background image

Manual 2100-411G
Page

6 of 23

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be
checked for external signs of shipping damage.  If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting  inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation.  Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 3 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

Any heat pump is more critical of proper operating
charge and an adequate duct system than a straight air
conditioning unit.  All duct work, supply and return,
must be properly sized for the design airflow
requirement of the equipment.  Air Conditioning
Contractors of America (ACCA) is an excellent guide to
proper sizing.  All duct work or portions thereof not in
the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.

1

Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

2

Based on 75°C copper wire.  All wiring must conform to NEC and all local codes.

3

These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors.  Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.

CAUTION:

When more than one field power conductor circuit is run through one conduit, the conductors must be derated.
Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors
are in a raceway.

TABLE  2

ELECTRICAL SPECIFICATIONS

T

I

U

C

R

I

C

E

L

G

N

I

S

T

I

U

C

R

I

C

L

A

U

D

l

e

d

o

M

d

e

t

a

R

&

s

t

l

o

V

e

s

a

h

P

.

o

N

d

l

e

i

F

r

e

w

o

P

s

t

i

u

r

i

C

3

m

u

m

i

n

i

M

t

i

u

c

r

i

C

y

t

i

c

a

p

m

A

1

m

u

m

i

x

a

M

l

a

n

r

e

t

x

E

r

o

e

s

u

F

t

i

u

c

r

i

C

r

e

k

a

e

r

B

2

d

l

e

i

F

r

e

w

o

P

e

r

i

W

e

z

i

S

2

d

n

u

o

r

G

e

r

i

W

e

z

i

S

3

m

u

m

i

n

i

M

t

i

u

c

r

i

C

y

t

i

c

a

p

m

A

1

m

u

m

i

x

a

M

l

a

n

r

e

t

x

E

r

o

e

s

u

F

t

i

u

c

r

i

C

r

e

k

a

e

r

B

2

d

l

e

i

F

r

e

w

o

P

e

z

i

S

e

r

i

W

2

d

n

u

o

r

G

e

z

i

S

e

r

i

W

.

t

k

C

A

.

t

k

C

B

.

t

k

C

A

.

t

k

C

B

.

t

k

C

A

.

t

k

C

B

.

t

k

C

A

.

t

k

C

B

Z

0

A

,

0

0

A

-

1

1

6

H

S

5

0

A

8

0

A

0

1

A

0

2

A

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1

2

r

o

1

2

r

o

1

2

r

o

1

2

r

o

1

2

5

4

7

8

8

8

9

0

1

1

0

6

0

0

1

0

1

1

0

2

1

0

2

1

6
4
3
3
2

0

1

8
6
6
6

-

-

-

2

5

2

5

2

5

8

5

-

-

-

6

2

2

4

2

5

2

5

-

-

-

0

6

0

6

0

6

0

6

-

-

-

0

3

0

5

0

6

0

6

-

-

-

6
6
6
6

-

-

-

0

1

8
6
6

-

-

-

0

1

0

1

0

1

0

1

-

-

-

0

1

0

1

0

1

0

1

Z

0

B

,

0

0

B

-

1

1

6

H

S

9

0

B

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1
1

6

3

0

6

0

5

0

7

8
6

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Z

0

C

,

0

0

C

-

1

1

6

H

S

9

0

C

3

-

0

6

4

3

-

0

6

4

1
1

8

1

2

3

5

2

5

3

0

1

8

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Summary of Contents for SH611

Page 1: ...NSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model SH611 Manual 2100 411G Supersedes 2100 411F File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 19...

Page 2: ...d CFM and Rated ESP 22 Table 9 Indoor Blower Performance 22 Table 10 Maximum ESP of Operation 22 Table 11 Pressure Table Cooling 23 Table 12 Pressure Table Heating 23 Getting Other Information and Pub...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...2 0 2 2 3 8 0 6 2 8 6 4 2 7 0 0 2 1 5 MODEL NUMBER CONTROL MODULES CAPACITY 61 5 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Dampe...

Page 5: ...Manual 2100 411G Page 5 of 23 FIGURE 1 UNIT DIMENSIONS SH611...

Page 6: ...an adequate duct system than a straight air conditioning unit All duct work supply and return must be properly sized for the design airflow requirement of the equipment Air Conditioning Contractors o...

Page 7: ...using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm FILTERS A 1 inch throwaway filter is supplied with each unit The filter slides into position...

Page 8: ...g would then be 32 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 3 4 Mount bottom mounting bracket 5 Hook top rain flashing...

Page 9: ...796 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Supply flange Side view of wall w...

Page 10: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Page 11: ...Manual 2100 411G Page 11 of 23 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 12: ...Manual 2100 411G Page 12 of 23 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Page 13: ...Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current Depending on the installed KW of electric heat there may be two field power circuits requir...

Page 14: ...pment at the time of manufacture is not designated for any specific destination of the country and are installed in areas not approaching the lower outdoor temperature range outdoor thermostats are no...

Page 15: ...ermostat This is done to maximize efficiency by utilizing the heat pump to bring the FIGURE 12 ELECTRIC HEAT HOLD OFF WIRING 15 20KW 1 PH 3 PH FIGURE 11 ELECTRIC HEAT HOLD OFF WIRING 4 10KW 1 PH 6 9KW...

Page 16: ...uired 5 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need to be energized Removing...

Page 17: ...or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Page 18: ...the system operating pressures can be observed Pressure tables can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure ta...

Page 19: ...r time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch...

Page 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Page 21: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Page 22: ...e t a R P S E d e d n e m m o c e R e g n a R w o l f r i A 1 1 6 H S 0 5 3 1 0 2 0 0 1 1 5 7 4 1 Subtract 08 static for 2 filter TABLE 9 INDOOR BLOWER PERFORMANCE CFM 230V 460V P S E H n I 2 O 1 1 6...

Page 23: ...i S h g i H 9 6 1 8 1 0 7 7 0 2 2 7 9 2 2 3 7 7 4 2 5 7 1 6 2 6 7 2 7 2 6 7 8 7 2 7 7 1 8 2 8 7 0 8 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 7 7 8 1 2 7 4 1 2 5 7 7 3 2 6 7 6 5 2...

Reviews: