Manual 2100-631
Page
6 of 53
AIR CONDITIONING MODULE OPTIONS
1. IMPORTANT
The equipment covered in this manual is to be installed by
trained, experienced service and installation technicians.
All duct work or portions thereof not in the conditioned
space should be properly insulated in order to both conserve
energy and prevent condensation or moisture damage.
2. APPLICATION
This is a fan-assisted forced air gas furnace with
electric air conditioning for outdoor installation. A
fan-assisted furnace is equipped with an integral
mechanical means to draw products of combustion
through the combustion chamber and heat exchanger.
The furnace installation must conform with local
building codes and ordinances or, in their absence,
with the National Fuel Gas Code ANSI Z223.1 or
CAN/CGA-B149.1, latest edition, and the National
Electrical Code ANSI/NFPA-7 or CSA C22.1, latest
edition. It is the personal responsibility and obligation
of the purchaser to contact a qualified installer
to assure that installation is adequate and is in
conformance with governing codes and ordinances.
3. DUCT WORK
The unit is designed for use with or without duct
work. See Warning on Page 10. Flanges are provided
for attaching the supply and return ducts. These
instructions explain the recommended method to install
the air cooled self-contained electric air conditioning
and gas heating unit and the electrical wiring
connections and gas piping to the unit. The refrigerant
system is completely assembled and charged. All
internal wiring is complete.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
heating/cooling system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
All duct work, supply and return, must be properly sized
for the design airflow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.
Refer to Tables later in this Manual for maximum static
pressure available for duct design.
CAUTION
During the initial firing of the burners there will probably be some amount of smoke issued to the
circulating air stream as the result of residual oil burning off of the heat exchanger tubes. This oil
is required during the forming process of the stainless steel heat exchanger tubes to facilitate the
bending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. In vapor
form this may be irritating to the eyes or could cause headaches. This is a one time occurrence,
and ventilation of the space may be required depending upon the space being conditioned.
STD – Standard equipment.
CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break timer. On initial power up, or any
time the power is interrupted, the delay-on-make will be 2 minutes plus 10% of the delay-on-break setting. There is no
delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high
and/or low pressure controls, and a 2-minute timed bypass for low pressure control.
HPC High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See Note
.
LPC Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See Note
.
LAC Low ambient control permits cooling operation down to 0°F.
CCM
HPC
LPC
LAC
Factory Installed
Code
Field Installed
Part
STD
STD
STD
X
N/A
STD
STD
STD
•
H
CMA-28