background image

Manual 2100-365Q
Page

30 of 73

23. MEASURING AIR TEMPERATURE

RISE

Air temperature rise (supply air temperature minus
return air temperature) must be within allowable air
temperature rise range specified on furnace rating plate
and in Table 1.

You will need 2 thermometers with 1 degree resolution
capable of reading up to 200 degrees F.  Check
thermometers to make sure they agree, or compensate
accordingly.

Follow this procedure:

1. Open supply air registers and return air grilles.

Make sure the registers and grilles are free of
obstruction from rugs, carpets, drapes or furniture.

22.   CONVERSION OF GAS INPUT BTUH
FROM HIGH TO LOW RATING

All the derated WG series units are produced with
maximum BTUH input orifices installed.  To field
convert input, a change to main burner orifices is
required.

NOTE: 

 

No change to air orifices is necessary.  A set
of low input orifices is shipped with every
unit.  They will be found packaged in a bag
behind the burner door.  Refer to the unit
rating plate to confirm the proper orifice size.
Proper installation of the orifices is detailed
as follows:

A. Shut off electrical supply to the unit.

B. Shut off gas supply to the unit.

C. Remove burner access panel.

D. Disconnect gas valve from gas supply piping.

E. Disconnect the two wires from the gas valve.

F. Remove the manifold assembly so that orifices are

now accessible and remove orifices.

G. Apply a modest amount of pipe compound to the

new orifices and screw them into the manifold.

H. To assemble burner reverse steps A through G.

2. Set balancing dampers in supply duct system.

3. Check duct work for obstructions or leaks.

4. Make sure filters are clean and in place.

5. Place one thermometer in supply air plenum

approximately 2 feet from furnace.  Locate
thermometer tip in center of plenum to insure proper
temperature measurement.

6. Place second thermometer in return air duct

approximately 2 feet from furnace.  Locate
thermometer tip in center of duct to insure proper
temperature measurement.

7. Set room thermostat on highest temperature setting.

Operate furnace 10 minutes.  Record supply air and
return air temperatures.

8. Calculate air temperature rise by subtracting return

air temperature from supply air temperature.

If air temperature rise is above the temperature
rise range on rating plate, furnace is overfired
or has insufficient airflow.  Check gas input
following the instructions in Section, “Checking
Gas Input Rate”.  If air temperature rise is still
above temperature rise range specified, more
heating airflow is needed.  Check duct work and
grilles to make sure all are properly sized.

If air temperature rise is below the temperature
rise range on rating plate, furnace is underfired
or has too much airflow.  Check gas input
following the instructions in Section, “Checking
Gas Input Rate”.  If air temperature rise is still
below temperature rise range specified, less
heating airflow is needed.  Adjust dampers or
grilles as needed.

After making adjustments, you must check air
temperature rise to verify that resulting air
temperature rise is within allowable range.  If
air temperature rise is still outside the
temperature rise range specified on rating
plate, check duct system design with a
qualified heating engineer.  It may be
necessary to re-size the duct work.  Recheck
air temperature rise after revising duct systems.

9. Set room thermostat to desired setting.

10. Remove thermometers and seal duct work holes.

NOTE:  Failure to seal holes could result in reduced

system performance.

       WARNING

Failure to follow these instructions could
create a hazard resulting in property damage,
bodily injury, or death.

Summary of Contents for WG242-A

Page 1: ...facturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 2004 WARNING READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION THE INSTALLATION MUST COMPLY WIT...

Page 2: ...7 Thermostats 21 18 Gas Supply Piping 24 19 Manifold Pressure Adjustment 25 20 Checking Gas Input Rate 25 26 21 Standard Orifice Sizing High Altitude Derate 27 22 Conversion of Gas Input BTUH From Hig...

Page 3: ...f Operation Electronic Blower Control 36 Figure 18 Furnace Control Board Blower Control 37 Figure 19 Fan Blade 46 Figure 20 Low NOx Insert 46 TABLES Table 1 Specifications WG24 36 Models 7 Table 1A Sp...

Page 4: ...47 4044 COPYRIGHT SEPTEMBER 2003 BARD MANUFACTURING COMPANY INC BRYAN OHIO 43506 USA Manufactured under the following U S patent numbers 5 485 878 5 002 116 4 924 934 4 875 520 4 4825 936 These public...

Page 5: ...l a i c r e m m o C P 3 P V R C G W 5 P V R C G W g n i t a l u d o M y l l u F r e z i m o n o c E 1 E 3 M F I E G W 5 M F I E G W t l o V 0 3 2 r o t a l i t n e V y r e v o c e R y g r e n E R 3 A...

Page 6: ...dure and any tags and or labels attached to the equipment All duct work supply and return must be properly sized for the design airflow requirement of the equipment Air Conditioning Contractors of Ame...

Page 7: ...8 0 2 0 3 2 0 6 4 s p m A d a o L d e t a R 5 0 1 5 9 6 6 2 6 3 3 5 3 1 5 2 1 5 9 0 9 5 6 1 4 1 0 1 5 9 5 t n e r r u C n o i t c e l e S t i u c r i C h c n a r B 5 0 1 7 6 5 3 1 4 1 5 9 5 6 1 0 1 5...

Page 8: ...2 0 3 2 0 6 4 s p m A d a o L d e t a R 5 9 1 1 2 5 4 1 5 3 1 8 5 1 2 1 2 3 1 5 2 1 2 6 0 3 7 2 5 9 1 7 1 9 t n e r r u C n o i t c e l e S t i u c r i C h c n a r B 1 2 5 1 6 7 2 2 3 1 4 6 0 3 5 9 1...

Page 9: ...N AIR EXHAUST COMBUSTION AIR INTAKE CONTROL LOW VOLTAGE ENTRANCES CIRCUIT BREAKER VENT OPTION MIS 2123 A UNIT A B C D E F G H I J K L M N O W G 24 W G 30 W G 3 6 7 88 27 88 13 88 24 25 40 25 63 81 63...

Page 10: ...nd in the absence of specific recommendations from the local authority having jurisdiction equipment ratings shall be reduced as specified in Section 21 5 TRANSPORTATION DAMAGE All units are packed se...

Page 11: ...ible wall use a minimum of Figure 1 A dimension plus 2 inches and B dimension plus 2 inches See Figures 4 and 5 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location 4...

Page 12: ...PTIONAL 12 FLANGE SCREWS UNIT SUPPORT 1 MIN NECCESSARY NO CLEARANCE SUPPLY AIR DUCT RETURN AIR DUCT CONTROL PANEL VESTIBULE DOOR WALL STRUCTURE OUTSIDE 1 CLEARANCE ON ALL FOUR SIDES OF SUPPLY AIR DUCT...

Page 13: ...Manual 2100 365Q Page 13 of 73 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG42 WG48 AND WG60...

Page 14: ...of one 1 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first three 3 feet of ducting It is important to insure that the one 1 inch m...

Page 15: ...Manual 2100 365Q Page 15 of 73 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS...

Page 16: ...Manual 2100 365Q Page 16 of 73 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 17: ...ed air from the condenser to recirculate to the condenser inlet TABLE 2 MINIMUM INSTALLATION CLEARANCES s l a i r e t a m e l b i t s u b m o c m o r f t c u D t e l t u O t e e f 3 t s r i f h c n i...

Page 18: ...ang The kit includes a stainless steel transition drain tee silicone sealant and drain tubing If unit is installed with vertical vent kit annually inspect the vent system and drain Replace any portion...

Page 19: ...nce spillage at the draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle 6 After it has been determined that each appliance connected to the venting sy...

Page 20: ...r electrical ground could result in electric shock or fire 15 WIRING MAIN POWER Refer to unit rating plate for wire sizing information and maximum fuse or HACR type circuit breaker size Each outdoor u...

Page 21: ...All models are equipped with single primary voltage transformers and no rewiring is required TABLE 3 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i...

Page 22: ...Manual 2100 365Q Page 22 of 73 FIGURE 11 LOW VOLTAGE WIRING...

Page 23: ...Manual 2100 365Q Page 23 of 73 FIGURE 12 GAS PIPE CONNECTION...

Page 24: ...0 0 0 0 5 0 5 0 0 0 6 5 0 0 0 5 1 1 0 0 0 5 1 2 0 0 0 0 4 4 0 6 0 0 0 0 5 0 0 0 5 0 1 0 0 0 5 9 1 0 0 0 0 0 4 0 7 0 0 0 6 4 0 0 0 6 9 0 0 0 0 8 1 0 0 0 0 7 3 0 8 0 0 0 3 4 0 0 0 0 9 0 0 0 0 7 1 0 0 0...

Page 25: ...kits may be purchased from your local distributor 5 Slowly open equipment shut off valve in gas supply line just ahead of furnace Start furnace following Operating Instructions on front door 6 Slowly...

Page 26: ...the furnace gas input PROPANE LP GAS INPUT RATE 1 Make sure you have proper main burner orifices 2 Gas supply pressure must be between 11 and 13 inches W C for propane LP gas 3 Start furnace followin...

Page 27: ...5 7 0 6 0 0 5 7 6 6 0 8 8 5 0 4 3 5 6 2 6 8 6 5 0 8 1 3 6 8 1 9 4 5 0 2 0 1 6 0 6 4 3 5 0 0 4 9 5 8 8 4 2 5 0 2 3 8 5 3 7 2 1 5 0 7 9 6 5 4 4 5 0 5 0 6 1 6 5 2 7 5 9 4 0 8 0 5 5 5 6 9 8 4 5 0 4 4 5 4...

Page 28: ...F 0 0 0 0 1 o t 1 0 0 8 h c t i w S e r u s s e r P s e r i u q e R e g n a h C e c i f i r O d n a e g n a h C t n e t n o C U T B n o d e s a B U T B 0 5 2 0 2 r e n r u B r e P 9 4 7 0 0 7 0 6 2 0...

Page 29: ...r e d 0 1 l a n o i t p o l a n o i t p O d l e i F 0 1 d e t r e v n o C e t a r e D t a e H s a G e u l a V t F u C U T B o N t e e F 0 0 0 6 o t p U t p e c x E s e g n a h C t n e t n o C U T B r...

Page 30: ...oximately 2 feet from furnace Locate thermometer tip in center of plenum to insure proper temperature measurement 6 Place second thermometer in return air duct approximately 2 feet from furnace Locate...

Page 31: ...ontactor will de energize immediately The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on make time has expired If the high pr...

Page 32: ...e DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of Delay on Break DOB setting 0 5 minute 30 seconds DOB 123 second DOM 1 0 minute 60 seconds DOB 126 second DOM 2 0...

Page 33: ...Manual 2100 365Q Page 33 of 73 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 15 INSTRUCTION LABEL...

Page 34: ...ht on small mirror or an extension handle Remove the screws securing the inducer and collector box Now inspect the upper tubes of the heat exchanger Check the exterior of the heat exchanger and the in...

Page 35: ...sure the supply and return air flange sleeves or duct work are securely fastened to unit and physically sound d Supply and return grilles must be open and free from obstructions e Inspect to make sur...

Page 36: ...cle on and off until the condensing pressure remains above 180 PSIG LAC energizes the fan motor at 280 PSIG de energizes at 180 PSIG FIGURE 17 SEQUENCE OF OPERATION ELECTRONIC BLOWER CONTROL N O I T C...

Page 37: ...f it is desirable to have both HEAT COOL blower motor speed at the same speed install a jumper wire between HEAT and COOL terminals of the integrated furnace control board and place both unused motor...

Page 38: ...0 7 0 2 1 1 0 2 1 1 0 4 9 4 0 0 9 7 0 3 0 1 0 3 0 1 0 6 8 5 0 0 1 9 0 1 7 0 5 9 6 0 0 0 8 0 4 8 P S E s e h c n I H2 O E D O M G N I L O O C E D O M G N I T A E H d n a N A F L A U N A M l i o C t e W...

Page 39: ...3 0 1 0 9 1 1 0 3 0 1 0 6 8 5 0 0 5 0 1 0 1 9 0 9 0 1 0 5 9 0 9 0 1 0 5 9 6 0 0 4 9 0 8 9 0 8 9 0 4 8 P S E s e h c n I H2 O E D O M G N I L O O C E D O M G N I T A E H d n a N A F L A U N A M l i o C...

Page 40: ...1 0 3 0 1 0 9 1 1 0 3 0 1 0 6 8 5 0 0 5 0 1 0 9 0 1 0 5 9 0 9 0 1 0 5 9 6 0 0 4 9 0 8 9 0 8 9 0 4 8 P S E s e h c n I H2 O E D O M G N I L O O C E D O M G N I T A E H d n a N A F L A U N A M l i o C...

Page 41: ...3 1 1 0 3 4 1 0 3 1 1 P S E s e h c n I Hs O E D O M G N I L O O C N A F L A U N A M d n a E D O M G N I T A E H l i o C t e W U T B 0 0 0 0 0 1 t u p n I U T B 0 0 0 0 9 h g i H m u i d e M w o L h g...

Page 42: ...0 4 3 1 0 3 4 1 0 3 4 1 0 3 1 1 P S E s e h c n I Hs O E D O M G N I L O O C N A F L A U N A M d n a E D O M G N I T A E H l i o C t e W U T B 0 0 0 0 0 1 t u p n I U T B 0 0 0 0 9 h g i H m u i d e...

Page 43: ...3 1 0 3 4 1 0 3 4 1 0 3 1 1 P S E s e h c n I Hs O E D O M G N I L O O C N A F L A U N A M d n a E D O M G N I T A E H l i o C t e W U T B 0 0 0 0 0 1 t u p n I U T B 0 0 0 0 9 h g i H m u i d e M w...

Page 44: ...c e l e s e h t r o f e t a r e p o l l i w r e w o l b r i a t r o f m o c e h t e t a r e p o o t e u n i t n o c l l i w r e w o l b r i a t r o f m o c e h t n o i t a r e p o S T I N U Y T E F A...

Page 45: ...8 6 2 3 2 8 6 4 3 3 8 6 6 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 7 7 8 2 2 9 7 5 4 2 1 8 2 6 2 2 8 9 7 2 4 8 8 9 2 5 8 6 1 3 7 8 5 3 3 8 8 5 5 3 9 8 5 7 3 B D g e d 5 8 B W g e d...

Page 46: ...9 FAN BLADE 36 LOW NOX BURNER ASSEMBLY N SUFFIX MODELS ONLY U S INSTALLATIONS ONLY NATURAL GAS MODELS ONLY Model numbers designated with an N are designed for low NOx emissions which comply with all C...

Page 47: ...7 5 C 3 0 3 G W 3 4 3 5 8 0 4 8 5 A 4 4 3 5 8 0 4 9 5 A 2 6 3 G W A 8 3 1 5 8 0 4 0 6 A 5 3 1 5 8 0 4 9 4 B 2 6 3 G W A 8 3 2 5 8 0 4 1 6 A 5 3 2 5 8 0 4 1 5 C 3 6 3 G W 5 4 3 5 8 0 4 2 6 A 6 4 3 5 8...

Page 48: ...Manual 2100 365Q Page 48 of 73 WG242 A 230 208 60 1...

Page 49: ...Manual 2100 365Q Page 49 of 73 WG242 A WG362 A 230 208 60 1...

Page 50: ...Manual 2100 365Q Page 50 of 73 WG242 B 230 208 60 3...

Page 51: ...Manual 2100 365Q Page 51 of 73 WG242 B WG362 B 230 208 60 3...

Page 52: ...Manual 2100 365Q Page 52 of 73 WG243 C 460 60 3...

Page 53: ...Manual 2100 365Q Page 53 of 73 WG243 C 460 60 3...

Page 54: ...Manual 2100 365Q Page 54 of 73 WG302 A 230 208 60 1...

Page 55: ...Manual 2100 365Q Page 55 of 73 WG302 A WG482 A WG602 A 230 208 60 1...

Page 56: ...Manual 2100 365Q Page 56 of 73 WG302 B 230 208 60 3...

Page 57: ...Manual 2100 365Q Page 57 of 73 WG302 B WG482 B WG602 B 230 208 60 3...

Page 58: ...Manual 2100 365Q Page 58 of 73 WG303 C 460 60 3...

Page 59: ...Manual 2100 365Q Page 59 of 73 WG303 C 460 60 3...

Page 60: ...Manual 2100 365Q Page 60 of 73 WG362 A 230 208 60 1...

Page 61: ...Manual 2100 365Q Page 61 of 73 WG362 B 230 208 60 3...

Page 62: ...Manual 2100 365Q Page 62 of 73 WG363 C 460 60 3...

Page 63: ...Manual 2100 365Q Page 63 of 73 WG363 C 460 60 3...

Page 64: ...Manual 2100 365Q Page 64 of 73 WG423 A 230 208 60 1...

Page 65: ...Manual 2100 365Q Page 65 of 73 WG423 A 230 208 60 1...

Page 66: ...Manual 2100 365Q Page 66 of 73 WG423 B 230 208 60 3...

Page 67: ...Manual 2100 365Q Page 67 of 73 WG423 B 230 208 60 3...

Page 68: ...Manual 2100 365Q Page 68 of 73 WG424 C 460 60 3...

Page 69: ...Manual 2100 365Q Page 69 of 73 WG424 C 460 60 3...

Page 70: ...Manual 2100 365Q Page 70 of 73 WG482 A WG602 A 230 208 60 1...

Page 71: ...Manual 2100 365Q Page 71 of 73 WG482 B WG602 B 230 208 60 3...

Page 72: ...Manual 2100 365Q Page 72 of 73 WG483 C WG603 C 460 60 3...

Page 73: ...Manual 2100 365Q Page 73 of 73 WG483C WG603 C 460 60 3...

Reviews: