Manual 2100-720E
Page
38 of 42
TABLE 14
Indoor Blower Performance
E.S.P.
1
(In. H
2
O)
Balanced Climate
TM
Speed
Default LO
Cooling & Heating/
Ventilation Speed
2
Optional MED
Cooling & Heating
Speed
Optional HI Cooling
& Heating Speed
Dry Coil
Wet Coil
Dry Coil
Wet Coil
Dry Coil
Wet Coil
Dry Coil
Wet Coil
W3SAC
0.00
1035
935
1375
1300
1590
1535
1665
1600
0.10
840
770
1255
1185
1530
1475
1625
1570
0.15
750
700
1195
1130
1490
1440
1595
1545
0.20
665
630
1135
1070
1450
1400
1560
1510
0.25
1075
1015
1400
1355
1520
1470
0.30
1015
960
1350
1300
1470
1420
0.40
895
850
1235
1185
1350
1305
.050
775
745
1100
1050
1210
1165
W4SAC
0.00
1275
1195
1795
1685
1895
1850
2000
1920
0.10
1140
1070
1730
1625
1845
1765
1940
1850
0.15
1075
1015
1690
1590
1815
1725
1905
1815
0.20
1015
960
1655
1555
1785
1685
1870
1780
0.25
1615
1520
1750
1645
1835
1745
0.30
1575
1485
1715
1610
1800
1710
0.40
1485
1405
1635
1540
1730
1635
.050
1390
1325
1550
1475
1655
1560
W5SAC
0.00
1350
1300
1960
1870
2085
1985
2160
2065
0.10
1275
1225
1880
1815
2005
1925
2070
1985
0.15
1240
1180
1840
1785
1970
1895
2025
1950
0.20
1150
1100
1805
1760
1935
1865
1990
1915
0.25
1770
1730
1905
1835
1950
1885
0.30
1735
1700
1870
1810
1920
1855
0.40
1675
1635
1815
1750
1865
1800
.050
1625
1570
1770
1700
1820
1755
1
E.S.P. is the total combined external static pressure of both the supply and return ducts or grills.
2
This is the speed set at the factory.