background image

Manual 2100-411G
Page

19 of 23

DEFROST CYCLE

The defrost cycle is controlled by temperature and time
on the solid state heat pump control.  See Figure 14.

When the outdoor temperature is in the lower 40°F
temperature range or colder, the outdoor coil
temperature is 32°F or below.  This coil temperature is
sensed by the coil temperature sensor mounted near the
bottom of the outdoor coil.  Once coil temperature
reaches 30°F or below, the coil temperature sensor
sends a signal to the control logic of the heat pump
control and the defrost timer will start.

After 60 minutes at 30°F or below, the heat pump
control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops,
electric heaters are energized, and hot gas passing
through the outdoor coil melts any accumulated frost.
When the temperature rises to approximately 57°F, the
coil temperature sensor will send a signal to the heat
pump control which will return the system to heating
operations automatically.

If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.

The heat pump defrost control board has an option of
30, 60 or 90-minute setting.  All models are shipped
from the factory on the 60-minute pin.  If special
circumstances require a change to another time, remove
the wire from the 60-minute terminal and reconnect to
the desired terminal.  The manufacturer's
recommendation is for 60-minute defrost cycles.  Refer
to Figure 14.

FIGURE  14

DEFROST CONTROL BOARD

There is a cycle speed up jumper on the control.  This
can be used to reduce the time between defrost cycle
operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or
another 1/4 inch QC, to short between the 

SPEEDUP

terminals to accelerate the HPC timer and initiate
defrost.

Be careful not to touch any other terminals with the
instrument used to short the 

SPEEDUP

 terminals.  It

may take up to 10 seconds with the 

SPEEDUP

terminals shorted for  the speedup to be completed and
the defrost cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.

Otherwise, the timing will remain accelerated and run
through the 1-minute minimum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a 0° coil temperature.  This
can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the 

SEN JMP

 terminals (a

1/4 inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test the 

SEN JMP

jumper must be removed.  If left in place too long, the
compressor could stop due to the high pressure control
opening because of  high pressure condition created by
operating in the cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is likely no actual
frost on the outdoor coil in this artificial test condition.

There is also a 5-minute compressor time delay
function built into the HPC.  This is to protect
the compressor from short cycling conditions.
In some instances it is helpful to the service
technician to override or speed up this timing
period, and shorting out the 

SPEEDUP

 terminals

for a few seconds can do this.

Summary of Contents for SH611

Page 1: ...NSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model SH611 Manual 2100 411G Supersedes 2100 411F File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 19...

Page 2: ...d CFM and Rated ESP 22 Table 9 Indoor Blower Performance 22 Table 10 Maximum ESP of Operation 22 Table 11 Pressure Table Cooling 23 Table 12 Pressure Table Heating 23 Getting Other Information and Pub...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...2 0 2 2 3 8 0 6 2 8 6 4 2 7 0 0 2 1 5 MODEL NUMBER CONTROL MODULES CAPACITY 61 5 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Dampe...

Page 5: ...Manual 2100 411G Page 5 of 23 FIGURE 1 UNIT DIMENSIONS SH611...

Page 6: ...an adequate duct system than a straight air conditioning unit All duct work supply and return must be properly sized for the design airflow requirement of the equipment Air Conditioning Contractors o...

Page 7: ...using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm FILTERS A 1 inch throwaway filter is supplied with each unit The filter slides into position...

Page 8: ...g would then be 32 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 3 4 Mount bottom mounting bracket 5 Hook top rain flashing...

Page 9: ...796 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Supply flange Side view of wall w...

Page 10: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Page 11: ...Manual 2100 411G Page 11 of 23 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 12: ...Manual 2100 411G Page 12 of 23 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Page 13: ...Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current Depending on the installed KW of electric heat there may be two field power circuits requir...

Page 14: ...pment at the time of manufacture is not designated for any specific destination of the country and are installed in areas not approaching the lower outdoor temperature range outdoor thermostats are no...

Page 15: ...ermostat This is done to maximize efficiency by utilizing the heat pump to bring the FIGURE 12 ELECTRIC HEAT HOLD OFF WIRING 15 20KW 1 PH 3 PH FIGURE 11 ELECTRIC HEAT HOLD OFF WIRING 4 10KW 1 PH 6 9KW...

Page 16: ...uired 5 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need to be energized Removing...

Page 17: ...or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Page 18: ...the system operating pressures can be observed Pressure tables can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure ta...

Page 19: ...r time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch...

Page 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Page 21: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Page 22: ...e t a R P S E d e d n e m m o c e R e g n a R w o l f r i A 1 1 6 H S 0 5 3 1 0 2 0 0 1 1 5 7 4 1 Subtract 08 static for 2 filter TABLE 9 INDOOR BLOWER PERFORMANCE CFM 230V 460V P S E H n I 2 O 1 1 6...

Page 23: ...i S h g i H 9 6 1 8 1 0 7 7 0 2 2 7 9 2 2 3 7 7 4 2 5 7 1 6 2 6 7 2 7 2 6 7 8 7 2 7 7 1 8 2 8 7 0 8 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 7 7 8 1 2 7 4 1 2 5 7 7 3 2 6 7 6 5 2...

Reviews: