Manual 2100-721B
Page
46 of 54
TABLE 13
W30G4 Indoor Blower Performance @ 230 AND 460 VOLTS
Recommended W30G cooling airflow range at rated 900 CFM @ 0.15 ESP (WC) is 750 - 1150 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
Dehumidification coil adjustment
– Reduce airflow by 35 CFM for dehumidification coil installed
SG-3, RG-3, non-ducted application adjustment
– Reduce airflow by 100 CFM for SG-3 and RG-3 installations
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
90,000 BTU Input
81,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
850
1022
1157
1281
0.1
769
953
1098
1237
1375
1237
0.2
688
883
1038
1188
1329
1188
0.3
606
812
975
1134
1279
1134
0.4
523
739
910
1075
1225
1075
1225
0.5
439
664
843
1011
1168
1011
1168
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
68,000 BTU Input
61,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
850
1022
1157
1281
0.1
769
953
1098
1237
0.2
688
883
1038
1188
0.3
606
812
975
1134
1279
1134
0.4
523
739
910
1075
1225
1075
0.5
439
664
843
1011
1168
1011
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
45,000 BTU Input
41,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
850
1022
1157
1281
0.1
769
953
1098
1237
0.2
688
883
1038
1188
1329
1188
0.3
606
812
975
1134
1279
1134
0.4
523
739
910
1075
1225
1075
0.5
439
664
843
1011
1168
1011
1168