controller can be installed). This will increase the
humidity removal up to 35% and provide a much more
comfortable environment.
If the application is likely to require air conditioning
operation below 60°F outdoor conditions, a low
ambient control (LAC) kit must be installed.
The LAC
kit is equipped with an additional sensor that disables
Balanced Climate mode when the outdoor temperature
drops below 50°F. This prevents potential evaporator
coil freeze up issues.
If the unit is being installed with any ventilation
package, a Bard LAC kit must be installed.
Failure to
utilize an LAC with any air conditioner can cause coil
freeze up.
NOTE:
Economizer will disable Balanced
Climate operation.
Balanced Climate can readily be applied to duct-free
(supply and return air grille) applications. It may also
be applied to ducted applications with
limited static
of 0.20" ESP (total including both supply and return
statics)
. Consult Bard Application Engineering for
details prior to implementation.
CAUTION:
Balanced Climate is not a replacement for
a dehumidification (hot gas reheat) unit for extreme
applications, but rather an enhancement feature for
limited climates and applications.
Summary of Contents for WA Series
Page 2: ......
Page 12: ......
Page 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 24: ......
Page 66: ...Manual 2100 720C Page 42 of 42 GRAPH 3 W5SAC FAD NE5 W O Exhaust Ventilation Delivery...
Page 67: ......
Page 72: ...Manual 2110 1461B Page 5 of 17 This page intentionally left blank...
Page 76: ...Manual 2110 1461B Page 9 of 17 This page intentionally left blank...
Page 85: ......