Manual 2100-721B
Page
45 of 54
TABLE 12
W24G4 Indoor Blower Performance @ 230 and 460 VOLTS
Recommended W24G cooling airflow range at rated 800 CFM @ 0.10 ESP (WC) is 700 - 910 CFM
Factory set on Rated speed for cooling and Medium speed for heating.
SG-3, RG-3, non-ducted application adjustment
– Reduce airflow by 100 CFM for SG-3 and RG-3 installations
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
90,000 BTU Input
81,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
670
928
1213
0.1
598
851
1141
1361
0.2
511
760
1055
1288
1373
1288
0.3
417
662
962
1214
1324
1214
0.4
323
564
870
1143
1278
1143
0.5
235
473
784
1077
1237
1077
1237
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
68,000 BTU Input
61,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
670
928
1213
0.1
598
851
1141
0.2
511
760
1055
1288
0.3
417
662
962
1214
0.4
323
564
870
1143
1278
1143
0.5
235
473
784
1077
1237
1077
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
45,000 BTU Input
41,000 BTU Input
Balanced
Rated
High
Medium
High
Medium
High
0
670
928
1213
0.1
598
851
1141
1361
0.2
511
760
1055
1288
0.3
417
662
962
1214
1324
0.4
323
564
870
1143
1278
1143
0.5
235
473
784
1077
1237