Manual 2100-365Q
Page
30 of 73
23. MEASURING AIR TEMPERATURE
RISE
Air temperature rise (supply air temperature minus
return air temperature) must be within allowable air
temperature rise range specified on furnace rating plate
and in Table 1.
You will need 2 thermometers with 1 degree resolution
capable of reading up to 200 degrees F. Check
thermometers to make sure they agree, or compensate
accordingly.
Follow this procedure:
1. Open supply air registers and return air grilles.
Make sure the registers and grilles are free of
obstruction from rugs, carpets, drapes or furniture.
22. CONVERSION OF GAS INPUT BTUH
FROM HIGH TO LOW RATING
All the derated WG series units are produced with
maximum BTUH input orifices installed. To field
convert input, a change to main burner orifices is
required.
NOTE:
No change to air orifices is necessary. A set
of low input orifices is shipped with every
unit. They will be found packaged in a bag
behind the burner door. Refer to the unit
rating plate to confirm the proper orifice size.
Proper installation of the orifices is detailed
as follows:
A. Shut off electrical supply to the unit.
B. Shut off gas supply to the unit.
C. Remove burner access panel.
D. Disconnect gas valve from gas supply piping.
E. Disconnect the two wires from the gas valve.
F. Remove the manifold assembly so that orifices are
now accessible and remove orifices.
G. Apply a modest amount of pipe compound to the
new orifices and screw them into the manifold.
H. To assemble burner reverse steps A through G.
2. Set balancing dampers in supply duct system.
3. Check duct work for obstructions or leaks.
4. Make sure filters are clean and in place.
5. Place one thermometer in supply air plenum
approximately 2 feet from furnace. Locate
thermometer tip in center of plenum to insure proper
temperature measurement.
6. Place second thermometer in return air duct
approximately 2 feet from furnace. Locate
thermometer tip in center of duct to insure proper
temperature measurement.
7. Set room thermostat on highest temperature setting.
Operate furnace 10 minutes. Record supply air and
return air temperatures.
8. Calculate air temperature rise by subtracting return
air temperature from supply air temperature.
•
If air temperature rise is above the temperature
rise range on rating plate, furnace is overfired
or has insufficient airflow. Check gas input
following the instructions in Section, “Checking
Gas Input Rate”. If air temperature rise is still
above temperature rise range specified, more
heating airflow is needed. Check duct work and
grilles to make sure all are properly sized.
•
If air temperature rise is below the temperature
rise range on rating plate, furnace is underfired
or has too much airflow. Check gas input
following the instructions in Section, “Checking
Gas Input Rate”. If air temperature rise is still
below temperature rise range specified, less
heating airflow is needed. Adjust dampers or
grilles as needed.
•
After making adjustments, you must check air
temperature rise to verify that resulting air
temperature rise is within allowable range. If
air temperature rise is still outside the
temperature rise range specified on rating
plate, check duct system design with a
qualified heating engineer. It may be
necessary to re-size the duct work. Recheck
air temperature rise after revising duct systems.
9. Set room thermostat to desired setting.
10. Remove thermometers and seal duct work holes.
NOTE: Failure to seal holes could result in reduced
system performance.
WARNING
Failure to follow these instructions could
create a hazard resulting in property damage,
bodily injury, or death.
Summary of Contents for WG242-A
Page 13: ...Manual 2100 365Q Page 13 of 73 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...
Page 16: ...Manual 2100 365Q Page 16 of 73 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Page 22: ...Manual 2100 365Q Page 22 of 73 FIGURE 11 LOW VOLTAGE WIRING...
Page 23: ...Manual 2100 365Q Page 23 of 73 FIGURE 12 GAS PIPE CONNECTION...
Page 48: ...Manual 2100 365Q Page 48 of 73 WG242 A 230 208 60 1...
Page 49: ...Manual 2100 365Q Page 49 of 73 WG242 A WG362 A 230 208 60 1...
Page 50: ...Manual 2100 365Q Page 50 of 73 WG242 B 230 208 60 3...
Page 51: ...Manual 2100 365Q Page 51 of 73 WG242 B WG362 B 230 208 60 3...
Page 52: ...Manual 2100 365Q Page 52 of 73 WG243 C 460 60 3...
Page 53: ...Manual 2100 365Q Page 53 of 73 WG243 C 460 60 3...
Page 54: ...Manual 2100 365Q Page 54 of 73 WG302 A 230 208 60 1...
Page 55: ...Manual 2100 365Q Page 55 of 73 WG302 A WG482 A WG602 A 230 208 60 1...
Page 56: ...Manual 2100 365Q Page 56 of 73 WG302 B 230 208 60 3...
Page 57: ...Manual 2100 365Q Page 57 of 73 WG302 B WG482 B WG602 B 230 208 60 3...
Page 58: ...Manual 2100 365Q Page 58 of 73 WG303 C 460 60 3...
Page 59: ...Manual 2100 365Q Page 59 of 73 WG303 C 460 60 3...
Page 60: ...Manual 2100 365Q Page 60 of 73 WG362 A 230 208 60 1...
Page 61: ...Manual 2100 365Q Page 61 of 73 WG362 B 230 208 60 3...
Page 62: ...Manual 2100 365Q Page 62 of 73 WG363 C 460 60 3...
Page 63: ...Manual 2100 365Q Page 63 of 73 WG363 C 460 60 3...
Page 64: ...Manual 2100 365Q Page 64 of 73 WG423 A 230 208 60 1...
Page 65: ...Manual 2100 365Q Page 65 of 73 WG423 A 230 208 60 1...
Page 66: ...Manual 2100 365Q Page 66 of 73 WG423 B 230 208 60 3...
Page 67: ...Manual 2100 365Q Page 67 of 73 WG423 B 230 208 60 3...
Page 68: ...Manual 2100 365Q Page 68 of 73 WG424 C 460 60 3...
Page 69: ...Manual 2100 365Q Page 69 of 73 WG424 C 460 60 3...
Page 70: ...Manual 2100 365Q Page 70 of 73 WG482 A WG602 A 230 208 60 1...
Page 71: ...Manual 2100 365Q Page 71 of 73 WG482 B WG602 B 230 208 60 3...
Page 72: ...Manual 2100 365Q Page 72 of 73 WG483 C WG603 C 460 60 3...
Page 73: ...Manual 2100 365Q Page 73 of 73 WG483C WG603 C 460 60 3...