START UP

THESE UNITS REQUIRE R-410A
REFRIGERANT AND POLYOL
ESTER OIL.

GENERAL:

1. Use separate service equipment to avoid cross

contamination of oil and refrigerants.

2. Use recovery equipment rated for R-410A

refrigerant.

3. Use manifold gauges rated for R-410A (800 psi/250

psi low).

4. R-410A is a binary blend of HFC-32 and HFC-125.

5. R-410A is nearly azeotropic - similar to R-22 and

R-12.  Although nearly azeotropic, charge with
liquid refrigerant.

6. R-410A operates at 40-70% higher pressure than

R-22, and systems designed for R-22 cannot
withstand this higher pressure.

7. R-410A has an ozone depletion potential of zero,

but must be reclaimed due to its global warming
potential.

8. R-410A compressors use polyolester oil.

9. Polyol Ester oil is hygroscopic; it will rapidly absorb

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used - even a deep

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug

compressor immediately after removal.  Purge with
small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard Manufacturing
recommends reclaiming, evacuating (see criteria above),
and charging to the nameplate charge.  If done correctly,
topping off the system charge can be done without
problems.

With R-410A, there are no significant changes in the
refrigerant composition during multiple leaks and
recharges.  R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound or
single component refrigerant).  The remaining
refrigerant charge, in the system, may be used after
leaks have occurred and then “top-off” the charge by
utilizing the charging charts on the inner control panel
cover as a guideline.

REMEMBER:  

When adding R-410A refrigerant, it

must come out of the charging cylinder/tank as a liquid
to avoid any fractionation, and to insure optimal system
performance.  Refer to instructions for the cylinder that
is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1. Never mix R-410A with other refrigerants.

2. Use gloves and safety glasses, Polyol Ester oils can

be irritating to the skin, and liquid refrigerant will
freeze the skin.

3. Never use air and R-410A to leak check; the

mixture may become flammable.

4. Do not inhale R-410A – the vapor attacks the

nervous system, creating dizziness, loss of
coordination and slurred speech.  Cardiac
irregularities, unconsciousness and ultimate death
can result from breathing this concentration.

5. Do not burn R-410A.  This decomposition

produces hazardous vapors.  Evacuate the area if
exposed.

6. Use only cylinders rated DOT4BA/4BW 400.

7. Never fill cylinders over 80% of total capacity.

8. Store cylinders in a cool area, out of direct

sunlight.

9. Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge

lines or cylinders.  R-410A expands significantly
at warmer temperatures.  Once a cylinder or line is
full of liquid, any further rise in temperature will
cause it to burst.

        WARNING

Failure to conform to these practices
could lead to damage, injury or death.

Summary of Contents for W3LV1

Page 1: ...LL MOUNTED VARIABLE CAPACITY PACKAGE AIR CONDITIONERS MODELS W3RV1 W3LV1 W5RV1 W5LV1 W6RV1 W6LV1 Manual 2100 538A Supersedes 2100 538 File Volume III Tab 16 Date 08 02 10 Bard Manufacturing Company In...

Page 2: ...nt Control Options 23 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 C...

Page 3: ...gn for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshir...

Page 4: ...ards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in acc...

Page 5: ...FG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity...

Page 6: ...ght of the installed unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to sk...

Page 7: ...urn Air Opening Built In Optional Electrical Entrances Top Rain Flashing Bottom Installation Bracket Back View L M O E R S S S S S T 44 N Q P B 1 Dimension is 21 00 inches on W6RV W6LV models 2 Option...

Page 8: ...CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CA...

Page 9: ...D E 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4 32 12 5 1 2 2 RETURN AIR FOAM AIR SEAL OPENING 29 Wall Opening and Hole Location View NOTES Supply Opening SUPPLY AIR Return Opening IT IS RECOMMENDED THAT A BEAD...

Page 10: ...bustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheati...

Page 11: ...0 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...formation on three phase scroll compressor start ups See Table 4 for Electrical Specifications WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All eq...

Page 14: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 15: ...mpact on the durability of the compressor However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rota...

Page 16: ...ked ON as long as the unit is in the Test Mode 2 While in Test Mode 2 the compressor will NOT modulate but will be locked on at 100 to maintain the occupied room setpoint During the Test Mode 2 if the...

Page 17: ...ll be set at normal outdoor airflow Below 55 degrees the outdoor fan will modulate to maintain a 300 psi head pressure This will act as a low ambient fan cycling control The output may go to zero outp...

Page 18: ...s expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize Recycling the wall...

Page 19: ...harge resulting in a liquid subcooling as shown in Table 2 If charge is in doubt reclaim and recharge to factory nameplate charge Values are at 100 capacity TABLE 2 REFRIGERANTCHARGE l e d o M d e t a...

Page 20: ...1 9 6 4 0 3 1 8 9 4 2 3 1 0 3 5 5 3 1 5 6 5 e e S e t o N 2 F 7 6 0 8 C 4 9 1 7 6 2 e d i S w o L e d i S h g i H 7 3 1 4 6 3 6 3 1 3 8 3 6 3 1 4 0 4 6 3 1 7 2 4 7 3 1 3 5 4 8 3 1 1 8 4 9 3 1 1 1 5 1...

Page 21: ...A N 6 A N A N 0 1 A N A N A N A N A N 0 1 A N A N 0 1 A N A N A N Z 0 S 1 V L 3 W 1 V R 3 W 6 0 S 9 0 S 3 0 6 8 0 2 0 3 2 0 2 2 3 0 5 0 0 2 1 1 1 9 1 7 3 6 4 0 3 0 4 0 5 0 1 8 8 0 1 0 1 0 1 A N A N A...

Page 22: ...7 0 0 5 0 2 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 2 1 4 4 1 0 5 9 0 4 5 1 5 2 6 0 5 2 1 5 0 4 5 0 0 4 8 3 2 6 3 0 0 2...

Page 23: ...n o i t p i r c s e D 5 1 C M C e s a h P 1 V 0 3 2 t i K t r a t S X X 3 D A F B d r a d n a t S r e p m a D r i A h s e r F c i r t e m o r a B X 3 P O B e t a l P f f O k n a l B X 5 D A F B d r a...

Reviews: