background image

Manual 2100-527E
Page

16 of 29

START UP

THESE UNITS REQUIRE R-410A
REFRIGERANT AND POLYOL
ESTER OIL.

GENERAL:

1. Use separate service equipment to avoid cross

contamination of oil and refrigerants.

2. Use recovery equipment rated for R-410A

refrigerant.

3. Use manifold gauges rated for R-410A (800 psi/250

psi low).

4. R-410A is a binary blend of HFC-32 and HFC-125.

5. R-410A is nearly azeotropic - similar to R-22 and

R-12.  Although nearly azeotropic, charge with
liquid refrigerant.

6. R-410A operates at 40-70% higher pressure than

R-22, and systems designed for R-22 cannot
withstand this higher pressure.

7. R-410A has an ozone depletion potential of zero,

but must be reclaimed due to its global warming
potential.

8. R-410A compressors use Polyol Ester oil.

9. Polyol Ester oil is hygroscopic; it will rapidly absorb

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used - even a deep

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug

compressor immediately after removal.  Purge with
small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard Manufacturing
recommends reclaiming, evacuating (see criteria above),
and charging to the nameplate charge.  If done correctly,
topping off the system charge can be done without
problems.

With R-410A, there are no significant changes in the
refrigerant composition during multiple leaks and
recharges.  R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound or
single component refrigerant).  The remaining
refrigerant charge, in the system, may be used after
leaks have occurred and then “top-off” the charge by
utilizing the pressure charts on the inner control panel
cover as a guideline.

REMEMBER:  

When adding R-410A refrigerant, it

must come out of the charging cylinder/tank as a liquid
to avoid any fractionation, and to insure optimal system
performance.  Refer to instructions for the cylinder that
is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1. Never mix R-410A with other refrigerants.

2. Use gloves and safety glasses, Polyol Ester oils can

be irritating to the skin, and liquid refrigerant will
freeze the skin.

3. Never use air and R-410A to leak check; the

mixture may become flammable.

4. Do not inhale R-410A – the vapor attacks the

nervous system, creating dizziness, loss of
coordination and slurred speech.  Cardiac
irregularities, unconsciousness and ultimate death
can result from breathing this concentration.

5. Do not burn R-410A.  This decomposition

produces hazardous vapors.  Evacuate the area if
exposed.

6. Use only cylinders rated DOT4BA/4BW 400.

7. Never fill cylinders over 80% of total capacity.

8. Store cylinders in a cool area, out of direct

sunlight.

9. Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge

lines or cylinders.  R-410A expands significantly
at warmer temperatures.  Once a cylinder or line is
full of liquid, any further rise in temperature will
cause it to burst.

        WARNING

Failure to conform to these practices
could lead to damage, injury or death.

Summary of Contents for S26H1

Page 1: ...S MODELS S26H1 S26H1D W26H1 S31H1 S31H1D W31H1 S38H1 S38H1D W38H1 S43H1 S43H1D W43H1 S49H1 S49H1D W49H1 S61H1 S61H1D W61H1 Manual 2100 527E Supersedes 2100 527D File Volume III Tab 17 Date 12 15 11 Ba...

Page 2: ...Specifications S H 25 Table 7B Electrical Specifications W H 26 Table 8 Indoor Blower Performance 27 Tables 9A Indoor Blower Performance S H 27 Tables 9B Indoor Blower Performance W H 27 Getting Other...

Page 3: ...Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Ham...

Page 4: ...efore the installation is made See Page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss gain calculation made according to methods of Air...

Page 5: ...act distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used app...

Page 6: ...tion and maintaining the required clearance to combustible material See Figure 3 for details on opening sizes 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figures 3A 3...

Page 7: ...a B f o s n o i s n e m i D L E D O M H T D I W W H T P E D D T H G I E H H Y L P P U S N R U T E R A B C B E F G I J K L M N O P Q R 1 S 2 S T 1 H 6 2 S 1 H 1 3 S 1 H 6 2 W 1 H 1 3 W 0 0 2 8 3 5 2 1...

Page 8: ...R 1 4 CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES...

Page 9: ...3 4 32 12 5 1 2 TOP FOAM AIR SEAL HEATER ACCESS RETURN AIR 2 Wall Opening and Hole Location View Right Side View 29 OPENING SUPPLIED Supply Opening NOTES SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF R...

Page 10: ...This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible...

Page 11: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...ircuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high st...

Page 14: ...the correct set points NOTE The additional LAB low ambient bypass relay is required to prevent heater operation during low temperature cooling operation OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figu...

Page 15: ...mostat This is done to maximize FIGURE 11 ELECTRIC HEAT HOLD OFF WIRING 15 20KW 1 PH 3 PH FIGURE 10 ELECTRIC HEAT HOLD OFF WIRING 4 10KW 1 PH 6 9KW 3 PH efficiency by utilizing the heat pump to bring...

Page 16: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 17: ...l minutes the compressor s internal protector will trip All three phase ZP compressors are wired identically internally As a result once the correct phasing is determined for a specific system or inst...

Page 18: ...e system to heating operation automatically after 10 minutes The heat pump defrost control board HPC has an option of 30 60 or 90 minute setting All models are shipped from the factory on the 60 minut...

Page 19: ...29 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIG...

Page 20: ...i r o s s e r p m o c Y o N 1 1 y l l a n i f d n a r o t i n o M e s a h P n o n o i t c e s e e s t i n u f o e s a h p t c e r r o c n i g n i r i w t a t s o m r e h t k c e h C g n i r i w t i n...

Page 21: ...6 4 0 7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5...

Page 22: ...ure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide fo...

Page 23: ...1 7 3 3 9 3 1 2 5 3 1 4 1 0 7 3 3 4 1 1 9 3 4 4 1 3 1 4 8 4 1 0 4 4 0 5 1 9 6 4 3 5 1 1 0 5 5 5 1 5 3 5 8 5 1 2 7 5 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 2 4 1 9 4 3 4 4 1 4 6 3 6...

Page 24: ...8 B W g e d 7 6 e d i S w o L e d i S h g i H 0 4 1 3 3 3 0 4 1 2 5 3 1 4 1 2 7 3 3 4 1 4 9 3 3 4 1 8 1 4 7 4 1 3 4 4 9 4 1 0 7 4 2 5 1 9 9 4 5 5 1 9 2 5 8 5 1 1 6 5 B D g e d 5 8 B W g e d 2 7 e d i...

Page 25: ...6 8 0 A 1 8 4 0 5 8 0 1 Z 0 B 0 0 B 1 H 1 3 S 3 0 6 8 0 2 0 3 2 1 9 1 5 2 0 1 0 1 6 0 B 1 7 3 0 4 8 0 1 Z 0 C 0 0 C 1 H 1 3 S 3 0 6 0 6 4 1 0 1 5 1 4 1 4 1 6 0 C 1 9 1 0 2 2 1 2 1 Z 0 A 0 0 A 1 H 8 3...

Page 26: ...1 7 4 0 5 8 0 1 Z 0 B 0 0 B 1 H 1 3 W 3 0 6 8 0 2 0 3 2 1 9 1 5 2 0 1 0 1 6 0 B 1 7 3 0 4 8 0 1 Z 0 C 0 0 C 1 H 1 3 W 3 0 6 0 6 4 1 9 5 1 4 1 4 1 6 0 C 1 8 1 0 2 2 1 2 1 Z 0 A 0 0 A 1 H 8 3 W 1 0 6 8...

Page 27: ...d e e p S h g i H l i o C t e W y r D d e e p S w o L l i o C t e W y r D 0 0 0 0 1 0 5 0 1 0 0 9 0 5 9 1 0 5 8 0 0 9 0 0 8 0 4 8 2 0 0 7 0 5 7 0 5 6 0 0 7 l e d o M P S E d e t a R 1 P S E x a M 2 y...

Page 28: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 29: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Reviews: