Manual 2100-790
Page
39 of 49
TABLE 13
Electrical Specifications
Model
Rated
Volts
&
Phase
No. Field
Power
Circuits
Single Circuit
Dual Circuit
j
Minimum
Circuit Ampacity
k
Maximum
External Fuse
or Circuit
Breaker
j
Minimum
Circuit
Ampacity
k
Maximum
External Fuse
or Circuit
Breaker
Ckt.
A
Ckt.
B
Ckt.
A
Ckt.
B
W18HY-A00, A0Z
A04
A08
230/208-1
1
1
1
16
37
58
20
40
60
W24HY-A00, A0Z
A04
A08
230/208-1
1
1
1 or 2
22
43
63
25
45
70
22
42
25
45
W24HY-B00, B0Z
B05
230/208-3
1
1
15
30
20
30
W24HY-C00, C0Z
C05
460-3
1
1
8
15
15
15
W30HY-A00, A0Z
A05
A10
230/208-1
1
1
1 or 2
24
50
76
30
50
80
24
52
30
60
W30HY-B00, B0Z
B05
B09
230/208-3
1
1
1
17
32
44
20
35
45
W30HY-C00, C0Z
C05
C09
460-3
1
1
1
9
16
22
15
20
25
W36HY-A00, A0Z
A05
A10
A15
230/208-1
1
1
1 or 2
1 or 2
27
53
79
84
35
60
80
90
27
32
52
52
35
35
60
60
W36HY-B00, B0Z
B05
B09
230/208-3
1
1
1
20
35
47
25
35
50
W36HY-C00, C0Z
C05
C09
460-3
1
1
1
11
18
24
15
20
25
j
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing.
CAUTION
: When more than one field power circuit is run through one conduit, the
conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than
three (3) current carrying conductors are in a raceway.
k
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Maximum KW that can operate with the heat pump on is 10KW. Full heat available during emergency heat mode.
NOTE:
The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 60335 calculations for MOCP (branch-
circuit conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective device (circuit
breaker) in this model may be lower than the maximum UL 60335 allowable MOCP value, but still above the UL 60335 minimum
calculated value or Minimum Circuit Ampacity (MCA) listed.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.