Manual 2100-479
Page
9 of 11
T
roubleshooTing
The
M
echanical
s
ysTeM
HEAT PUMP
—
HEATING
LOW SUCTION — LOW HEAD PRESSURE
1. Restricted airflow through outdoor coil. (Restricted water
flow through water coil.
)
2. Defective outdoor motor. (Defective water pump.
)
3. Low outdoor air temperature. (Low water
temperature.
)
4. Frozen outdoor coil. (Frozen water coil.
)
5. Restricted liquid line, dryer, metering device, etc.
6. Low charge.
7. Low indoor air temperature.
HIGH SUCTION — LOW HEAD
PRESSURE
1. Defective or broken valves.
2. IPR valve open.
3. Defective reversing valve.
LOW SUCTION — LOW HEAD
PRESSURE
1. Restricted airflow over indoor coil.
2. Defective indoor fan motor.
3. Low indoor temperature
4. Iced indoor coil.
5. Restricted liquid line, dryer, metering device, etc.
6. Low charge.
7. Low ambient entering air temperature. (Low entering
water temperature to water coil.
)
HIGH SUCTION — LOW HEAD
PRESSURE
1. Defective or broken valves.
2. IPRV valve open.
3. Defective reversing valve.
AIR CONDITIONING AND HEAT PUMP — COOLING
LOW SUCTION — HIGH HEAD
PRESSURE
1. Partial restriction and then overcharged.
HIGH SUCTION — HIGH HEAD
PRESSURE
1. High entering outdoor air temperature. (High entering
water temperature.
)
2. Low airflow outdoor coil. (Low water flow.
)
3. Overcharged.
4. Air in system.
5. Restricted outdoor coil. (Restricted water coil.
)
6. High indoor air temperature.
Water source heat pump.
LOW SUCTION — HIGH HEAD
PRESSURE
1. Partial restriction and then overcharged.
HIGH SUCTION — HIGH HEAD
PRESSURE
1. High entering outdoor air temperature. (High entering
water temperature.
)
2. Low indoor airflow.
3. Overcharged.
4. Air in system.
5. Restricted air coil.
6. High indoor air temperature.
Water source heat pump.
Summary of Contents for W3LV2-R
Page 2: ......
Page 27: ......
Page 34: ......
Page 43: ......
Page 46: ......
Page 68: ......
Page 74: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 75: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 80: ......
Page 82: ...Manual 2110 1418G Page 2 of 16 CABINET COMPONENTS RIGHT EXTREME DUTY DOOR...
Page 84: ...Manual 2110 1418G Page 4 of 16 CABINET COMPONENTS RIGHT MODERATE DUTY DOOR...
Page 86: ...Manual 2110 1418G Page 6 of 16 CABINET COMPONENTS LEFT EXTREME DUTY DOOR...
Page 88: ...Manual 2110 1418G Page 8 of 16 CABINET COMPONENTS LEFT MODERATE DUTY DOOR...
Page 97: ......
Page 100: ......