background image

Manual 2100-401A
Page

9 of 21

INSTALLATION  INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes for the supply and return air openings

must be cut through the wall as shown in Figure 1
or 2.  Figure 1 is for models WA4843, and WA6023.
Figure 2 is for Models WA4842 and WA6022.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

       WARING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is
not maintained.  See Figure 3.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the installed unit.

WA4842 AND WA6022 ONLY

These units are equipped with adjustable return and
supply air flanges.  The flanges are adjustable side to
side in 1" increments.  This allows these units to be
adjusted so that in side-by-side applications these units
can replace two 2 ton units using the same wall
openings.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. The unit itself is suitable for 0 inch clearance, but

the supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material.  If a combustible
wall use a minimum of 30½" x 10½" dimensions for
sizing.  However, it is generally recommended that a
1-inch clearance is used for ease of installation and
maintaining the required clearance to combustible
material.  The supply air opening would then be
32" x 12".  See Figures 2 and 3 for details.

        WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing damage, injury or death.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 2.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of
the back.

6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 2.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

9. On side-by-side installations, maintain a minimum

of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airflow to the outdoor coil.  Additional clearance
may be required to meet local or national codes.

Summary of Contents for WA4842

Page 1: ...STRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS WA4842 WA4843 WA6022 WA6023 Manual 2100 401A Supersedes 2100 401 File Volume III Tab 16 Date 07 25 06 Bard Manufacturing Company Inc Bryan Ohio...

Page 2: ...arge 19 Table 8 Rated CFM and Rated ESP 19 Table 9 Maximum ESP of Operation Electric Heat Only 20 Table 10 Pressure Table 20 Table 11 Optional Accessories 21 Getting Other Information and Publications...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Page 4: ...0 5 0 7 1 1 8 1 0 0 8 2 1 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS K...

Page 5: ...Manual 2100 401A Page 5 of 21 FIGURE 1 UNIT DIMENSIONS WA6023 WA4843 ONLY...

Page 6: ...Manual 2100 401A Page 6 of 21 FIGURE 2 UNIT DIMENSIONS WA6022 WA4842 ONLY...

Page 7: ...i c a p m A 1 m u m i x a M e s u F l a n r e t x E r o r e k a e r B t k C 2 r e w o P d l e i F e z i S e r i W 2 d n u o r G e z i S e r i W A T K C B T K C A T K C B T K C A T K C B T K C A T K C...

Page 8: ...ags and or labels attached to the equipment Design the duct work according to methods given by the Air Conditioning Contractors of America ACCA When duct runs through unheated spaces it should be insu...

Page 9: ...et of supply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 x 10 dimensions for sizing However it is generally recommended that a 1...

Page 10: ...Manual 2100 401A Page 10 of 21 FIGURE 3 MOUNTING INSTRUCTIONS WA6023 WA4843 ONLY...

Page 11: ...Manual 2100 401A Page 11 of 21 FIGURE 4 MOUNTING INSTRUCTIONS WA6022 WA4842 ONLY...

Page 12: ...This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible...

Page 13: ...Manual 2100 401A Page 13 of 21 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 14: ...Manual 2100 401A Page 14 of 21 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS...

Page 15: ...ening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up sec...

Page 16: ...Manual 2100 401A Page 16 of 21 FIGURE 9 UNIT 24V TERMINAL BOARD...

Page 17: ...etermined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor...

Page 18: ...ual covering all models It is imperative to match the correct pressure table to the unit by model number Adjustable Delay On Make And Break Timer On initial power up or any time power is interrupted t...

Page 19: ...e e p S h g i H d e e p S h g i H d e e p S h g i H y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6...

Page 20: ...1 0 1 1 5 1 1 2 0 6 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 3 3 2 2 7 7 4 2 4 7 2 6 2 5 7 8 7 2 6 7 5 9 2 7 7 3 1 3 8 7 1 3 3 8 7 1 5 3 9 7 1 7 3 B D g e d 0 8 B W g e d 7 6...

Page 21: ...A WA4842A WA4843B WA4842B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k...

Reviews: