TABLE 13
W42G INDOOR BLOWER PERFORMANCE @ 230 AND 460 VOLTS
Recommended W42G cooling airflow range at rated 1300 CFM @ .35 ESP (WC) is 1500 - 1030 CFM
Factory set on Medium Speed for heating and cooling
Voltage adjustment
– Reduce airflow by 130 CFM for 208 Volt
Top outlet adjustment
– Increase airflow by 65 CFM for top outlet models
SG-5, RG-5, non-ducted application adjustment
– Reduce airflow by 170 CFM for SG-5 and RG-5 installations
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
125,000 BTU Input
113,000 BTU Input
High
Medium
Low
High
Medium
Low
High
Medium
Low
0.0
- - -
1540
1140
- - -
1640
1230
- - -
1640
1230
0.1
- - -
1480
1090
- - -
1580
1180
- - -
1580
1180
0.2
- - -
1410
1030
1880
1510
- - -
- - -
1510
1090
0.3
- - -
1360
- - -
1760
1460
- - -
- - -
1460
- - -
0.4
- - -
1250
- - -
1670
1340
- - -
1670
1340
- - -
0.5
1460
1150
- - -
1560
1240
- - -
1560
1240
- - -
0.6
1340
1040
- - -
1430
1130
- - -
1430
1130
- - -
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
100,000 BTU
90,000 BTU Input
High
Medium
Low
High
Medium
Low
High
Medium
Low
0.0
- - -
- - -
1190
- - -
1690
1280
- - -
1690
1280
0.1
- - -
1530
1140
- - -
1630
1230
- - -
1630
1230
0.2
- - -
1460
1070
- - -
1560
1160
- - -
1560
1160
0.3
- - -
1410
1050
1810
1510
1140
- - -
1510
1140
0.4
- - -
1300
- - -
1720
1390
- - -
1720
1390
1020
0.5
1510
1200
- - -
1610
1290
- - -
1610
1290
970
0.6
1390
1090
- - -
1480
1180
- - -
1480
1180
- - -
ESP
Inches
H
2
O
COOLING MODE
MANUAL FAN and HEATING MODE
Wet Coil
75,000 BTU Input
68,000 BTU Input
High
Medium
Low
High
Medium
Low
High
Medium
Low
0.0
- - -
- - -
1240
- - -
1740
1330
- - -
1740
1330
0.1
- - -
- - -
1190
- - -
1680
1280
- - -
1680
1280
0.2
- - -
1510
1120
- - -
1610
1210
- - -
1610
1210
0.3
- - -
1460
1100
1860
1560
1190
- - -
1560
1190
0.4
- - -
1340
- - -
1770
1440
1070
- - -
1440
1070
0.5
- - -
1260
- - -
1660
1340
970
1660
1340
970
0.6
1440
1140
- - -
1530
1230
- - -
1530
1230
- - -