33. W**G DEHUMIDIFICATION RELAY LOGIC BOARD
DEHUMIDIFICATION RELAY LOGIC BOARD
Cooling takes precedence over dehumidification. A cooling call cancels dehumidification.
First stage heating cancels dehumidification.
If jumper on RLB is set to “1-2 full-time dehumidification”, outputs will energize. This is the factory default
setting. If jumper is set to “2-3 occupied dehumidification only”, outputs will be off.
24V Terminal Block Connections
G
Y
3
W1
Outputs from Board
Inputs to Board
G
Y
D
W2
G1
TWV
YO
Cooling Mode
Unoccupied
X
X
X
X
Cooling Mode
Occupied
X
X
X
X
Cooling Mode
With Dehum
X
X
X
X
X
1st Stage Heating
Unoccupied
X
X
1st Stage Heating
Occupied
X
X
1st Stage Heating
With Dehum
X
X
X
2nd Stage Heating
Unoccupied
X
X
2nd Stage Heating
Occupied
X
X
2nd Stage Heating
With Dehum
X
X
X
Dehumidification
Unoccupied
X
Dehumidification
Occupied
X
X
X
X