 15 Service Hints 1...

Page 3: ...nter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditionin...

Page 4: ...ered in this manual is to be installed by trained experienced service and installation technicians The refrigerant system is completely assembled and charged All internal wiring is complete The unit i...

Page 5: ...Manual 2100 423C Page 5 of 21 FIGURE 1 UNIT DIMENSIONS...

Page 6: ...to note 89 of table 310 regarding Ampacity Adjustment Factors when more than 3 are in a raceway TABLE 2 ELECTRICALSPECIFICATIONS T I U C R I C E L G N I S l e d o M d e t a R s t l o V d n a e s a h...

Page 7: ...NSATE DRAIN A plastic drain hose extends from the drain pan at the top of the unit down to the unit base There are openings in the unit base for the drain hose to pass through In the event the drain h...

Page 8: ...as shown in Figure 3 2 Locate and mark lag bolt locations and bottom mounting bracket location if desired See Figure 3 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend...

Page 9: ...Manual 2100 423C Page 9 of 21 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 10: ...Manual 2100 423C Page 10 of 21 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 11: ...Manual 2100 423C Page 11 of 21 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 12: ...orm to NEC and all local codes The electrical data lists fuse and wire sizes 75 C copper for all models including the most commonly used heater sizes Also shown are the number of field power circuits...

Page 13: ...ecific destination of the country and are installed in areas not approaching the lower outdoor temperature range outdoor thermostats are not factory installed as standard equipment but are offered as...

Page 14: ...s desirable to disable the operation of the electric heat until outdoor temperatures have reached a certain design point This won t allow the electric heat to come on as second stage heating unless th...

Page 15: ...motor The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation FIGURE 10 HEATING a 24V...

Page 16: ...re is a cycle speed up jumper on the control This can be used to reduce the time between defrost cycle operation without waiting for time to elapse Use a small screwdriver or other metallic object or...

Page 17: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Page 18: ...898 17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 9...

Page 19: ...Table 7 The suction line temperatures in Table 7 are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across the evaporator during cooling cycle FIGURE 12 FAN BLADE SETTING...

Page 20: ...e d i S w o L e d i S h g i H 2 8 0 0 2 4 8 4 1 2 5 8 9 2 2 7 8 5 4 2 8 8 2 6 2 9 8 9 7 2 1 9 7 9 2 1 9 6 1 3 2 9 5 3 3 2 4 2 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 5 7 6 1 2 6...

Page 21: ...r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o c E r o t a l i t n e V y r e v o c e R y g r e n E X X X X X X X X X X X X X X X X X X X X X X X 3 H M C 7 H M C 9 H M C 4...

Reviews: