Manual 2100-615A
Page
23 of 24
TABLE 6
ELECTRIC HEAT
TABLE 4
RECOMMENDED AIRFLOW
TABLE 5
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
Values shown are for units equipped with standard 1-inch
throwaway filter or 1-inch washable filter.
Derate ESP by .15 for 2-inch pleated filters.
Model
Rated
CFM*
Rated
ESP*
Recommended
Airflow Range
W3R/LV
1100
.15
1100 - 550
W5R/LV
1700
.20
1700 - 850
W6R/LV
1700
.20
1700 - 850
Model
W3
W5, W6
FRONT
FRONT
High
High
-A0Z
-A05
-A10
.50
.50
.50
.50
.50
.50
-B0Z
-B06
-B09
.50
.50
.50
.50
.50
.50
-C0Z
-C09
-C12
.50
.50
.45
.50
.50
.50
Models
240V-1
208V-1
240V-3
208V-3
460V-3
KW
Amps
BTUH
Amps
BTUH
Amps
BTUH
Amps
BTUH
Amps
BTUH
4
16.7
13650
14.4
10240
5
20.8
17065
18.1
12800
6
14.4
20500
12.5
15360
7.2
20500
8
33.3
27300
28.8
20475
9
21.7
30600
18.7
23030
10.8
30700
10
41.6
34130
36.2
25600
12
14.4
40950
15
62.5
51250
54.0
38400
36.2
51200
31.2
38400
18.0
51200
18
43.3
61430
37.5
46100
20
83.2
68260
72.1
51200
* Rated CFM and ESP on high speed tap.
Summary of Contents for W3LV2-R
Page 2: ......
Page 27: ......
Page 34: ......
Page 43: ......
Page 46: ......
Page 68: ......
Page 74: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 75: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 80: ......
Page 82: ...Manual 2110 1418G Page 2 of 16 CABINET COMPONENTS RIGHT EXTREME DUTY DOOR...
Page 84: ...Manual 2110 1418G Page 4 of 16 CABINET COMPONENTS RIGHT MODERATE DUTY DOOR...
Page 86: ...Manual 2110 1418G Page 6 of 16 CABINET COMPONENTS LEFT EXTREME DUTY DOOR...
Page 88: ...Manual 2110 1418G Page 8 of 16 CABINET COMPONENTS LEFT MODERATE DUTY DOOR...
Page 97: ......
Page 100: ......