Bard W18HB-A Installation Instructions Manual Download Page 6

Manual 2100-703 

Page 

6 of 40

INSTALLATION

Basic Installation Design and 

Application Planning

Successful unit installations require proper planning 
and site inspection before installation begins. Before 
installing the wall mount unit, make sure that all 
service and airflow clearances are met and that the 
unit can meet all applicable code and regulation 
requirements. Provide an inspection of both the inside 
and outside of the structure by reviewing floorplans and/
or visiting the installation site.

Wall Construction

The wall must be inspected to ensure that the weight 
of the unit can be supported. Be sure to review all 
applicable construction codes and regulations including 
seismic requirements. When inspecting wood frame 
walls, the wall construction must be strong and 
rigid enough to carry the weight of the unit without 
transmitting any unit vibration. It is important that 
the side unit wall mounting lags and optional bottom 
bracket are supported by structural members inside 
the wall cavity. Concrete block and brick walls must be 
thoroughly inspected to ensure that they are capable of 
carrying the weight of the installed unit. Metal buildings 
must contain structural components to support the unit 
weight. If heavily corrugated siding is present, it may 
need to be trimmed and flashed to provide a flat, even 
surface to attach and seal the unit to the wall.

Outdoor Area Inspection

Inspect the outdoor area of the jobsite or review 
construction plans and locate the area where the wall 
mount is to be installed. The outdoor area must be 
free from obstructions including fences, bushes and 
walls that will hinder unit operation regarding outdoor 
condenser airflow and unit serviceability. Do not 
install units in enclosed areas that limit the amount 
of ambient temperature airflow. Warm air will exit 
the front condenser section of the unit, and outdoor 
ambient temperature air must be able to enter side 
intake condenser openings of the unit. Portable or 
modular building placement must be in a way that the 
wall mount units have a constant supply of outdoor air 
for proper unit operation. Make sure that the service 
panels of the unit are accessible. Inspect wall surfaces 
for obstructions that could hinder unit installation 
and servicing including outdoor electrical conduits, 
junction boxes, wall drains, vent hoods, windows, doors, 
overhangs and posts.

NOTE:

 

Before mounting the heat pump unit, 

consideration should be given to the 

condensate removal from the outdoor coil when 

in heating mode. The unit must be mounted 

high enough above grade to ensure that ice 

will not build up under the unit and come into 

contact with the base of the unit. If allowed, 

this could cause damage to the coil and other 

base components. Also, be sure there are no 

air obstructions to the sides or front of the 

unit, such as bushes or fences, that would 

inhibit condenser airflow.

Condensate Water Drainage

Review all codes and requirements for unit condensate 
drainage. A clear, flexible PVC drain hose (3/4" ID, 1" 
OD) extends from the drain pan in the upper section of 
the unit and extends down to the unit base. An opening 
is supplied towards the back of the unit base for the 
drain hose to pass through, and the hose extends 1" 
to 2" below the unit base. Water removed from the 
indoor air (condensate) will be expelled from the unit 
in large amounts during cooling operation through the 
hose. Units running in cooling operation in cold outdoor 
below freezing conditions can cause the condensate 
to freeze after leaving the drain hose. In the event the 
drain hose is connected to a drain system of some type, 
it must be an open or vented type system to ensure 
proper drainage throughout seasonal use.

Indoor Ducted and Non-Ducted 

Applications

Air distribution inside the structure being conditioned 
plays an important role in making sure the area is 
a consistent temperature. Improper air distribution 
can result in areas being cooler or warmer, electrical 
equipment not receiving sufficient airflow or occupancy 
discomfort felt inside an area. Thermostat or indoor 
temperature sensor placement inside the area being 
conditioned also plays an important role in indoor 
climate control.

Indoor Supply Airflow

Indoor installation areas must provide a non-restrictive 
path for the conditioned supply air to leave supply 
grilles and registers. Inspect the area to ensure that all 
indoor portions of the room or rooms will have access 
to supply air. Ductwork may be used to ensure proper 
air circulation and all provided ductwork guidelines and 
clearances must be followed. Non-ducted applications 
must use a supply louver grille installed over the supply 
opening inside the room. Be sure to adjust supply 
deflectors to properly disperse the conditioned supply 
air to all parts of the room. Avoid closing sections of 
the supply grilles which would cause unneeded supply 
duct pressurization.

Indoor Return Airflow

A non-restrictive path for room air returning to the 
center section of the unit must be provided inside 
the room. Avoid placing objects including furniture, 
electronics equipment, equipment racks and cabinets 

Summary of Contents for W18HB-A

Page 1: ...UCTIONS W18HB A W24HB A W24HB B W24HB C W30HB A W30HB B W30HB C W36HB A W36HB B W36HB C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 703 Supersedes NEW Date 8 12 19 W24...

Page 2: ...Applications 7 Free Blow Applications 7 Thermostat or Indoor Temperature Sensor Placement 7 Unit Installation 8 Materials Tool List 8 Wall Preparation 8 Wall Mount Installation to Wall Surface 8 Wirin...

Page 3: ...ir Conditioning and Ventilating Systems Standard for Warm Air ANSI NFPA 90B Heating and Air Conditioning Systems Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct...

Page 4: ...n of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local regulations are at a var...

Page 5: ...utor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable ins...

Page 6: ...ensate removal from the outdoor coil when in heating mode The unit must be mounted high enough above grade to ensure that ice will not build up under the unit and come into contact with the base of th...

Page 7: ...upply duct must be used in the wall cavity to transition between the supply collar on the unit and the supply louver grille in the room The duct must be properly insulated in order to conserve energy...

Page 8: ...hind the unit that is against the wall A bottom mounting bracket attached to the skid for shipping is provided for ease of installation but is not required Review all requirements listed on unit label...

Page 9: ...Flashing Bottom Installation Bracket Back View T O E R S S S S S M 44 N Q B P L All dimensions are in inches Dimensional drawings are not to scale TABLE 1 Clearance Required for Service Access and Ad...

Page 10: ...ING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMM...

Page 11: ...ON ALL DUCT THE SIDE MOUNTING FLANGES AND UNDER HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION FROM COMBUSTABLE SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF WALL Wall Opening and Hole Location...

Page 12: ...intain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3 of ducting Failure to do so could result in fire causing damage injury or death WARNING SIDE SECTION V...

Page 13: ...IT RETURN AIR WALL STRUCTURE RETURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT F...

Page 14: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Page 15: ...m amperage operating condition For low voltage wiring an 18 gauge copper color coded cable is recommended See Table 7 on page 17 for more information Low Voltage Connections These units use a 24 volt...

Page 16: ...ooling capacity During dehumidification the indoor blower speed is reduced to help with the humidity removal A humidity sensing thermostat or humidistat is required to control dehumidification operati...

Page 17: ...on Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification Motion Sensor w Intelligent Learning Control BACnet compatible Ethernet compatible CS9BE THOCA 3 stage C...

Page 18: ...ode Wire required for dehumidification models only MIS 4063 0 10 VDC modulating C02 control signal for modulating ventilation 1 6 4 2 Do not connect A from thermostat if optional CO2 controller is use...

Page 19: ...entilation control Optional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized 4 Factory installe...

Page 20: ...r single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control pa...

Page 21: ...two of the supply leads to the unit Do not reverse any of the unit factory wires as damage may occur Condenser Fan Operation NOTE Certain models may be equipped with a low ambient control LAC and if...

Page 22: ...ped from the factory with the defrost time on the 60 minute pin If circumstances require a change to another time remove the wire from the 60 minute terminal and reconnect to the desired terminal Refe...

Page 23: ...behind the front vent door behind the filter access door If the unit is supplied with a factory installed vent package it will be plugged in but the jumper plug will also be tethered next to the conn...

Page 24: ...ol Board 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN...

Page 25: ...mer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat w...

Page 26: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Page 27: ...onnections Manual 2100 467H FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS I...

Page 28: ...failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output Model SelecTech Communication Diagnostics The SelecTech...

Page 29: ...refrigerant charge quantity The pressure tables on the following pages show nominal pressures for the units Since many installation specific situations can affect the pressure readings this informatio...

Page 30: ...389 150 414 152 440 154 467 156 495 157 524 159 554 161 585 162 618 TABLE 11B Heating Pressure Air Temperature Entering Outdoor Coil F Model Indoor Heating 0 5 10 15 17 20 25 30 35 40 45 47 50 55 60...

Page 31: ...Low Side High Side 125 302 131 327 136 352 141 377 145 403 148 430 151 458 153 486 154 514 155 543 155 573 155 609 W24HB 75 62 Low Side High Side 116 294 118 314 121 336 123 359 125 382 127 406 129 4...

Page 32: ...6 10 6 10 10 10 10 W36HB B00 B0Z B05 B09 l B15 230 208 3 1 1 1 1 19 36 47 51 25 40 50 60 10 8 8 6 10 10 10 10 W36HB C00 C0Z C05 C09 C15 460 3 1 1 1 1 11 19 25 26 15 25 25 30 14 12 10 10 14 12 10 10 Th...

Page 33: ...lt W24HB 800 10 700 950 W30HB 1000 15 900 1125 W36HB 1100 15 1000 1200 Rated CFM and ESP on factory speed connection NOTE Be sure to adjust the system static or blower speed to maintain airflows above...

Page 34: ...Cooling X X X X Balanced Climate On Full Load Cool X X X X X X Lo Med Hi On Balanced Climate Heat Pump Heating X X X X X Balanced Climate On Full Load Heat Pump Heating X X X X X X X Lo Med Hi On 1st...

Page 35: ...0 25 484 470 777 761 899 878 1017 981 0 30 452 438 758 742 880 856 988 944 0 40 392 378 716 701 831 806 912 860 0 50 335 321 664 655 767 747 814 761 W30HB 0 00 856 823 1083 1063 Dedicated electric he...

Page 36: ...10 A15 50 40 35 35 50 50 40 40 W30H W36H B00 0Z B06 B09 B15 50 40 30 30 50 50 35 35 W30H W36H C00 0Z C06 C09 C15 50 40 30 30 50 50 40 40 Models 240V 1 208V 1 240V 3 208V 3 460V 3 KW Amps BTUH Amps BTU...

Page 37: ...X EHW18H A08 X EHW2TH A04 X EHW2TH A08 X EHWH24 B06B X EHWH24B C06 X EHWH30 A05 X EHW30H A10 X EHWH36 A05 X EHW3TH A10 X EHW3TH A15 X EHWH03 B06 X EHW36H B06 X EHWH03 B09 X X EHW3TH B15 X EHW3TH C06...

Page 38: ...r Damper No Exhaust X X FAD BE2 Fresh Air Damper Barometric Exhaust X X CRV F2 Commercial Ventilator On Off Spring Return X X CRV V2 Commercial Ventilator 0 10V Spring Return X X ECON NC2 Economizer B...

Page 39: ...Manual 2100 703 Page 39 of 40 GRAPH 1 W18HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 2 W24HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Page 40: ...Manual 2100 703 Page 40 of 40 GRAPH 3 W30HB FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 4 W36HB FAD NE2 3 W O Exhaust Ventilation Delivery...

Reviews: