Manual 2100-720E
Page
22 of 42
FIGURE 21
Non-Programmable Thermostat Connections
CO2 OUT
Optional CO2 Controller
Bard Part #8403-096
6
5
4
3
2
1
TEMP-OUT
24VAC
W3
Y3
6
5
4
2
1
R
Unit Low
Voltage
Term. Strip
W2
C
G
RT
Y1
Y2
B/W1
L
D
A
3
Factory installed jumper. Remove jumper to activate Balanced Climate
™
Mode.
A 3-stage thermostat is recommended for Balanced Climate mode. Must not be
removed if Econ is installed.
5 Do not add these wires if setting up for modulating control. See note 6.
7
Jumper needs added.
8
2B
Install Jumper for 1 stage electric heat on units with more
than 10KW.
0-10 VDC Modulating CO2 control signal for modulating ventilation control
(Optional for ECON Only) - See vent installation manual.
6
For vent operation, add jumper if optional CO2 controller is not used.
Vent will run while blower is energized.
For ECON & CRV-V anadditional wire change is required
See install Manual.
4
Factory installed jumper. Remove jumper and connect
to N.C fire alarm circuit if emergency shutdown required.
3
Wire not needed below 15KW.
2A
Wire required for dehumidification models only.
1
Thermostat will not work with units equipped with economizers.
9
6
10
12
11
9
4
12-Pin
Vent Plug
2
3
5
7
8403-038
1
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
8403-047
ALL VENT OPTIONS PLUG IN HERE
4
2A
W
Rc
C
R
G
Y
Y2
W2
4
3
5
6
8
Electronic Humidistat
Units With Dehumidification
T6 Pro 8403-090
T4 Pro 8403-089
W
C
Rc
Y
R
G
O
2B
B
Mechanical Humidistat
3
7
6
5
9
MIS-4068 C