DUCT WORK

Any heat pump is more critical of proper operating
charge and an adequate duct system than a straight air
conditioning unit.  All duct work, supply and return,
must be properly sized for the design airflow
requirement of the equipment.  Air Conditioning
Contractors of America (ACCA) is an excellent guide to
proper sizing.  All duct work or portions thereof not in
the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

A 1/4 inch clearance to combustible material for the
first three feet of duct attached to the outlet air frame is
required.  See Wall Mounting Instructions and Figures
3, 4, 5 and 6 for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Some installations may not require any return air duct.
A metallic return air grille is required with installations
not requiring a return air duct.  The spacing between
louvers on the grille shall not be larger than 5/8 inch.

NOTE:  If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

Any grille that meets with 5/8 inch louver criteria may
be used.  It is recommended that Bard Return Air Grille
Kit RG2 through RG5 or RFG2 through RFG5 be
installed when no return duct is used.  Contact
distributor or factory for ordering information.  If using
a return air filter grille, filters must be of sufficient size
to allow a maximum velocity of 400 fpm.

FILTERS

A 1-inch throwaway filter is supplied with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the service door.  A 1-inch washable filter and a 2-inch
pleated filter are also available as optional accessories.
The internal filter brackets are adjustable to
accommodate the 2-inch filter by bending down the two
horizontal tabs on each filter bracket.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be
checked for external signs of shipping damage.  If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation.  Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 3 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

Summary of Contents for SH381D Series

Page 1: ...ION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Models SH381D SH431D SH491D Manual 2100 413G Supersedes 2100 413F File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506...

Page 2: ...ing Dimensions 25 Removal of Fan Shroud 25 Refrigerant Charge 25 Pressure Tables 27 Figures Figure 1 Unit Dimensions 6 Figure 2 Fresh Air Damper Assembly 8 Figure 3 Mounting Instructions 10 Figure 4 E...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Page 4: ...d 1 PhenolicCoatedEvaporator 2 PhenolicCoatedCondenser 3 PhenolicCoatedEvaporator andCondenser MODEL NUMBER REVISIONS OUTLET OPTIONS X Front Standard COLOR OPTIONS X Beige Standard 1 White 4 Buckeye G...

Page 5: ...A 1 m u m i x a M l l a n r e t x E r o e s u F t i u c r i C r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 e r i W d n u o r G e z i S A t k C B t k C A t k C B t k C A t k C B t k C A t k C...

Page 6: ...p u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T D 1 8 3 H S D 1 3 4 H S D 1 9 4 H S 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4...

Page 7: ...h each unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washable filter and a 2 inch pleated filter are...

Page 8: ...unched in the service panel If the unit is equipped with a fresh air damper assembly the assembly is shipped already attached to the unit The damper blade is locked in the closed position To allow the...

Page 9: ...g would then be 32 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain flashing...

Page 10: ...Manual 2100 413G Page 10 of 28 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 11: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Page 12: ...Manual 2100 413G Page 12 of 28 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 13: ...Manual 2100 413G Page 13 of 28 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Page 14: ...g current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab locate in th...

Page 15: ...Manual 2100 413G Page 15 of 28 FIGURE 8 SHXXXDX HOT GAS REHEAT DURING DEHUMIDIFICATION WITH CS2000A2 ENERGY MONITOR FULL TIME DEHUMIDIFICATION...

Page 16: ...Manual 2100 413G Page 16 of 28 FIGURE 9 SHXXXDX HOT GAS REHEAT DURING DEHUMIDIFICATION WITH PROGRAMMABLE THERMOSTAT FULL TIME DEHUMIDIFICATION...

Page 17: ...talled FIGURE 10 10KW 1 PH 6 9KW 3 PH TABLE 2 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u...

Page 18: ...ntrolled outputs are required 6 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need t...

Page 19: ...or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Page 20: ...can be energized by manual fan switch on subbase for constant air circulation Refer to Figure 14 HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to...

Page 21: ...river or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instr...

Page 22: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Page 23: ...0 48 0 49 0 50 0 51 0 52 0 53 0 54 0 55 0 56 0 57 0 58 0 59 0 60 0 61 0 62 0 63 0 64 0 65 0 66 0 67 0 68 0 69 0 70 0 71 0 72 0 73 0 74 0 39898 38757 37652 36583 35548 34545 33574 32634 31723 30840 29...

Page 24: ...d e i p u c c O X X X X X X X e d o M g n i l o o C m u h e D w X X X X X X g n i t a e H e g a t S t s 1 d e i p u c c o n U X X X X X X X g n i t a e H e g a t S t s 1 d e i p u c c O X X X X X X g...

Page 25: ...7 4 1 D 1 9 4 H S 0 5 2 1 0 2 0 0 1 1 5 7 4 1 REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge shown on...

Page 26: ...i o C 0 1 2 3 5 2 6 1 5 7 4 1 0 5 3 1 0 5 1 1 5 7 4 1 0 5 3 1 0 5 1 1 5 2 8 5 2 4 1 5 2 3 1 0 0 2 1 5 2 0 1 5 2 3 1 0 0 2 1 5 2 0 1 0 5 7 5 2 1 1 0 0 1 1 0 0 0 1 5 2 8 0 0 1 1 0 0 0 1 0 5 8 5 7 6 0 0...

Page 27: ...8 8 3 2 4 8 5 5 2 5 8 3 7 2 6 8 2 9 2 8 8 1 1 3 0 9 1 3 3 2 9 2 5 3 D 1 9 4 H S B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 2 7 8 9 1 2 7 3 1 2 8 7 8 2 2 3 7 4 4 2 4 7 0 6 2 5 7 8 7 2 7...

Page 28: ...Manual 2100 413G Page 28 of 28 FIGURE 14 BARD HEAT PUMP COOLING MODE CIRCUIT DIAGRAM FIGURE 15 BARD HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...

Reviews: