background image

Manual 2100-401A
Page

17 of 21

START UP

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil
with a dish washing detergent.

CRANKCASE HEATERS

These units are not provided with crankcase heat.  These
units utilize scroll compressors which do not require
crankcase heat in this application.

HIGH PRESSURE SWITCH

The models are supplied with a remote reset high
pressure switch.  If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as, substantially
reduced current draw compared to tabulated values.

Verification of 

proper rotation

 must be made at the

time the equipment is put into service.  If improper
rotation is corrected at this time, there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes, the compressor’s
internal protector will trip.

All three phase ZR3 compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation direction.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at

all times.  Also, not to needlessly close off supply
and return air registers.  This reduces airflow through
the system, which shortens equipment service life as
well as increasing operating costs.

2. Switching to heating cycle at 75° F or higher outside

temperature may cause a nuisance trip of the remote
reset high pressure switch.  Turn thermostat off, then
on to reset the high pressure switch.

3. Check all power fuses or circuit breakers to be sure

they are the correct rating.

4. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling

in compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase of constant air circulation.  On all 230 volt units
there is a one minute off delay on the blower motor.  460
volt models do not have an off delay.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on the
models covered by this manual.  The compressor control
is an anti-short cycle/lockout timer with high and low
pressure switch monitoring and alarm relay output.

Summary of Contents for WA4842

Page 1: ...STRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS WA4842 WA4843 WA6022 WA6023 Manual 2100 401A Supersedes 2100 401 File Volume III Tab 16 Date 07 25 06 Bard Manufacturing Company Inc Bryan Ohio...

Page 2: ...arge 19 Table 8 Rated CFM and Rated ESP 19 Table 9 Maximum ESP of Operation Electric Heat Only 20 Table 10 Pressure Table 20 Table 11 Optional Accessories 21 Getting Other Information and Publications...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Page 4: ...0 5 0 7 1 1 8 1 0 0 8 2 1 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS K...

Page 5: ...Manual 2100 401A Page 5 of 21 FIGURE 1 UNIT DIMENSIONS WA6023 WA4843 ONLY...

Page 6: ...Manual 2100 401A Page 6 of 21 FIGURE 2 UNIT DIMENSIONS WA6022 WA4842 ONLY...

Page 7: ...i c a p m A 1 m u m i x a M e s u F l a n r e t x E r o r e k a e r B t k C 2 r e w o P d l e i F e z i S e r i W 2 d n u o r G e z i S e r i W A T K C B T K C A T K C B T K C A T K C B T K C A T K C...

Page 8: ...ags and or labels attached to the equipment Design the duct work according to methods given by the Air Conditioning Contractors of America ACCA When duct runs through unheated spaces it should be insu...

Page 9: ...et of supply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 x 10 dimensions for sizing However it is generally recommended that a 1...

Page 10: ...Manual 2100 401A Page 10 of 21 FIGURE 3 MOUNTING INSTRUCTIONS WA6023 WA4843 ONLY...

Page 11: ...Manual 2100 401A Page 11 of 21 FIGURE 4 MOUNTING INSTRUCTIONS WA6022 WA4842 ONLY...

Page 12: ...This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible...

Page 13: ...Manual 2100 401A Page 13 of 21 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 14: ...Manual 2100 401A Page 14 of 21 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS...

Page 15: ...ening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up sec...

Page 16: ...Manual 2100 401A Page 16 of 21 FIGURE 9 UNIT 24V TERMINAL BOARD...

Page 17: ...etermined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor...

Page 18: ...ual covering all models It is imperative to match the correct pressure table to the unit by model number Adjustable Delay On Make And Break Timer On initial power up or any time power is interrupted t...

Page 19: ...e e p S h g i H d e e p S h g i H d e e p S h g i H y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6...

Page 20: ...1 0 1 1 5 1 1 2 0 6 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 3 3 2 2 7 7 4 2 4 7 2 6 2 5 7 8 7 2 6 7 5 9 2 7 7 3 1 3 8 7 1 3 3 8 7 1 5 3 9 7 1 7 3 B D g e d 0 8 B W g e d 7 6...

Page 21: ...A WA4842A WA4843B WA4842B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k...

Reviews: