Bard W18HB-A Installation Instructions Manual Download Page 7

Manual 2100-703 

Page 

7 of 40

Fire hazard.

Maintain minimum 1/4" clearance between the 
supply air duct and combustible materials in 

the first 3' of ducting.
Failure to do so could result in fire causing 

damage, injury or death.

!

WARNING

directly in front of the unit return grilles and registers. 
Bard recommends at least 2' between solid objects 
and return grilles or registers. Ductwork may be used to 
ensure proper air circulation and all provided ductwork 
guidelines and clearances must be followed. Non-
ducted applications must use a return louver grille 
installed over the return opening inside the room. 

Ducted Applications

Field fabricated supply and return duct work may be 
installed inside the structure being conditioned. A short 
supply and/or return stub duct may be connected to the 
unit supply and return flanges before unit installation to 
help with duct connections inside the structure. Supply 
and return ducts must be properly sized for the design 
airflow requirement of the equipment. Air Conditioning 
Contractors of America (ACCA) is an excellent guide 
to proper sizing. All duct work or portions thereof not 
in the conditioned space should be properly insulated 
in order to conserve energy, reduce heat conductivity, 
and prevent condensation or moisture damage. Refer to 
Maximum External Static Pressure (ESP) of Operation 
Table 17 on page 36. Design the duct work according 
to methods given by the Air Conditioning Contractors 
of America (ACCA). When duct work is installed 
in unheated spaces, it should be insulated with a 
minimum of 1" of insulation. Use insulation with a 
vapor barrier on the outside of the insulation. Flexible 
joints should be used to connect the duct work to the 
equipment in order to keep the noise transmission to a 
minimum. Ducts through the walls must be insulated 
and all joints taped or sealed to prevent air or moisture 
from entering the wall cavity.
The unit itself is suitable for 0" clearance, but the 
supply air duct flange and the first 3' of supply air duct 
require a minimum of 1/4" clearance to combustible 
material for model series W30 and W36. However, it 
is generally recommended that a 1" clearance is used 
for ease of installation and maintaining the required 
clearance to combustible material. See Figures 3A and 
3B on pages 10 and 11 for details on opening sizes.

Free Blow Applications

Some installations may not require extensive supply 
duct work throughout the structure and are referred 
to as free blow applications. A short field-fabricated 
supply duct must be used in the wall cavity to 
transition between the supply collar on the unit and 
the supply louver grille in the room. The duct must 
be properly insulated in order to conserve energy, 
reduce heat conductivity and prevent condensation or 
moisture damage. All joints must be taped or sealed to 
prevent air or moisture entering the wall cavity. Follow 
all clearances including distances to combustible 
materials and all instructions provided in this manual. 
A non-restrictive metallic supply air grille with 
deflectors is required for free blow applications. Contact 
the local Bard distributor or visit www.bardhvac.com for 
ordering information.
A metallic return air grille is required for non-ducted 
applications. The spacing between louvers on the grille 
shall not be larger than 5/8". It is recommended that a 
Bard Return Air Grille Kit be installed that is designed 
specifically for the wall mount product. Contact the 
local Bard distributor or visit www.bardhvac.com for 
ordering information. A field-supplied return grille 
that meets the 5/8" louver criteria and does not cause 
the unit to exceed the maximum specified external 
static pressure (ESP) may be used. If using a return 
air filter grille, filters must be of sufficient size to 
allow a maximum velocity of 400 fpm. Filter return 
air grilles do not filter air being brought into the 
structure through ventilation options including fresh air 
dampers, ventilators, economizers and energy recovery 
ventilators. Be sure to install the return grille with the 
louvers pointed downward towards the floor. This will 
help ensure return air is drawn upward from the floor 
and improve air circulation in the room.

NOTE:

  If no return air duct is used, applicable 

installation codes may limit this cabinet to 

installation only in a single story structure.

Thermostat or Indoor Temperature Sensor Placement

The location and installation of the thermostat or 
temperature sensor that monitors indoor temperature is 
very important regarding unit operation. Avoid placing 
the thermostat in an area exposed to direct sunlight 
or air from doorways leading outdoors. Use a piece 
of insulating material to close off conduit openings 
or holes in the wall surface for wire entry into the 
thermostat or temperature sensor. This will help avoid 
non-conditioned air from entering the thermostat 
and effecting temperature and/or humidity readings. 
As common practice, the thermostat or temperature 
sensor should measure the temperature of the air 
being returned to the unit, and not the conditioned 
air being supplied by the unit. Placing the thermostat 
or temperature sensor near a return air opening will 
normally result in optimal unit performance.

Summary of Contents for W18HB-A

Page 1: ...UCTIONS W18HB A W24HB A W24HB B W24HB C W30HB A W30HB B W30HB C W36HB A W36HB B W36HB C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 703 Supersedes NEW Date 8 12 19 W24...

Page 2: ...Applications 7 Free Blow Applications 7 Thermostat or Indoor Temperature Sensor Placement 7 Unit Installation 8 Materials Tool List 8 Wall Preparation 8 Wall Mount Installation to Wall Surface 8 Wirin...

Page 3: ...ir Conditioning and Ventilating Systems Standard for Warm Air ANSI NFPA 90B Heating and Air Conditioning Systems Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct...

Page 4: ...n of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a var...

Page 5: ...utor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable ins...

Page 6: ...ensate removal from the outdoor coil when in heating mode The unit must be mounted high enough above grade to ensure that ice will not build up under the unit and come into contact with the base of th...

Page 7: ...upply duct must be used in the wall cavity to transition between the supply collar on the unit and the supply louver grille in the room The duct must be properly insulated in order to conserve energy...

Page 8: ...hind the unit that is against the wall A bottom mounting bracket attached to the skid for shipping is provided for ease of installation but is not required Review all requirements listed on unit label...

Page 9: ...Flashing Bottom Installation Bracket Back View T O E R S S S S S M 44 N Q B P L All dimensions are in inches Dimensional drawings are not to scale TABLE 1 Clearance Required for Service Access and Ad...

Page 10: ...ING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMM...

Page 11: ...ON ALL DUCT THE SIDE MOUNTING FLANGES AND UNDER HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION FROM COMBUSTABLE SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF WALL Wall Opening and Hole Location...

Page 12: ...intain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3 of ducting Failure to do so could result in fire causing damage injury or death WARNING SIDE SECTION V...

Page 13: ...IT RETURN AIR WALL STRUCTURE RETURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT F...

Page 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Page 15: ...m amperage operating condition For low voltage wiring an 18 gauge copper color coded cable is recommended See Table 7 on page 17 for more information Low Voltage Connections These units use a 24 volt...

Page 16: ...ooling capacity During dehumidification the indoor blower speed is reduced to help with the humidity removal A humidity sensing thermostat or humidistat is required to control dehumidification operati...

Page 17: ...on Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification Motion Sensor w Intelligent Learning Control BACnet compatible Ethernet compatible CS9BE THOCA 3 stage C...

Page 18: ...ode Wire required for dehumidification models only MIS 4063 0 10 VDC modulating C02 control signal for modulating ventilation 1 6 4 2 Do not connect A from thermostat if optional CO2 controller is use...

Page 19: ...entilation control Optional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized 4 Factory installe...

Page 20: ...r single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control pa...

Page 21: ...two of the supply leads to the unit Do not reverse any of the unit factory wires as damage may occur Condenser Fan Operation NOTE Certain models may be equipped with a low ambient control LAC and if...

Page 22: ...ped from the factory with the defrost time on the 60 minute pin If circumstances require a change to another time remove the wire from the 60 minute terminal and reconnect to the desired terminal Refe...

Page 23: ...behind the front vent door behind the filter access door If the unit is supplied with a factory installed vent package it will be plugged in but the jumper plug will also be tethered next to the conn...

Page 24: ...ol Board 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN...

Page 25: ...mer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat w...

Page 26: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Page 27: ...onnections Manual 2100 467H FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS I...

Page 28: ...failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output Model SelecTech Communication Diagnostics The SelecTech...

Page 29: ...refrigerant charge quantity The pressure tables on the following pages show nominal pressures for the units Since many installation specific situations can affect the pressure readings this informatio...

Page 30: ...389 150 414 152 440 154 467 156 495 157 524 159 554 161 585 162 618 TABLE 11B Heating Pressure Air Temperature Entering Outdoor Coil F Model Indoor Heating 0 5 10 15 17 20 25 30 35 40 45 47 50 55 60...

Page 31: ...Low Side High Side 125 302 131 327 136 352 141 377 145 403 148 430 151 458 153 486 154 514 155 543 155 573 155 609 W24HB 75 62 Low Side High Side 116 294 118 314 121 336 123 359 125 382 127 406 129 4...

Page 32: ...6 10 6 10 10 10 10 W36HB B00 B0Z B05 B09 l B15 230 208 3 1 1 1 1 19 36 47 51 25 40 50 60 10 8 8 6 10 10 10 10 W36HB C00 C0Z C05 C09 C15 460 3 1 1 1 1 11 19 25 26 15 25 25 30 14 12 10 10 14 12 10 10 Th...

Page 33: ...lt W24HB 800 10 700 950 W30HB 1000 15 900 1125 W36HB 1100 15 1000 1200 Rated CFM and ESP on factory speed connection NOTE Be sure to adjust the system static or blower speed to maintain airflows above...

Page 34: ...Cooling X X X X Balanced Climate On Full Load Cool X X X X X X Lo Med Hi On Balanced Climate Heat Pump Heating X X X X X Balanced Climate On Full Load Heat Pump Heating X X X X X X X Lo Med Hi On 1st...

Page 35: ...0 25 484 470 777 761 899 878 1017 981 0 30 452 438 758 742 880 856 988 944 0 40 392 378 716 701 831 806 912 860 0 50 335 321 664 655 767 747 814 761 W30HB 0 00 856 823 1083 1063 Dedicated electric he...

Page 36: ...10 A15 50 40 35 35 50 50 40 40 W30H W36H B00 0Z B06 B09 B15 50 40 30 30 50 50 35 35 W30H W36H C00 0Z C06 C09 C15 50 40 30 30 50 50 40 40 Models 240V 1 208V 1 240V 3 208V 3 460V 3 KW Amps BTUH Amps BTU...

Page 37: ...X EHW18H A08 X EHW2TH A04 X EHW2TH A08 X EHWH24 B06B X EHWH24B C06 X EHWH30 A05 X EHW30H A10 X EHWH36 A05 X EHW3TH A10 X EHW3TH A15 X EHWH03 B06 X EHW36H B06 X EHWH03 B09 X X EHW3TH B15 X EHW3TH C06...

Page 38: ...r Damper No Exhaust X X FAD BE2 Fresh Air Damper Barometric Exhaust X X CRV F2 Commercial Ventilator On Off Spring Return X X CRV V2 Commercial Ventilator 0 10V Spring Return X X ECON NC2 Economizer B...

Page 39: ...Manual 2100 703 Page 39 of 40 GRAPH 1 W18HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 2 W24HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Page 40: ...Manual 2100 703 Page 40 of 40 GRAPH 3 W30HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 4 W36HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Reviews: