High Pressure Switch and Lockout Sequence

• If the high pressure switch opens, the compressor

contactor will de-energize immediately.  The
lockout time in the CCM will go into a soft
lockout and stay locked out until the high pressure
switch closes and the delay on break has expired.

• If the high pressure switch opens again during

the same operating cycle the CCM will go into
a manual lockout condition.

• Recycling the wall thermostat resets the manual

lockout.

Low Pressure Switch, Bypass and Lockout
Sequence  (Optional)

• If the low pressure switch opens for more than

120 seconds the compressor contactor will de-
energize and the CCM will go into soft
lockout.

• Regardless of the state of the low pressure

switch the compressor contactor will
reenergize after the delay on break time has
expired.

• If the low pressure switch remains open, or

opens again for longer than 120 seconds, the
CCM will go into a manual lockout and the
alarm relay circuit will energize.

• Recycling the wall thermostat resets the manual

lockout.

NOTE: Both high and low pressure switch controls

are inherently automatic reset devices.  The
high pressure switch opens at 425 and
closes at 325 psig, and the low pressure
switch opens at 14 and closes at 30 psig.
The lockout features, both soft and manual,
are a function of the Compressor Control
Module.

Alarm Relay Output

• Alarm terminal on Compressor Control Module is

24V AC output connection for applications where
signal is desired.  This terminal is powered
whenever compressor is in manual lockout due to
high pressure or low pressure sequences as
described.

SECTION 4  •  TURNING OFF FURNACE IN

AN EMERGENCY

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a three phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the “&” signal is present at the phase
monitor and phases are correct, the green LED will
light.

If phases are reversed, the red fault LED will be lit
and compressor operation is inhibited.

3.3 MANUAL FAN (CONTINUOUS AIRFLOW)

OPERATION

If wall thermostat is set to MANUAL (ON) position to
operate comfort air blower continuously to provide air
circulation throughout the building, the blower will
operate on the heating speed rather than the cooling as
is typical with most systems.  This permits the air to
circulate as desired but helps keep the operating noise
level down as well a conserving energy.

During a call for cooling, the blower automatically
shifts up to cooling speed, and remains there until 60
seconds after thermostat is satisfied then drops back to
heating speed.

         WARNING

Have a qualified installer, service agency
or gas supplier teach you location and
operation of gas and electrical shut-off
devices.  Ask them any questions you
have about this section.  If you don’t turn
off your furnace in an emergency damage,
injury or death could result.

Summary of Contents for WG-Series

Page 1: ...nditioner gas furnace for years of dependable service We re pleased you ve chosen our air conditioner gas furnace to supply your cooling heating needs Please keep this manual in a safe yet readily ava...

Page 2: ...r Conditioning Start Up Procedure Crankcase Heater 12 Section 8 Ventilation Options 12 Section 9 Replacement Parts 13 Section 10 Outdoor Coil 13 Figures Figure 1 Typical Gas Piping 6 Figure 2 Step by...

Page 3: ...____________ Model Number _______________________________________________________________ Serial Number _______________________________________________________________ Date Installed _________________...

Page 4: ...s or vapors near or on your furnace These include gasoline kerosene cigarette lighter fluid cleaning fluids solvents paint thinners or painting compounds Flammable vapors can travel great distances be...

Page 5: ...rs There is a 60 second delay after main burner is on until the comfort air blower starts on heating speed After the thermostat is satisfied the burners will go off as gas valve closes The inducer wil...

Page 6: ...ut Alarm terminal on Compressor Control Module is 24V AC output connection for applications where signal is desired This terminal is powered whenever compressor is in manual lockout due to high pressu...

Page 7: ...r or Propane LP Gas Tank Normally natural gas is ON when you turn shut off parallel to gas pipe Gas is OFF when you turn shut off 90 from gas pipe Some valves require a wrench or other tools 2 ELECTRI...

Page 8: ...Manual 2100 366 Page 6 FIGURE 1 TYPICAL GAS PIPING MIS 1478...

Page 9: ...condition indicates lack of airflow through furnace ACTION a Make sure air filter is clean and installed correctly b Check that registers and return air grilles are open and unobstructed c If conditio...

Page 10: ...R FURNACE 1 Do not try to light main burners 2 Do not touch or turn on any electrical switch 3 Do not use any phone in your building 4 Immediately call your gas supplier from a neighbor s phone Follow...

Page 11: ...Manual 2100 366 Page 9 FIGURE 2 START UP PROCEDURE...

Page 12: ...of deterioration of the furnace 6 Periodic examinations of the vent terminal should also be conducted by the owner on a regular basis preferably every month but at least every two months during the he...

Page 13: ...Manual 2100 366 Page 11 FIGURE 4 PERIODIC INSPECTIONS MIS 1449 FIGURE 3 FILTER LOCATIONS MIS 1447a...

Page 14: ...is very important Please read carefully IMPORTANT These procedures must be followed at ini tial start up and at any time power has been removed for 12 hours or longer To prevent compressor damage whi...

Page 15: ...ered by these instructions it is very important to always supply the complete model number and serial number of the unit This is necessary to assure that the correct parts or an approved alternate par...

Reviews: