Manual 2100-538A
Page

15 of 23

START UP (Continued)

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil
with a dish washing detergent.

HIGH PRESSURE SWITCH

All W*R/LV wall mounted air conditioner series models
are supplied with a remote reset for the high and low
pressure switch.  If tripped, this pressure switch may be
reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as substantially
reduced current draw compared to tabulated values.

Verification of 

proper rotation

 must be made at the

time the equipment is put into service.  If improper
rotation is corrected at this time, there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse rotation

for several minutes, the compressor’s internal
protector will trip.

All three phase compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  

Do not reverse any of the unit factory

wires as damage may occur.

SERVICE HINTS

1. Caution owner/operator to maintain clean air filters

at all times.  Also, not to needlessly close off supply
and return air registers.  This reduces airflow
through the system, which shortens equipment
service life as well as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

Summary of Contents for W3LV1

Page 1: ...LL MOUNTED VARIABLE CAPACITY PACKAGE AIR CONDITIONERS MODELS W3RV1 W3LV1 W5RV1 W5LV1 W6RV1 W6LV1 Manual 2100 538A Supersedes 2100 538 File Volume III Tab 16 Date 08 02 10 Bard Manufacturing Company In...

Page 2: ...nt Control Options 23 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 C...

Page 3: ...gn for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshir...

Page 4: ...ards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in acc...

Page 5: ...FG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity...

Page 6: ...ght of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to sk...

Page 7: ...urn Air Opening Built In Optional Electrical Entrances Top Rain Flashing Bottom Installation Bracket Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on W6RV W6LV models 2 Option...

Page 8: ...CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CA...

Page 9: ...D E 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 RETURN AIR FOAM AIR SEAL OPENING 29 Wall Opening and Hole Location View NOTES Supply Opening SUPPLY AIR Return Opening IT IS RECOMMENDED THAT A BEAD...

Page 10: ...bustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheati...

Page 11: ...0 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...formation on three phase scroll compressor start ups See Table 4 for Electrical Specifications WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All eq...

Page 14: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 15: ...mpact on the durability of the compressor However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rota...

Page 16: ...ked ON as long as the unit is in the Test Mode 2 While in Test Mode 2 the compressor will NOT modulate but will be locked on at 100 to maintain the occupied room setpoint During the Test Mode 2 if the...

Page 17: ...ll be set at normal outdoor airflow Below 55 degrees the outdoor fan will modulate to maintain a 300 psi head pressure This will act as a low ambient fan cycling control The output may go to zero outp...

Page 18: ...s expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize Recycling the wall...

Page 19: ...harge resulting in a liquid subcooling as shown in Table 2 If charge is in doubt reclaim and recharge to factory nameplate charge Values are at 100 capacity TABLE 2 REFRIGERANTCHARGE l e d o M d e t a...

Page 20: ...1 9 6 4 0 3 1 8 9 4 2 3 1 0 3 5 5 3 1 5 6 5 e e S e t o N 2 F 7 6 0 8 C 4 9 1 7 6 2 e d i S w o L e d i S h g i H 7 3 1 4 6 3 6 3 1 3 8 3 6 3 1 4 0 4 6 3 1 7 2 4 7 3 1 3 5 4 8 3 1 1 8 4 9 3 1 1 1 5 1...

Page 21: ...A N 6 A N A N 0 1 A N A N A N A N A N 0 1 A N A N 0 1 A N A N A N Z 0 S 1 V L 3 W 1 V R 3 W 6 0 S 9 0 S 3 0 6 8 0 2 0 3 2 0 2 2 3 0 5 0 0 2 1 1 1 9 1 7 3 6 4 0 3 0 4 0 5 0 1 8 8 0 1 0 1 0 1 A N A N A...

Page 22: ...7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 2 1 4 4 1 0 5 9 0 4 5 1 5 2 6 0 5 2 1 5 0 4 5 0 0 4 8 3 2 6 3 0 0 2...

Page 23: ...n o i t p i r c s e D 5 1 C M C e s a h P 1 V 0 3 2 t i K t r a t S X X 3 D A F B d r a d n a t S r e p m a D r i A h s e r F c i r t e m o r a B X 3 P O B e t a l P f f O k n a l B X 5 D A F B d r a...

Reviews: