Manual 2100-720C
Page
21 of 42
FIGURE 20
Programmable Thermostat Connections
Thermostat
W1/E
A
YO/D
L
O/B
Y2
Y1
R
G
C
W2
Bard #8403-060
6
10
12
11
9
4
12-Pin
Vent Plug
2
3
5
7
CO2 OUT
Optional CO2 Controller
Bard Part #8403-067
6
5
4
3
2
1
TEMP-OUT
24VAC
W3
Y3
6
5
4
2
1
R
Unit Low
Voltage
Term. Strip
W2
C
G
RT
Y1
Y2
B/W1
L
D
A
3
A 3-stage thermostat is recommended for Balanced Climate mode. Must not be
8
7
6
Do not connect "A" from thermostat if optional CO2 controller is used
0-10 VDC modulating C02 control signal for modulating ventilation
control (optional for ECON only - see vent instruction manuals)
5
Change model configuration from heat pump to heat/cool. Must be configured to programmable
and fan set to be programmed fan for the "A" output to function during scheduled occupied
periods. Must be configured for multi-stage for Y1 output to be active 1st stage cooling. For
dehumidification, must be configured for "No Economizer" for YO/D to be active for humidity
control.
4
Factory installed jumper. Remove jumper and connect
to N.C fire alarm circuit if emergency shutdown required.
3
Wire not needed below 15KW.
2
Wire required for dehumidification models only.
1
Do not add these wires if setting up for modulating control. See note 7.
Install jumper for 1 stage electric heat on units with less than 15KW
9 Factory installed jumper. Remove jumper to activate Balanced Climate
™
mode.
removed if Econ is installed.
W1/E
SC
SC
SC
Completestat
Model #CS9B-THO or
Model #CS9BE-THO
W2
COM
G
24V
Y1
Y2
O/B
L
D
A
GND
MIS-4067
2
ALL VENT OPTIONS PLUG IN HERE
2
3
3
4
6
1
4
5
7
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
8
9
Summary of Contents for WA Series
Page 2: ......
Page 12: ......
Page 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 24: ......
Page 66: ...Manual 2100 720C Page 42 of 42 GRAPH 3 W5SAC FAD NE5 W O Exhaust Ventilation Delivery...
Page 67: ......
Page 72: ...Manual 2110 1461B Page 5 of 17 This page intentionally left blank...
Page 76: ...Manual 2110 1461B Page 9 of 17 This page intentionally left blank...
Page 85: ......