background image

Manual 2100-385B
Page

20

NOTICE

The refrigeration system in this unit is charged

with refrigerant R-407C

SERVICE PROCEDURE AND

CONSIDERATIONS

Refrigerant R-407C is a blend of three refrigerants,
HFC-32 / HFC-125 / HFC134A.  Unlike pure fluids and
azeotropes, blends boil and condense at varying
temperatures for a given pressure.  The range over
which the temperature varies is referred to as
temperature glide.  R-407C has moderately high
temperature glide between about 9° F and 13° F (5 to
7.2 Celsius) depending upon pressure.

When dealing with blends, pressure temperature tables
are presented in an unconventional manner.  Two
temperatures are listed for the same pressure – the liquid
temperature and the vapor temperature.

When a pressure reading is taken from the suction line
or discharge line it is converted to temperature from the
“Vapor Temperature” column on the pressure
temperature chart.

When a pressure reading is taken at the liquid line it is
converted to temperature from the “Liquid
Temperature” column on the pressure temperature chart.

All Bard “WE” models have a pressure tap in the
suction line and the liquid line.

See Pressure Temperature Table 12 on page 21.

CHARGING

When charging a system with R-407C, only the

liquid phase is to be used to ensure proper

refrigerant composition and system performance.

When charging the system into the suction side, care
must be exercised to avoid damage to the compressor.
Because the refrigerant leaving the refrigerant cylinder
must be in liquid phase, it is suggested that a sight glass
be connected between the charging hose and the suction
service port.  This will permit you to adjust the cylinder
hand valve so that liquid can leave the cylinder while
allowing vapor to enter the compressor.

The proper refrigerant amount is shown on the unit
rating plate.

LEAKS

If a significant leak develops in the system and a
noticeable change in the system performance occurs,
remove the remaining refrigerant with proper refrigerant
recovery methods, repair the leak with proper industry
practice and methods, and then, after evacuation,
recharge the system with new refrigerant.  Again, charge
only with liquid refrigerant to ensure that the proper
composition is in the system.

         CAUTION

Leak checking should never be done with a
mixture of R-407C and air.  Leak checking
can be performed safely with a mixture of
R-407C and nitrogen.  Make sure the leak
detector is capable of detecting R-407C
before using.

Notice:

When opening a system, care must be taken to

minimize the system exposure to atmosphere.

Exposure for more than five minutes could

shorten the life of the system.  The compressor in

this system contains Polyol Ester (POE) oil.

POE's are very hygroscopic.  They absorb

moisture from the atmosphere at a much faster

rate than mineral oils used in R-22 systems.

This system has a factory-installed filter drier in the
liquid line.  It is highly recommended that the filter drier
be replaced when the system has been open.  Make sure
the replacement filter drier is suitable and approved for
use with R-407C.

Before recharging the system, a vacuum of 250 microns
or less must be achieved.

Summary of Contents for WE252

Page 1: ...STRUCTIONS WALL MOUNTED PACKAGED AIR CONDITIONER Models WE252 WE301 WE371 WE421 WE482 WE602 WE701 Manual No 2100 385B Supersedes 2100 385A File Volume III Tab 16 Date 04 25 05 Bard Manufacturing Compa...

Page 2: ...gerant Service Procedures Considerations 20 Charging 20 Leaks 20 Figures Figure 1 Unit Dimensions 4 Figure 2 Fresh Air Damper Assembly 6 Figure 3 Mounting Instructions 8 Figure 4 Electric Heat Clearan...

Page 3: ...s Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORM...

Page 4: ...DAMPER V COMMERCIALVENTILATOR MOTORIZED WITH EXHAUST E ECONOMIZER INTERNAL FULLY MODULATING WITH EXHAUST R ENERGY RECOVERY VENTILATOR MOTORIZED WITH EXHAUST TABLE 1 ELECTRIC HEAT TABLE s l e d o M D...

Page 5: ...i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E e s u F t i u c r i C r o r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 d n u o r G e z i S e r i W Z 0 D 2 5 2 E W 5 0 D 8 0...

Page 6: ...7 2 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 4 5 8 1 5 7 5 2 3 9 7 1 5 7 6 2 5 7 8 2 5 2 9 2 0 7 2 5 7 2 9 1 9 3 5 7 2 2 4 1 9 9 1 4 0 2 1 0 5 0 2 1 1 2 4 E W 2 8 4 E W 2 0 6 E W 5 7 0 2 4 2 3...

Page 7: ...local regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the...

Page 8: ...is shipped already attached to the unit The damper blade is locked in the closed position To allow the damper to operate the maximum and minimum blade position stops must be installed See Figure 2 Cap...

Page 9: ...clearance to combustible material However it is highly recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material See Figures...

Page 10: ...Manual 2100 385B Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 1641 SEE FIGURE 4 FOR FURTHER DETAILS...

Page 11: ...hat the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death NOTE A 1 4...

Page 12: ...L AROUND RETURN DUCT OPENING A I C K THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS ATTACH TO BOTTOM PLATE OF WALL 2 x 6 1 000 CLE...

Page 13: ...OOR WALL SLEEVE CLOSET WALL LOWERED CEILING SUPPLY AIR GRILLE FINISHED CEILING SURFACE RAIN FLASHING SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE S...

Page 14: ...through the hole in the tab preventing entry Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is r...

Page 15: ...Manual 2100 385B Page 13 FIGURE 8 LOW VOLTAGE WIRING DIAGRAM MIS 1373...

Page 16: ...h monitoring and alarm relay output Adjustable Delay On Make And Break Timer On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes pl...

Page 17: ...DOB set at 2 minutes and DOM is 132 seconds Unit 2 DOB set at 4 minutes and DOM is 144 seconds PHASE MONITOR All units with three phase compressors are equipped with a 3 phase line monitor to prevent...

Page 18: ...mance will occur with a refrigerant charge resulting in a suction line temperature 6 inches from compressor as shown in Table 6 The suction line temperatures shown in Table 6 are based upon 80 F dry b...

Page 19: ...h g i H d e e p S w o L d e e p S h g i H d e e p S w o L d e e p S h g i H d e e p S w o L y r D l i o C t e W y r D l i o C t e W y r D l i o C t e W y r D l i o C t e W y r D l i o C t e W y r D l...

Page 20: ...e d i S w o L e d i S h g i H 8 8 8 3 2 0 9 6 5 2 1 9 4 7 2 3 9 4 9 2 4 9 4 1 3 6 9 4 3 3 7 9 6 5 3 9 9 9 7 3 0 0 1 2 0 4 1 2 4 E W B D 5 7 B W 2 6 e d i S w o L e d i S h g i H 8 7 5 3 2 0 8 1 5 2 3...

Page 21: ...n e V m o o R l a i c r e m m o C r o t a l i t n e V m o o R l a i c r e m m o C r o t a l i t n e V m o o R l a i c r e m m o C X X X X X 2 M F I E 3 M F I E 5 M F I E t s u a h x E h t i W r e z i...

Page 22: ...erant cylinder must be in liquid phase it is suggested that a sight glass be connected between the charging hose and the suction service port This will permit you to adjust the cylinder hand valve so...

Page 23: ...8 5 6 9 5 7 0 6 7 1 6 7 2 6 2 5 6 7 7 6 0 0 7 3 2 7 8 4 7 7 6 7 8 8 7 9 0 8 9 2 8 0 5 1 5 5 1 0 6 1 5 6 1 0 7 1 5 7 1 0 8 1 5 8 1 0 9 1 5 9 1 0 0 2 5 0 2 0 1 2 5 1 2 0 2 2 5 2 2 0 3 2 5 3 2 0 4 2 5 4...

Reviews: